Specification Data
Packaging (lbs per bag) Temperature Limit Coverage per 100 lbs Applied! dried 1" thick Approximate Ratio water to mix per 100 tbs Density, Dry
Base Material
Color
301 50
1400F 36 sq ft
15 gals
FINISHING CEMENTS
302 352 50 or 100 50 or 100
LOOOF 25 sq ft
1000F 19 sq ft
21 gals
12 gals
0352 50 or 100
1000F 19 sq ft
12 gals
INSULATING CEMENTS
85% Magnesia Superex
450
25 50 50
500 50
600F 55 sq ft
1900F 1800F 45 sq ft 50 sq ft
1800F 78 sq ft
42 gals 30 gals 30 gals 36 gals
18 pcf
hydraulic setting cement
20 pcf asbestos
20 pcf asbestos
30 pcf asbestos
20 pcf
12 pcf 8 pcf
10 pcf
mag. diatoma- mineral expanded
carbonate ceous
wool vermiculite
silica
light gray light gray
gray
gray white light gray golden
dries white
brown
gray
'The figures given In this table are average values obtained In accordance with accepted test methods.
FILLS
Fibrofil 60
Fil-lnsul 65
1800F
_
1000F
_
18 pcf (packing)
diatomaceous silica &
asbestos fiber
15 pcf (packing)
mineral fiber
MEAN TEMPERATURE. F
No. 301 No. 302 No. 352 No. 0352 No. 450 No. 500 85% Magnesia Superex Fibrofil Fil-lnsul
200 300 400 500 600 700 800 900 1000
-- .85 .86 XI .88 .90 .91 .93 .95
1.50 1.50 1.50 1.50 1.50 1.50 1.50 150 150 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10
.67 .72 .76 .81 .86 .91 .96 .99 1.01 .74 .79 .83 .88 .92 .97 1.02 1.06 1.11 .51 .54 .75 .77 .79 .82 .84 .86 .89 31 .94 .59 .61 .62 .63 55 .66 .68 .69 .70 .53 .58 .64 .70 .76 .83 .91 -- --
CONDUCTIVITY: BTU IN PER SO FT PER F PER HR
Navy 4S0 Cement meets MIL-C-2861, HH-C-168 and HH-l-00500, Type III.
85% Magnesia Cement meets HH-l-00500, Type I. Superex Cement meets HH-l-00500, Type V.
352 Asbestos Cement meets MIL-C-2908.
FINISH OVER BLOCKS
Asbestos cement (J-M No. 352, 0352 or 302) in two coats, or hydraulic setting cement (J-M No. 301) in one coat, shall be applied over hexagonal wire mesh stretched tightly over blocks and securely wired in place. The first coat of asbestos cement shall be left rough and allowed to dry thoroughly before applying second coat. Second coat of asbestos cement shall be mixed 2 to 1 by weight with portland cement and troweled
nooth. Insulating cement (J-M No. 450) may be subtituted for first coat in lieu of asbestos cement.
VALVES, FITTINGS AND FLANGES On piping 4" and larger, valves, fittings and flanges shall be insulated with pipe or block insulation of same material fabricated in sections, or pieces wired in place, and finished with a filling and smoothing coat of asbes tos cement. On pipe sizes smaller than 4" insulating ce ment (J-M No. 450) shall be used with an asbestos cement (J-M No. 352. 0352 or 302) finish. J-M No. 301 shall be applied in one coat over small pipe fittings.
ET-000096
JOHWS-MAMVTUt
8C48