AA9 A NEW AND SIMPLIFIED SOLUTION TO 1UU INSULATION jacketing problems
WHEREVER ATMOSPHERIC CONDITIONS PRESENT SEVERE BECAUSE IT REQUIRES NO SPECIALIZED INSTALLATION
FEATURES:
FLEXIBLE: Tough and flexible over wide temperature range, trom minus 50'F to over 200'F.
FLAME-RESISTANT: Virtually incombustible. T/NA 100 has been tested and labeled by Underwriters' Laboratories with a Flame Spread Rating ot 25 (In combustible).
WEATHER-RESISTANT: Exposed surface is "Tedlar" and is essentially unaffected by ultra-violet light. Will not chalk, craze, or erode on exposure; will not corrode in industrial atmospheres.
CHEMICAL AND SOLVENT RESISTANT: Retains its form and strength even when boiled in strong acids and bases. Unaffected at ordinary temperatures by many classes of common solvent, including hydrocarbons and chlorinated solvents. T/NA 100 is impermeable to greases and oils, is unaffected in strength and appearance by soil bacteria.
DESIGNED FOR MULTI-PURPOSE USE: Flexibility of material permits its use over large areas as well as narrow-diameter pipelines.
RESISTANT TO PUNCTURE AND ABRASION: Tough "Tedlar" surface is designed to take wear and tear.
EASY TO REPAIR: Damage can be readily repaired by patching with T/NA 100 Finishing Tape.
WHITE COLOR: Natural color is an attractive bright white.
MATERIAL SPECIFICATIONS:
Width of Roll___________ Length_________________ Area (Gross)____________ Approx. Shipping Weight
____ 35.5 in. 166.7 lin. ft 500.0 sq. ft ___60.0 lbs.
Note: Butt Strap Stock available in roils, 4 inches wide x 166.7 lineal feet
For Full Details Write:
INDUSTRIAL INSULATION DIVISION
The RUBEROID Co.
733 Third Avenue. New York 17, N.Y.
GAF 19874
RUBEROID T/NA 100s
MULTI-PURPOSE INSULATION JACKETING
T/NA 100 FIELD[ APPLICATION SPECIFICATION
1. SCOPE
1.1 This Specification covers field application of T/NA 100 Insulation Jacketing on rigid insulating materials such as Calcium Silicate. Cellular Glass and Glass Fiber, Urethane and Polystyrene Foam.
2. MATERIALS
2.1 T NA 100 Insulation Jacketing T/NA 100 Finishing Tape, 2* wide Metal Bands Lap Adhesive (a) Solvent type--Foster 82 x 32 (b) Emulsion type--Foster 82 x 29 Flashing Compound--Foster Foamseat 30-45 Mastic Finish--Foster Sealfas Mastic, White 31-99 Coating Finish--Foster Vitect Vinyl, White 57-15 Glass Cloth--Foster Mast-A-Fab Glass Cloth
3. PIPE-INSULATION APPLICATION
3.1 Pipe insulation shall be applied in standard approved manner with precautions taken to eliminate projections of bands or wires above the surface of the insulation. On lines operating above 600* F. insulation shall be applied in double layer with all joints staggered.
4. PIPE-JACKETING APPLICATION
4.1 The T NA 100 Jacketing shall be cut into sheets ap propriate to the insulation size with an allowance for a 2' minimum lap joint. Each sheet of jacketing shall be applied snugly to the insulation with an overlap of the adjacent sheet a minimum of 2*. On horizontal lines the lap shall be installed so that water runs over the lap joint rather than into it. On vertical lines the overlap should be outside the sheet below it.
42. METHOD A--Apply a uniform band of the selected lap adhesive a minimum of 2' wide to the asbestos face of the jacketing at the rate of 450 to 500 lineal feet per gallon. Position jacketing into place on the insula tion and press laps together firmly to assure good contact and check for tight seal.
4,3 METHOD B--Apply 2" T NA 100 Finishing Tape to all laps. Rub tape firmly after application to insure good contact.
4,4 METHOD C--(For hot lines only) Secure jacketing with aluminum bands, on 6* centers.
5. FITTINGS-INSULATION APPLICATION
5.1 Fittings and elbows shall be insulated with molded or fabricated insulation snugly fitted to the surface of the fitting. Thickness shall be at least equal to the adjacent pipe insulation.
6. FITTINGS-FINISH 6.1 All fittings shall be protected by an application by spray or trowel of Foster Sealfas Mastic, White applied to the insulation surface at the rate of 2 to 3 gallons per hundred square feet. Imbed into the mastic coat a layer of Mast-A-Fab Glass Cloth overlapping all seams a minimum of 2' and continuing onto the surface of the adjacent straight run piping a minimum of 2*. Apply a finish coat of Sealfas Mastic to the entire cloth surface at the rate of 4 to 5 gallons per hundred square feet. Apply T/NA Jacketing to overlap the fit ting finish and to assure a neat edge appearance.
6.2 Where desired T/NA 100 Jacketing and FinishingTape may be specified by the field in place of Mastic.
6-3 Where a glossy finish is required on fittings allow the Sealfas Mastic application to become thoroughly dry then apply two brush coats of Foster Vitect Vinyl, White to the mastic surface at the rate of 150 sq. ft. per gallon per coat.
7. FLASHING
7.1 At all protrusions and points where pipe hangers may protrude through jacketing, it is imperative that the flashing compound be applied to completely seal the opening to stop moisture penetration. Prior to applica tion wipe all surfaces clean and apply sufficient flash ing compound to extend over all intersecting surfaces to complete the seal. If a white finish is required at this point allow 8 hours drying of the flashing compound and apply a heavy flush coat of Sealfas Mastic. White.
8. PIPE HANGERS
8.1 Pipe hangers must not damage jacketing finish.
The RUBEROID Co. industrial insulation division . 733 third avenue, new york, n. y. 10017