CHAPTER 15
1960 Guide
Fig. 6.... Propeller Fan Unit Heater--Horizontal-BJow
Type
Fig. 8-----Floor-Mounted Centrifugal Unit Heater--Cabinet
Type
Fig. 10 .... Suspended Centrifugal Unit Heater--Industrial Type--Bypass Controlled
Fig. 11.... Floor-Mounted Cen trifugal Unit Heater--Industrial
Type--VaWe Controlled
Fig. 12....Gas-Fired Propeller Fan Unit Heater
Fig. 13....Oil-Fired Centrifugal Fan Unit Heater--Floor Mounted
Unit Ventilators and Unit Heaters
229
ieal applications are ticket booths, watchmen's offices, fac same leaving air temperature as would be obtained from a
tory offices, locker rooms, and other isolated rooms scattered lower temperature heating medium.
over large areas. Electric units are particularly useful in
In order to obtain the desired air distribution and beat
isolated and untended pumping stations or pits where they diffusion, unit heaters are commonly equipped with direc
may be thermostatically controlled to prevent freezing tem tional outlets, adjustable louvers, or fixed types of diffusers.
peratures.
For a given unit with a given discharge temperature and
Type of Unit
outlet velocity, the mounting height and heat coverage can vary widely with the type of directional outlet, adjustable
Propeller fan units are usually used in free-delivery ap plications where the heating capacity and distribution re quirements can best be met by units of moderate output used singly or in multiples, and where filtration of the heated air is not required. Horizontal-blow units are usually asso ciated with low to moderate ceiling heights. Dovmrblow units are employed in high-ceiling spaces, and where floor and wall space limitations dictate an out-of-the-way loca tion for the heating equipment.
Industrial centrifugal fan units are applied where heating capacities and space volumes are large, or where filtration of the heated air, operation against static resistance, or the introduction of outdoor air are required. Down-blow or
louver, or diffuser employed. Other factors which may influence the beat coverage must
also be considered. Obstructions, such as columns, beams, partitions, or machinery, either in the discharge air stream or in the approach area to the unit, can reduce the heat
coverage substantially. The presence of strong drafts or other air currents will also reduce the coverage. Exposures such as large glass areas, or outside doors, especially on the windward side of the building, require special attention, and units should be arranged so as to blanket such exposures with a curtain of heated air which will intercept the cold drafts.
For area heating, horizontal-blow unit beaters in exterior
horizontal-blow units may be used, depending on the re quirement.
Cabinet unit heaters are used for applications where a more attractive appearance is desired. They are suitable for free delivery or low static pressure duct applications, may be equipped with filters, and can be arranged to dis charge either horizontally, or vertically up or down.
Location for Proper Heat Distribution
- zones should be located so as to blow along the exposure or toward it at a slight angle. Where possible, multiple units should be arranged so that the discharge air streams sup port each other and create a general circulatory motion in the space. Interior zones under exposed roofs or skylights should be completely blanketed. Down-blow units should be arranged so that the heated areas from adjacent units over lap slightly so as to provide complete coverage. For spot heating of individual spaces in larger unheated
Location of the units for proper heat distribution is of utmost importance in the application of unit heaters. In general, the units must be selected, located, and arranged so'as to provide complete heat coverage and at the same time maintain acceptable air motion and temperature-in the working or occupied zone. Proper application depends on a number of factors: the size, number, type and direction of blow of the units, the mounting height, the outlet velocity, the outlet temperature, the air volume and the type of di rectional outlet employed. Many of these factors are inter related, and manufacturers therefore publish data for spe cific units showing heat coverage and mounting heights for various outlet velocities and outlet arrangements. Such data should normally be consulted in selecting unit heaters for a particular application.
In general, however, mounting height and the area of heat coverage increase with increased air volume and outlet veloc
areas, single unit heaters may be employed, but allowance must be made for the inflow of unheated air from adjacent spaces and the consequent reduction in heat coverage. Iso lation of such spaces by partitioning or enclosure is always desirable from a heating standpoint.
Horizontal unit heaters should have their discharge out lets located well above the head level, and both horizontal and vertical units should be so applied that the heated air stream will be delivered to the occupied zone at tempera tures and velocities which are not objectionable. Where possible, units should be so located that the discharge air flow is into open spaces such as aisles and not directly on the occupants.
- Manufacturers' catalogs usually give suggestions for the best arrangements of various unit heaters, recommended mounting heights, heat coverages for various outlet veloc ities, final temperatures, and directional outlets.
ity, and decrease with increased final temperature. The mounting height may be governed by space limitations or by
Sound Level
the presence of equipment such as display cases or ma-
Consideration must be given to the problem of noise
-chinery. Both noise and air velocity in the occupied zone generated by unit heaters if they are applied in spaces hav
generally increase with increased outlet velocities and must ing a requirement for low sound levels. All unit heaters
therefore be considered.
generate some noise, and whether or not that noise will be y
The blow is dependent to a marked degree on the tem acceptable depends upon the type of space in which it is
perature of air leaving the heater as well as upon its velocity applied. For example, units with noise levels acceptable in
and volume. Increased final temperature will reduce the area a manufacturing plant might be too noisy for use in a
of heat coverage and the mounting height. Care must be show-room. A unit heater for a particular application must
exercised in_the application of down-blow unit heaters.-The __ therefore be.selected for 6atisfactory sound'level aswell as "
higher the mounting height, the lower must be the outlet for adequate heating capacity and proper heat distribution.
temperature of the air leaving the heater in order that the heated air will be forced down into the occupied zone.
Ratings of Unit Heaters
Since the outlet temperature of air from a unit heater in
It is standard practice to rate all types of unit heaters on
creases with the temperature of the heating medium, unit the basis of the amount of heat delivered by the air in Btu
heaters for high-pressure steam -or high-temperature hot per hour above an entering air temperature of 60 F.
water should be designed to produce approximately the
Steam. Bating of steam unit heaters has been standard-