HEATING VENTILATING AIR-CONDITIONING CUIDE 1943
Table 6. Coefficients of Transmission (V) of Frame Interior Walls
and Partitions'!
Coefficients are expressed in Bin per hour per square foot per degree Fahrenheit difference in temperature between the air on the two sides, and are based on still air (no wind) conditions on both sides.
TYPICAL CONSTRUCTION
sfumiL jrtW
s
rune it 0Ar*
Wall No.
DOUBLE PARTITION
(Finished on Both Sides or Studding)
Single
Pabtition
(Finish
on One Sms or
Studding)
Air Space' Between Studding
Flaked Between Studding
Rock Wool FHP Between Studding
Flexible
Insulation Between Studding (One Air Space).
Type of Wall
Wood Lath and Plaster On Studding Metal Lath and Plaster* On Studding Plasterboard ($$ in.) and Plaster*
On Studding
AB CD E 77 0-62 0.34 0.11 0.076 0.21 78 0.69 - 0.39 0.11 0.078 0.23 79 0.61 0.34 0.10 0.075 0.21
Plasterboard in:) and Plaster* On Studding--bright aluminum foil ce mented to plasterboard on surface nailed to studding . .
80
0.42
0.24
0.16
H in- Rigid Insulation and Plaster* On Studding
1 in. Rigid Insulation and Plaster* On Studding
1H in. Corkboard and Plaster* On Studding
2 in. Corkboard and Plaster* On Studding
81 0.35 82 0.23 83 . 0.16 84 0.12
0.18 0.12 0.081 0.063
0.0S3 0.066 0.052 0.045
0.063 0.054 0.044 0.038
0.14 0.097 0.070 0.057
Computed from factors marked by in Table 2. "Plaster on metal lath assumed % in. thick.
Thickness assumed 3H in.
"Plaster assumed H in. thick.
Table 7. Coefficients of Transmission (U) of Masonry Partitions'!
Coefficients are expressed in Btu per hour per squarefoot per degree Fahrenheit difference in temperature between the air on the two sides, and are based on still air (no wind) conditions on both sides.
. TYPICAL construction -pU/flttlrtT
i nTwre*-
No.
Plain walls
(No Plasteb)
Plastered on One Side
Walls Plastered on Bote Sides
Type of Wall
4-in. Hollow Clay Hie 4-in. Common Brick 4-in. Hollow Gypsum Hie 2-in. Solid Plaster
85 86 ,87 88
"Computed from factors marked by * In Table 2.
A 0.45 0.50 0.30
;--
108
B
0:42 0.46
0.28
---.
C 0.40 0.43 0.27 0.53
CHAPTER 4. HEAT TRANSMISSION COEFFICIENTS
109 X
separated from lath and plaster ceiling by 1 in. furring strips. Bright aluminum foll.cemented to plasterboard