Document JN1YnQjz54p7RoG122z8pvpMv
104
CHAPTER 5
1950 Guide
Table 2.
Approximate Unit Conductances foe Thermal Convection for Several Flow Systems*
Expressed in Convenient Empirical Form
Cass
System
J Unit Conductance Equation*
Forced Convection
-0Longitudinal flow In cylinders, turbulent
err
l. region. Fluid being heated*.
For (-^-) > 3000
he 0.0036
2. For longitudinal air flow In cylinders case 1
reduces too.
For (-5^-) > 3000
Ac - 0.00486 (l + 0.01/) ---j-
3. For longitudinal water flow in cylinders case 1
reduces too.
For (-^-) > 3000
4. Air flow normal to a single right circular
cylinder.
Ho - 0.45
+ 0.178 C*
5. Air flow over staggered pipe banks.
Ac - 0.061
j
6. Air flow over single spheres. 7. Air flow over plane surfaces. 8. Air flow normal to finned cylinders.
no Ac - 0.040 -^3-
0 <t < 250 F
he - 2 + 0.22 Vs
For V# < fps or Ac = 0.53 36 fps < V < 100 fps
/G
Ac " 6.2
)
0 <t < 250 F
)."
Fbbe Convection*
9. Single horizontal right circular cylinder in air. ho " 0.23 (^)"
10. Vertical surfaces in air.
ho - 0.3
U. Top surface of horizontal plates to air.
Ac - 0.4
*
12. Bottom surface of horizontal plates to air. Ac - 0.2
* Heat Transihission, by W. H. McAdams.
^ Fluid properties should be evaluated at the arithmetic mean fluid temperature, U Ocurfte* +1 fluid) dividedfby 2.
* These expressions are applicable to longitudinal flow in other than right circular cylinders provided the hydraulic radius is employed as the conduit dimension parameter. For non-circular cross-eections D d 4
d For low rates of heat transfer by free convection the exponent decreases towards zero, and for higher rates increases towards 0.33. The following equations employing an exponent equal to 0.25 are applicable in the intermediate range.
Heat Transfer
105
The heat transmission by free or natural convection for objects surnded by air can be conveniently expressed as in Equation 2a:
where
q, = heat transmission by convection, Btu per (square foot) (hour). C = a constant depending upon the shape of the surface. O = diameter of pipe or circular duct or height of vertical wall, inches.
(Effect of diameter or height becomes constant at 24 in.) T , = average of wall surface and surrounding air temperature, Fahrenheit
degrees absolute. I -- (, = temperature excess between wall surface and surrounding air, Fahren
heit degrees.
For horizontal cylinders, the value of C = 1.016 has been well estab lished by various investigations. For vertical plates, the value of C -- 1 394 has been fairly well established. Suggested values* of C for hori zontal plates warmer than the surrounding air are 1.79 when facing upward, and 0.89 when facing downward.
Problems in either forced convection or natural convection may be solved by the simple first-power equation if the convection coefficient is expressed
as a unit conductance:
qe = h9 A (tt -- U)
(2b)
where
qc = heat transmission by convection, Btu per hour. A = surface area, square feet. lx-- = temperature difference between the surface and the fluid, Fahrenheit
degrees. k,, -- unit conductance, from Table 2, Btu per (square foot) (hour) (Fahren
heit degree temperature difference.)
Thermal Radiation Equation The relation shown in Equation 3 is usually applicable to systems in
NOMENCLATURE AND DIMENSIONS FOR TABLE 2
cp = fluid unit heat capacity at constant pressure, Btu per (pound) (Fahrenheit degree).
D = cylinder diameter, feet. G = 3600 Vap = fluid mass velocity, pounds per (hour) (square foot of flow
cross-section). p = density, pounds per cubic foot. K = unit conductance for thermal convection, Btu per (hour) (square foot)
(Fahrenheit degree). k = unit thermal conductivity of the fluid, Btu per (hour) (square foot)
(Fahrenheit degree per one foot thickness). Ra = hydraulic radius of the flow cross-section = (Jow cross-section area per
wetted perimeter, feet. a = fin spacing, feet. I = average fluid film temperature, Fahrenheit degree. h--li = temperature difference surface to main fluid, Fahrenheit degree. V% = fluid velocity, feet per second. fi = fluid viscosity, pounds per (hour) (foot) = viscosity in centipoises X 2.42.