Document JN2r9wwDkqQEQyO45dpzVVDmX
INDUSTRIAL HYGIENE MONITORING FOR
ASBESTOS
TO: D. L. Johnson, 511-5518
Computer Ref. W-1040
CC:
C. W. Carman, 725-105 G. F. Hurley, 701-334 C. R. Johnson, 511-2009 D. R. Paugh, 511-2009
P. A. Perry, 511-5583 C. E. Richardson, 511-2149 H. L. Robinson, 701-401 E. C. Shipley, 511-2009
PERSON MONITORED
G. H. Landers
Location #1 Powerhouse - Institutdlate
4/11/80
EXPOSURE RESULTS
Sample 1 2 3 4 5 6
Cone.
fibers > .35 5 gm/cm3
fibers > .42 5 pm/cm3
Sampling Time
60 minutes
105 minutes
fibers > 08 5 pm/cm3 80 minutes
fibers > .65 5 pm/cm3 38 minutes
Comments A.M. - Stripping insulation A.M. - Stripping insulation
P.M. - Stripping insulation
P.M. - Stripping insulation cleaning area.
Time-Weighted Average Concentration (TWA) 0.2 fibers > 5 urn/cm3 Ceiling Concentration __________________________
ALLOWABLE"EXPOSURE
TWA 2 fibers > 5 pm/cm3 <^051%)
Ceiling _OSHA
UCC
Other
UCC
Other
COMMENTS
Stripping suspected asbestos containing insulation from #2 boiler front and boiler front duct on second level of #1 Powerhouse at Institute. The last sample of the day was the highest concentration found. This may be attributed to the fact that they got in a hurry and didn't keep the insulation well wetted. Mr. Landers wore a disposable Norton dust respirator, and disposable coveralls during the stripping.
UCC 024720
oo
INDUSTRIAL HYGIENE MONITORING FOR
ASBESTOS
TO: D. L. Johnson, 511-5518
Computer Ref. W-1040
C. W. Carman, 725-105 G. F. Hurley, 701-334 C. R. Johnson, 511-2009 D. R. Paugh, 511-2009
PERSON MONITORED
D. K. Naylor
P. A. Perry, 511-5583 C. E. Richardson, 511-2149 H. L. Robinson, 701-401 E. C. Shipley, 511-2009
Location
#T Powerhouse -_______ Date Institute
4/11/80
EXPOSURE RESULTS
Sample 1 2 3 4 5
Cone.
fibers ^ .35 5 gm/cm: !
fibers ^ .81 5 gm/cnr `
.18 . 06
fibers ; > 5 gm/cm' * fibers : > 5 pm/cm' *
Sampling Time
60 minutes 105 minutes
87 minutes 49 minutes
Comments A.M. - Bagging insulation A.M. - Bagging insulation
P.M. - Bagging insulation P.M. - Bagging insulation
cleaning area
6
O
Time-Weighted Average Concentration (TWA) Q, 3 libers > 5 |tm/cm
Ceiling Concentration
ALLOWABLE EXPOSURE
TWA 2 fibers > 5 um/cm^ (fOSHA)
Ceiling
____
______
OSHA
UCC UCC
Other Other
COMMENTS
Bagging insulation that had been stripped from #2 boiler front and boiler front duct on second level of #1 Powerhouse at Institute. Mr. Naylor wore a disposable Norton dust respiratory and disposable coveralls during the bagging and cleanup. The insulation was placed in plastic bags for disposal and dropped from the second level to a truck below. At this point the full bags should be handled carefully It is suggested that they could be lowered on a rope to prevent the
UCC 024721
INDUSTRIAL HYGIENE MONITORING FOR _______ ASBESTOS
TO: D . L. Johnson, 511-5518
Computer Ref. w-1040
CC:
C . w. Carman, 725-105
G . F. Hurley, 701-334
C . R. Johnson, 511-2009
.D R. Paugh, 511-2009
P. A. Perry, 511-5583 C. E. Richardson, 511-2149 H. L. Robinson, 701-401 E. C. Shipley, 511-2009
PERSON MONITORED
B. M. Beckett
Location EXPOSURE RESULTS
#1 Powerhouse Institute
Date
4/11/80
Sample 1 2 3 4 5 6
Cone.
fibers > .48 5 pm/cm ^
fibers ' > 1.24 5 pm/cm *
Sampling Time
60 minutes
84 minutes
Comments A.M. - Stripping insulation A.M. - Stripping insulation
Time-Weighted Average Concentration (TWA) Not monitored long enough Ceiling Concentration ______to calculate TWA.
ALLOWABLE" EXPOSURE
TWA 2 fibers > 5 gm/cm3 (OSHA^)
Ceiling
___________
OSHA
UCC UCC
Other Other
COMMENTS
Stripping suspected asbestos containing insulation from #2 boiler front and boiler front duct on second level of #1 Powerhouse at Institute. Mr. Beckett was not monitored in the afternoon because he was trans ferred to another job. During the stripping he wore a disposable Norton dust respirator and disposable coveralls.
UCC 024722
INDUSTRIAL HYGIENE MONITORING FOR
ASBESTOS
TO: D. L. Johnson, 511-5518
Computer Ref. W-1041
CC:
C. W. Carman, 725-105 G. F. Hurley, 701-334 C. R. Johnson, 511-2009 D. R. Paugh, 511-2009
P. A. Perry, 511-5583 C. E. Richardson, 511-2149 H. L. Robinson, 701-401 E. C. Shipley, 511-2009
PERSON MONITORED ______________D. K. Milan___________________________________
Location
#1 Powerhouse - InstitutD&te
4/11/80
EXPOSURE RESULTS
Sample 1 2 3 4 5 6
Cone. fibers >
.69 5 gm/cm 3 fibers >
2.72 5 gm/cm 3
Sampling Time
68 minutes
27 minutes
Comments P.M. - Stripping insulation P.M. - Stripping insulation
Time-Weighted Average Concentration (TWA) Not monitored long enough
Ceiling Concentration
to calculate TWA.
ALLOWABLET EXPOSURE
TWA 2 fibers > 5 um/cm3 (JJSHa)
Ceiling _________________________
OSHA
UCC UCC
Other Other
COMMENTS
Stripping insulation from #2 boiler front and boiler front duct on second level of #1 Powerhouse at Institute* Mr. Milan wore a disposable Norton dust respirator and disposable coveralls during the stripping. The insulators got in a hurry toward the end of the day and didn't keep the insulation well wetted. This resulted in the last value being higher.
UCC 024723