Document Jr7EO9Evz3jXOVvv7V5J2LQmB
ILE COPY
KERR-McGEE CORPORATION
INTERNAL CORRESPONDENCE
TO L. Carrico
from ^ Evan R. Goltra, M.D. Corporate Medical Direct
DATE July 31, 1986 subject Asbestos
f
bU
Attached are the results of the bulk asbestos samples that were collected from the Calhoun facility on July 16, 1986 by John Stauter and Janet Smith.
Your response to items 86-1 through 86-3 is required by August 21, 1986.
Should you have any questions concerning this report, please call me on x2909.
ERG/1h
attachment
Copies to:
G. Collins M. Moore J. Warn
CORPORATE
1
KERR-McGEE CORPORATION
INTERNAL CORRESPONDENCE
TO FROM
E. R. Goltra, M.D. Janet Smith0^
date July 31, 1986 subject Asbestos
On July 16, 1986, John Stauter and I visited the Dubach and Calhoun facili ties. Bulk asbestos samples were collected from the Calhoun facility. Table I summarizes the results which were phoned to Dubach on July ?!, 1986.
As a result of the survey, the following recommendations are submitted:
86-1
Calhoun Facility - All asbestos on the ground should be promptly
removed utilizing wet methods, personal protective equipment and proper disposal techniques. This methodology was discussed with the operator during the survey. Any exposed or deteriorated asbestos insulation should be covered to prevent release to the environment.
86-2 86-3
Calhoun/Dubach Facilities - Employees, such as insulators, who have the potential for intermittent exposures to asbestos during main tenance activities must wear, at a minimum, half mask respirators with HEPA filters. Attachment I lists an example of an appropriate half mask respirator.
Employees, who are required to wear respirators, must be fit tested and have medical examinations to determine that they are physically able to perform the work and use the equipment. A fit testing form is included in Attachment II. A Medical Evaluation form is found in Attachment III.
The Corporate Asbestos Handling policy, found in the Kerr-McGee Health Guidelines number 9.6.1, can be utilized as a reference for the asbestos recommendations.
Should you have any questions concerning this report or if you need assis tance in conducting fit testing for respirators, please contact me.
JCS/lh attachment
tfani
CORPORATE
Sample Number 86-071 86-073 86-074
86-076
TABLE I
Calhoun Facility Bulk Asbestos Survey
July 16, 1986
^Location Glycol Heater Insulation (N. Side)
Feed to Pumps
Insulation found on ground near Product Tank (site meter)
Feed to West Pump #1_
Test Results
Positive. This sample contains approximately 75? amosite asbestos.
Positive. This sample contains approximately 95% amosite asbestos.
Positive. This sample contains approximately 85% chrysotile asbestos along with approximately 2% fiberglass.
Positive. This sample contains approximately 25% amosite asbestos.