508
CHAPTER 34
1960 Guide
in which these appliances are installed but the extent to which they must be equipped with reliable safety devices. For example, connection to an effective flue is mandatory. Furthermore, all such beating equipment must incorporate an automatic ignition pilot that will shut off gas supply to the main burner or burners in the event of pilot outage. If liquefied petroleum gas is used, the automatic pilot must cut off all gas supply to the appliance, including the pilot burner, in case the pilot flame becomes extinguished.
Rating and Sizing Gas Appliances
Input rating for a gas appliance is established by demon strating that the appliance can meet the Approval Require ments of the ASA. The tests are conducted at the A.GA. Testing Laboratories. Output rating is determined from the approved input and a minimum required efficiency stated in the Approval Requirements, and is the heat available at the nutlet.
Although gas-burning equipment usually is completely automatic, maintaining the temperature of rooms at a pre determined figure, there are some manually controlled in stallations. In order to overcome effectively the starting load and losses in piping, a manually-controlled gas boiler should have an output as much as UK) percent greater than the equivalent standard radiation which it is expected to serve.
Boilers under thermostatic control, however, are not sub ject to such severe pick-up loads and consequently, it is pos sible to use a lower selection factor. For a gas-fired boiler or furnace under thermostatic control, a factor of 20 to 25 per cent is usually sufficient for pick-up allowance.
In those installations, in mild climates where 100 percent outdoor air is used, furnaces should be of larger size in order to provide adequate capacity and quick pickup under in termittent heating conditions.
The factor to be allowed for loss of heat from piping will vary somewhat, the proportionate amount of piping in stalled being greater for small installations than for large ones. For selection factors to be added to installed radiation under thermostatic control, see Chapter 35.
Appliances used for heating with gas should bear the ap
proval seal of the A.GA. Testing Laboratories on the manu facturer's nameplate, together with the official input and output ratings. It is not permissible to operate a gas heating unit above its stated rating. It is necessary to reduce ratings at the rate of 4 percent for each 1000 ft elevation above sea level when appliances are installed in localities above 2000 ft elevation. Installations should be made in accordance with recommendations of the American Gas Association, as shown in current American Standard for Installation of Gas Ap pliances and Gas Piping, ASA Z2130, and in accordance with local regulations.
Sizing of Gas Piping
Piping for gas appliances should be of adequate size, and so installed as to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure be tween the point of supply (the meter) and the burner. The size of gas pipe required depends upon the following:
1. Maximum gas consumption to be provided. 2. Length of pipe and number of fittings. 3. Allowable loss in pressure from the outlet of the meter to the burner. 4. Specific gravity of the gas.
To obtain the cubic feet per hour of gas' required by the burner, divide the Btu input rate at which the burner will be adjusted, by the average Btu heating value per cubic foot of the gas.
Capacities of (Afferent sizes and lengths of pipe, in cubic feet per hour, with a pressure drop of 0.3 in. of water column for a gas of 0.60 specific gravity, are shown in Table 3. In adopting a 0.3 in. pressure drop, due allowance for an ordi nary number of fittings was made.
To convert the values given in Table 3 to capacities for another gas of different specific gravity, multiply the tabular values by the multipliers shown in Table 4.
Pipe capacities for gas'flow up to 100,000 cfb for various lengths of pipe are given in Fig. 16 which is based on a spe cific gravity of 0.60. The capacity at a given pressure loss for a different specific gravity may be obtained by multiply ing Fig. 6 capacities by a multiplier obtained from Table 4.
