1012 CHAPTER 49 1950 Guide The hair hygrometer consists of from one to several strands of hair with a mechanism whereby changes in length of the strands, due to changes in humidity, cause an indicator to move across a dial. In the recording instru ment, a pen is moved across and marks a moving paper ribbon, indexed in relative humidity. In a controller, or humidistat, the motion makes or breaks an electric contact governing the air conditioning equipment. Such devices require initial calibration and, for precise work, frequent recalibra tion or setting, especially if they are exposed to extremes of either high or low humidity. For continuous operation, with only slight changes in hu midity, some operators report satisfactory reproducibility of results. Electrolytic Hygrometers . The dampness, and therefore the electrical resistance of a salt film, varies with the humidity of the atmosphere to which the film is exposed, and at least two types of instruments based on this fact have been developed. The Dunmore hygrometer was originally designed for use in radio-sondes or small balloons, and means were devised whereby the device transmits humidity data back to earth in the form of a radio signal. In the more usual form, this hygrometer consists of a dual winding of small wire on a non-conducting tube. The whole is coated with an electrolytic film, usually containing a salt such as lithium chloride, which forms an electric connec tion between the windings. Means are provided for determining the elec trical resistance of the film, which is an indication of the humidity. In the radio-sonde, variations in the resistance of the film affect the frequency of an oscillating circuit. These hygrometers are usually calibrated by com parison with a wet and dry-bulb psychrometer. For calibration for some purposes, particularly for use at sub-zero temperatures, means have been provided for producing atmospheres of known humidity.41 Advantages of instruments of this type for 6ome scientific and industrial purposes are becoming apparent, and some forms of them are on the market. The Weaver type hygrometer is particularly useful for determining the humidity of air or other gas in pipes or closed vessels at various pressures and temperatures. It consists of a threaded' plug carrying a central elec trode insulated from the plug, except for a gelatinous electrolytic film. The film is exposed to the air or gas from the pipe or vessel, and provision is made for determining its electrical resistance. The hygrometer, or detector, is mounted in a manifold equipped with valves whereby the film can be alter nately exposed to the testgas, and to a standard gas having a known absolute humidity. The pressure of the standard gas is varied until contact with it establishes the same resistance in the film as the test gas, and the humidity of the test gas is then determined by computation based on the gas laws. Chemical Hygrometry The humidity of an atmosphere can be measured directly by extracting and weighing the water vapor from a known sample. For precise labora tory work, powerful desiccants such as sulphuric acid and phosphorus pentoxide are used for the extraction process, while for some purposes, calcium chloride, lithium chloride or silica gel are satisfactory. Freezing the water, vapor out of a measured stream of air or gas with solid carbon dioxide, and weighing the resulting ice, is a similar operation. A thermal conductivity method for gas analysis can be used for temperatures above 212 F, or for very low humidities.41 Instruments and Measurements 1013 HEAT TRANSFER THROUGH BUILDING MATERIALS Thermal Conductivity Use of the guarded hot plate apparatus for determining the thermal con-, ductivity (k value) of homogeneous materials was adopted by A.S.H.V.E. in 1942, and has become practically universal, and the apparatus is de scribed in an A.S.T.M. publication.4* 44 It consists essentially of an elec trically heated plate and two water cooled plates. Two identical speci mens or slabs of a material are required for a test, and one is mounted on each side of the hot plate. A cold plate is then pressed against the outside of each specimen by a clamp screw. Hot plate apparatus accommodating specimens on the order of one foot square and an inch or more thick, is common. The apparatus at the National Bureau of Standards takes speci mens 8 in. square, while plates as large as 3 ft square have been used. The heated plate is divided into two portions: the.central or measuring section, and the outer or guard section. During tests the two sections are main-, tained as nearly as possible at the same temperature, and the purpose of the guard section.is to minimize errors due to edge-effects. The electric energy required to heat the measuring section is carefully observed and, converted to Btu per hour, is divided by the area and the temperature gradient to obtain the conductivity of a material tested. Wall Conductances The thermal conductances (C values) of many walls can be satisfactorily estimated from the conductivities of their components and their dimensions, but some walls are complicated by the inclusion of metal, for instance, and tests for conductance are required. The apparatus is required to accom modate large specimens representing actual construction. The shielded hot box apparatus was developed for this purpose45 Specimens for the apparatus at the National Bureau of Standards are 5 ft long and 8 ft high, while others require different sizes, some larger, others smaller. The guarded hot box is described in the A.S.H.V.E. Standard Test Code for Heat Transmission through Walls.45 The apparatus consists essentially of three boxes: a cold box, cooled by a refrigerating machine; a hot box, heated electrically; and a metering box also heated electrically. Each box has an open side to be placed against the specimen. The cold box is clamped against one side of the specimen, and the hot box against the other. The hot box encloses the metering box and is kept at the same temperature to minimize heat exchanges to or from the metering box, except through the specimen. The electric energy necessary to heat the metering box is meas ured, converted to Btu per hour, and divided by the area and the tempera ture difference through the wall, from surface to surface, to yield the conductance of the wall. The transmittance or I/-value of the wall is then computed by means of the surface coefficients from Chapter 9. The Nicholls heat flow meter is sometimes useful for measuring steady heat flow through a wall or other building member." In essence, this meter consists of a plate or slab of material of known thermal resistance having attached thermocouples on both sides. For use, the device is pressed against or cemented to the wall to be tested. At steady state, the tempera ture difference through the slab, measured with the thermocouples, with the known thermal resistance of the slab, indicates the heat flow through the slab and hence, through the wall covered by it. For best results, such meters are calibrated by means of a guarded hot plate or other suitable apparatus. The chief precaution is to assure that the heat flow is steady at the time of measurement. '