Document JrMoJeJK3Jd3mGnZwVDL2KYYK
212
CHAPTER 10
1955 Guide-;
jrg
ture, is exposed to moisture damage--such as swelling, mold or discolora?~if
tion. Visible condensation may occur also in summer. It is often seen on||
basement concrete walls and floors which,are cooled by the earth and which;? being massive, tend to hold a constant temperature from day to day whilejf the weather dew-point temperature rises. When no water vapor is leased in the space, the dew point tends to equal that of the outside (though# it.is likely to lag when there is slight ventilation). At times the dewj;* point temperature rises above the temperature of Walls and floors and?; condensation results. If the basement is decorated the trouble may bel? serious. As an operating problem, the solution may be to reduce ventilation at times of high weather dew point, to warm the walls, or to dehumidify -
Fig. 5. Relative Humidity in Dwellings
the space. Warming the walls, a slow process at best, is generally accom--plished in favorable climates by excess ventilation. In a climate having low temperature at night, it may be feasible to ventilate only at night and; thus reduce the moisture content of hygroscopic materials which will thenact as a desiccant to retard the dew-point rise during the day. In basfr ment walls and floors insulation should be applied in the concrete or onits outside. Insulation placed on the inside of such walls eliminates visible;; condensation but fosters concealed condensation. The control of the latter.;, will be discussed. A practical and fully effective technique for such control has, however, not been developed. Usually, sub-surface dwellings should;; be designed for occupancy and should be dehumidified.
A similar situation is seen in dwellings with concrete floor slabs laid on . the ground where such slabs are not a part of the heating system. Inja. northern climate where high dew-point temperatures occur in summer, conj. densation or very high relative humidity may damage rugs which are theniselves contributors to the trouble since they reduce the floor slab tempera; ture. Slab floors above grade are not so serious a problem as floor slabs on grade but their response to air temperature change is slow. Faster warm ing is accomplished by the removal of rugs and abundant ventilation at proper times. In their design, floor slabs should have as low specific heat and as high thermal resistance as is consistent with other requirements;; Suitable insulation below the slab, especially well drained gravel, will help.;
Moisture in Building Construction
213
somewhat. A top surface cover of insulating value that is unaffected by water on its lower side would be desirable in the less favorable northern climates.
The avoidance of interior visible condensation is partly a construction and partly an operating problem. It is accomplished by reducing the in terior dew-point temperature or by raising the surface temperatures that are below the dew-point, or both. The dew-point temperature may be lowered by giving attention to the sources of the moisture, and in winter, may be controlled by ventilation, or possibly by some moisture absorption process. The temperatures of the inside room surfaces in winter may be increased by adding insulation to outside walls, by double glazing of win dows, by circulating warm air over the surface, or perhaps by direct heating of the surface. The most expedient method of overcoming a surface con densation difficulty will depend upon special conditions surrounding the problem.
CONCEALED CONDENSATION IN HEATED BUILDINGS
Water vapor produced in a building necessarily raises the vapor pressure above that outside thus providing the force that causes its diffusion into exterior walls. The amount of vapor pressure rise in the building depends on the amount of vapor produced and inversely on its chance to escape. The resulting balance may be expressed in terms of relative humidity if the inside temperature is 70 F. The relative humidity in heated buildings covers nearly all of the possible range. In zero weather it may be only 10 percent in an office, and 85 percent in an industrial plant where humidifi cation is required for a process, or where vapor release is incidental to a process. In residences the relative humidity in cold winter weather ranges from 10 percent to 60 percent, the latter figure applying to a very small, crowded and unventilated dwelling. A 40 percent level is considered representative of a substantial number of modem tightly constructed small houses although the average house relative humidity is probably below 25 percent. Surveys in residences show that the relative humidity increases as would be expected in warmer weather. Fig. 5 represents the results of one such survey.8
v iien water vapor is allowed to enter a wall and condensation occurs on its outer cold elements, it appears as frost or liquid. If the weather temperature rises frequently, frost melts and becoming liquid, is likely to penetrate capillary materials like wood, or run down when the surface is non-absorbing or is already saturated with water. In weather that is con tinuously cold for a long period, the frost may build back into a cavity or fibrous insulation and, when it reaches a warmer plane, will ran to lower,
cooler levels where it forms a mass of ice. Water seepage to the weather side may occur harmlessly in masonry walls when the weather is above freezing but water seepage into the building must obviously be avoided,
fn typical frame construction with wood sheathing which has large water absorbing capacity, seepage is rare and occurs only after a long period of steady cold weather. More generally, moisture accumulates in wood sheathing and siding through the colder months and reaches a peak in late
Winter, after which the drying of spring and summer completes the annual cycle. The average winter temperature and its duration are factors in the condensation problem. In Fig. 6 the map of the United States is divided in to condensation zones based on winter weather conditions. The solid lines
separating the zones follow state lines, and are those recommended by the