Toble 3 .... Capacity of Gas Piping--Cu Ft Per Hr
(At pnnm drop of 0.3 m. water. Specific gravity 0.60)
length at Pipe Ft
K
%
Iron Pipe Size ftPS) inches
W 1H 2 2H 3
10
132
278
520
1,050
1,600
3,050
4,800
8,500
20
92 190 350
730 1,100 2,100 3,300 5,900
30
73 152 285
590
890
1,650
2,700
4,700
63 130 245
500
760
1,450
2,300
4,100
50
56 115 215
440
670
1,270
2,000
3,600
60
50 105 195
400
610
1,150
1,850
3,250
46 96 180 370 560 1,050 1,700 3,000
80 43 90 170 350 530 990 1,600 2,800
90 40 84 160 320 490 930 1,500 2,600 38 79 150 305 460 870 1,400 2,500
125 34 72 130 275 410 780 1,250 2,200 150 31 64 120 250 380 710 1,130 2,000
L75
28
59 110
225
350
650
1,050
1,850
26 55 .100 210 320 610 9S0 1,700
From Arango* Stanford Installation of Oat Appliance* and Oat Pipinc, ASA Z21JO-1999.
4
12,000 9,700 8,300
7,400 6,800 6,200 5,800
5,400 5,100 4,500 4,100
3,800 3,500
. length of Pipe Ft
30 40
60 70 80
90 100 125 150
175 200
Automatic Fuel Burning Equipment
Table 4 .... Multipliers for Various Specific Gravities
(For Use With Tablm 3 and Fig. 16)
c~-gftf Gravity
MiAtipBer
Specific Gravity
MsiSpShr
0.35 0.40 0.45 0.50
0.55 0.60 0.65 0.70
0.75 0.80 0.85 0.90
1.31 1.23 1.16 1.10
1.04 1.00 0.962 0.926
0.895 0-867 0.841 0.817
1.00 1.10 1.20 1.30
1.40 1.50 1.60 1.70
1.80 1.90 2.00 2.10
0.775 0.740 0.707 0.680
0.655 0.633 0.612 0.594
0.577 0.565 0.547 0.535
COMMERCIAL AND INDUSTRIAL
GAS EQUIPMENT
No attempt can be made, due to space limitation, to de scribe or classify the varied types of equipment used for commercial and industrial applications. Much of the equip ment utilized is custom built to suit a particular process. Certain standard parts such as venturi and burner head sets, ring burners, proportional mixers, or compressors, are pur chased for assembly in existing equipment, usually by the installer. Furnaces to provide particular atmospheres or for annealing, soaking pits, metal melting, etc. are usually en gineered by industrial gas-equipment manufacturers.
Burners utilized in industrial equipment often operate at gas pressures higher than encountered in domestic usage. High-pressure gas provides flexibility of control required
509
in the production of constant temperatures. In addition, airgas ratios can be closely maintained under throttling con ditions, and heat liberation per cubic foot of combustion space is considerably greater Ilian can be achieved with lower pressures.
A few of the many base types of burners used are as follows: single-pipe high-pressure, proportional mixing, pre mix, two-pipe high-pressure, and atmospheric.
The single-pipe high-pressure burner system utilizes gas delivered to the orifice of a venturi at pressures from 10 to 50 prig. A constant pressure compressor, sometimes remotely plaiwd, is occasionally used'to increase the gas pressure. The velocity of the gas issuing from the orifice entrains primary air which is controlled by an air shutter on the venturi tube. An advantage of this system is that when the gas pressure is reduced (lowering the input) the air-gas ratio will remain constant over a fairly wide range.
In the proportional mixing burner, an enclosed type ven turi is used and high-pressure air is delivered through an ori fice. The resulting partial vacuum entrains the gas which is supplied through a zero pressure governor. When the air pressure is reduced, the amount of gas entrained is similarly reduced, thus maintaining a constant air-gas ratio over a wide fuel capacity range.
The pre-mix burner system embodies a compressor which mixes air and gas intimately and discharges the mixture through pipes to the burners where it is discharged through orifices and burned. The pre-mix compressor can be re motely installed and the mixture can be closely controlled.
The two-pipe high-pressure burner system utilizes both air and gas under pressure, both being delivered through orifices and mixed prior to delivery to the burner.
The atmospheric burner system is not commonly used. It consists of a burner supplied with gas at a pressure of 2
Q = FLOW in CUBIC FEET PER HOUR
Bated on Spftzgtea Friction Factor and 0.60 Specific Gravity. To convert for offcer specific gravity tee Table 4.
Fig? 16 .... Flow vs. Pressure Drop for low Pressure Natural Gos