Document Jr1R7NmjV8kR5YEvB8JKJEaLZ

American Society of Heating and Ventilating Engineers Guide, 1931 Table 24. Coefficients of Transmission (U) of Brick Veneer Frame Walls Note.--These coefficients are expressed in B.t.u.per hour per square foot per 1 deg. fahr. DIFFERENCE IN TEMPERATURE BETWEEN THE AIR ON THE TWO SIDES AND ARE BASED ON AN OUTSIDE WIND EXPOSURE OF IS MILES PER HOUR. TVie values of U in this Table are basedon tbefollowinq Internal Conductivities or Conductances which are. expressed in b.t.u.per Ur. per Sq.Ft. per 1* F Wood (Yellow Roeor Fir) Plaster (Gypsum) 1.00 perl" 2.32 per I" Plaster board 3.73 per J Cork board Wood Lath 4 Plaster 2.80 per ( 0.30 per I" 2.00 asapptied RiqiA Insulation (Boardforot) 0.33 perl" . Flexible Insulation 0.27 perl" Cellular Gypsum (18*) Flaked Gypsum (24*) 0.53 per 1" 0.4 & per I" Brick. 5.00: pen 1" Typical Construction .SheatVimq 4"Brickv Plaster Ba.se _J0D13 Type of SVieotViinq Insulation between Studdino) Wood Lath Metal Lath 2T i kiaid I'Eiqid Plaster Insula- Insuiaboard -tiof? -tion CIko."rk board 2" Cork board A B C D E F. G 1 Hone 0.247 0.258 0.248 0.189 0.147 QI14 Q087 2 rWoodb 3 Plaited Gypsum fill (24*) a 0.094 0.095 0.094 0.084 0.075 0.065 0.058 Cellular Gypsum 0.108 o. no 0.108 0.095 0.083 0.072 0.064 4. if Flexible Insulation 0.147 0.150 0.147 0.125 0.105 0.087 0.076 5 4 Riqid None 0.209 0.217 0.210 0.144 0.133 0.106 0.090 <0 Insulation ( board form) Flaked Gypsum Fill (24*> a 0.087 0.089 0.087 0.079 0.071 0.062 0.056 7 Cellular Gypsum Fill (18*) a-c 0.100 0.102 0.101 0.089 0.079 0.068 0.061 8 Flexible Insulation 0.(33 0.134 0.133 0.114 0.098 0.082 0.072 a None 0.276 0.290 0.277 0.204 0.157 0.120 0.100 10 t Plaster board u 12 Flaked Gypsum Fill (24*) a 0.098 0.100 0.098 0.087 O.Q77 0.067 0.060 Cellular Gypsum FiU(l8^tt-c 0.113 0.115 0.113 0.100 0.086 0.074 .0.066 Flexible Insulation 0.157 0.161 0.157 0.131 0.109 0.010 0.079 eThickness of fill assumed 3H in-, based on 2 in. by 4 in. studding. . bBased on % in., the .actual thickness of. 1 in. or Ji in. sheathing. Building paper neglected. cThe coefficient used for cellular gypsum,:0.59 is for 18 lb. weight--freights as low as 12 lb. may be used. 60 Chapter 3--Heat Losses by Transmission- Table 25. Coefficients of Transmission (U) of Interior Walls and Partitions ,, ,,__these coefficients are expressed in B.t.u. per hour per square foot per I deg. fahr. nnmRENCE in temperature between the. air on the two sides and are based on still-air (no wind) Seditions on both sides. " plastered Frame Partitions Tbhaesevdaoluntebseofof lUloiwnmthci)s Table are Internal ductivities or Conductances On one side of Studdinq only which are expressed in 6.t.u. per Hr perSq.Ft.perl F Studdinq^ Plaster (Gypsum) J3J per l Plasterboard 3.73 per j WoodLath 4 Plaster 2.00 as appid insulation (BoardTorm) : ; :pio*t*r- Flexible Insulation 0.27 perl' Cork board , 0.30 perr Cellular Gypsum (18 )0.99 perl Flaked Gypsum , Dry (24*) 0.48 perl Plaster V, On both sides of Studdinq Studd mq v. piode''. TosbA. 1 m V* if : Insulation between Studdmq Ins ulatton-7 .Gypsum Fill . .between Studdinq Gypsum Fill y (>laster\', S*HJ, 1 TplaM`r} (Jr PlaxtfV . r fciqid z nsulation Hexible 'Board Insulation rorm) Cellular Gypsum Fill *_d Flaked Gypsum Fill* Wo. Plaster Base A i Meta'i ; icessiw 2 Wood Lath C 3 ^ Plaster boardf 't l :0-504T-. 4 ^Riqtd Insulation (Boardforrn)L o:3io 5 fRiqid Insulation (Board fcftrjfi' ; 0.211 6 IV Cork,board 0.149 7 2* Cork boardL 0.119 B 0328. ; 0:294 0.297 0.170 0.113 0.078 0.062 c' D E F 0.183 0.173 0.121 0.103 0.172 0.162 0.116 0.100 0.172 0.163 0.117 0.100 0.121 O.llfc 0.090 0.080 0.0&8 0.086 0.071 0.064 0.066 0.064 0.055 0.052 0.054 0.053 0.047 0.044 Plastered masonry partitions The values <& U mihisTable are based on "the following internal Conducttv tttes or Conductance which are expr per Ur. per Sq.ft-per lF Uollow Clay Tile (4*) 0.^3 per 4" ` Brick. 5-00 per 1" Mol low GypsumTile. OAb per 4" .Plam Walls (No Piaster') 01 Walls Plastered Wills Plastered one side both sides z. Gy( sum _ F las rer %1 X Gyp sum Plast r ( Wo. Wall Construction i 4" Hollow Clay Tile 2 4" Brick. 3 4' Hollow GypsumTile A 0.390 0.437 > 0213 B 0.360 0.400 0.258 c 0.333 0.367 0.244 . . aThe thickness of the gypsum fill is approximately 33$ in., the approximate 4 in. dimension of 2 in. by 4 in. studding. CMeta1 lath and plaster assumed /i. in, thick. ,. ^Piaster assumed K in', thick. dTir coefficient.used for cellular gypsum, 0.59 isfor 18 lb. weight--weights as low as 12 lb may he used. 61