Document JJz2LGnE4Rn2xO4KQBDXYq9rO
350
CHAPTER 25
1959 Guide
S3R=T^F = *-NOOSMQ CFOTNSTANT
_ s = OtoF tRaOlOaMrIeNa SoQf FbToundaries
a = AVG ENERGY ABSORPTION
* . coefficieOnFt ToOf tihSejM
THE ABSOLUTE SPL (OB RE 00002 MICROBAR) EQUALS THE SUM OF THE ORDINATE AND THE PWL (DB RE I0-13 WATT) OF THE NOISE SOURCE AT NORMAL ROOM TEMPERATURE AND
~ PRESSURE CONDITIONS. TIm Estaner's poi&on is of a dttfaoco r and an angle 9 with resped to (he dud opening. Q a determined from 0 and from the dad dhnenn'onj (see Fig. 18). To me the graph proceed as /or the example shown by the doffed Ime for r = 7 ft, O 2. and B " 2000 eq ft. The sowid pressure level in die room equals the m of the ordinate and Che sound power leveL Normal room temperature and pressure condflions are ossumed.
fig. 20 .... Corves for Determining the Sound Pressure Level in the Room Relative to the Sound Power Level
. system, the total acoustic power delivered to the room by the fan will be 108 dbe. Assuming that the branch fittings at D, E, and F are similar to that at C in Fig. 21, the unattenuated fan acoustie power delivered to each of the four 12 z 18 in. grilles will be approximately
: . PWL{dort oa> - 108 - 10 log 4 = 102 dbe
-The octave band spectrum of the centrifugal fan noise is given by Fig. 6. This chart indicates that the power level in the first band (20-75 cps) will be about 102*1 or 101 dbe, aod the power level in each succeedingly higher octave band will be 5 dbe less. These levels are entered m line 1 of the calculation Table 9.
- The next step is to determine the natural duct attenuation between the fan discharge and the room supply grilles. From Table 4 the attenuation for straight sheet-metal ducts of medium size is 0.05 db per ft at all frequencies. Let us assume that.all of the ducts of-this system fall within this medium category^ The total length of the duct run from Station A to Station H, Fig. 21, is 90 ft. The straight duct attenuation is, therefore, 0.05 (90) -- 5 db, which is entered in line 2 of Table 9. It should be noted here that the ducts CD and DH of 12 x 48 aod 12 x 15 in. dimensions, respectively, are of about the same size as those reported in Table 5. Hence if we assume the
attenuation for these two bare ventilation duets can be taken from Table 5, it will be found that the straight duct attenuation between C and H (35 ft) will be approximately 10 db in the lowest two octave bands, 6 db in the third band, and 3 db for all octave bands above 300 cpa. That is. using Table 5 for ducts CD and DH, and Table 4 for ducts AB and BC, the first three columns in line 2, Table 9, would read 12,12, and 9 db in that order, and the other columns would be unchanged at 5 db. It would appear, therefore, that the 5 db attenuation values for the lower three octave bands are probably overly conserva tive. The divided-flow fitting at B may be considered equiva lent in attenuation to-an 18-in. square bend. Values are read from Fig. 10, Part A and entered as line 3 in the calculation table. The rounded corners of the branch flow fittingB at C, D, E, F, and Q are assumed to have no attenuation. The 12 x
15 in. risers serving each of the wall grilles have a square bend (see Fig. 22), and attenuation values are read from Fig. 10, Part A and entered as line 4 of Table 9. The attenuation due to the end reflection loss at the grille face is given by Fig. 11.
For the 12 x 18 in. grilles used here L " \/l2 X 18 * 14.7 in. Thus, for the first octave band. (20-75 cps), which has a geo metric mean frequency of 4Ocps,/L/1000" (40 X 14.7)/1000 0.58 and the end loss is 13 db.
The attenuation in the other octave bands is similarly deter-
Sound Control
351
Table 9 .... Summary of Calculations for Example 3 on Ventilating Noise levels m Libary Reading Room
Octave Frequency Sand*
Item
20-
75-
150-
300- 600-
1200-
2400-
4800-
75 cps
150 cps 300 cpi 600 cps 1200 cps 2400 cps 4800 cps 10,000 cps
1. PWL(daom................................................ 101 96 91 86 81 ' 76 ' 71 66
2. Attenuation^ dB*t>.................................
5
5' 5
5
5
5
5
5
3. Attenuation(baad B)....................................
--
--
2
7
7 ,6
11 12
4. Attenuation(bsd m....................................
--
--
1
4
7
7
8 .10..
S. Attenuation,;.^ (...)..................................
13
7
4
1 --. " "
6. Total duct attenuation............................
18
12
12 17
19
. 18
24 -
27'.
. 7. PWL(,fiiu ootuo......................................... 8. /L/1000 cps-in.............................................
9. Q................................................... .................. 10. Rel.L, at 7 ft.......................... ................. 11. Lp at 7 ft.............................. ..................... 12. PWL{,n gtnut)............................................ 13. Rel.L* far field........................................... 14. Reverberant Lp.......................................... 15. Criterion Lp................ ............................. 16. Required attenuation............................... 17. Attenuation 4 ft pkg. unit.....................
83 0.5 2
-22
61 89 -26 63 60
3 7
84 1.3 2
-22 62 90
-26 64 51 23 11
79 2.5 2.2
-22 57 85
-26 59 43' 16 14
69 5.1 2.7
-21 48 75
-^26 - 49
37 12 30
62. V 58 `
10.2-
20.4 .
3.2 3.6
--20 -20
42 38'
71 67
-26 .
-26
45 41
32 30
13 11
40 40
47 40.8
3.9 -20
27 56 -26 30 28
2 38
39 . - 81.6 '
4.1 -20 , 19 ' ' 48 : .-26-.
22 27
-- 33
mined and entered in tine 5 of Table 9: The total natural duct attenuation is now found By summing lines-2, 3, 4,' and 5 of Table 9, and the result appears in line 6. This total attenu ation may now be subtracted from the unattenuated power level in line 1 to give the estimated acoustic power'level radi ated into the room from the outlet grille at Station H. Line 7 of Table 9 gives the result.
Determining Room Sound Pressure Levels .
The next step, then, is to calculate the sound pressure level at the position in the room occupied by the listener nearest to any one grille, and for the overall reverberant sound pressure
level In the room due to this sound power radiated from all of the grilles. Fig. 22 shows that the position of the nearest listener is 7 ft from the grille. To determine Lp at this position, determine the directivity factor Q at 45 deg to the grille face: this is found from Fig. 18. The parameter fL/1000 is determined by taking the characteristic length L as the shortest side of the grille face or 12 in. Thus, for the first octave band, /L/1000 = 40 (12)/1000 =* 0.4S. Thu value together with allthe corre sponding values for the other seven octave bands are entered in line 8 of Table 9. Line 9 of the table gives the corresponding . directivity factors as read from Fig. 18, using curve B since the grille is flush with the wall but hot at on edge or corner.
It was initially assumed that the library reading room had average acoustical properties, and consequently, the room con stant h in sq ft may be read from the tine marked average room
fig. 22 .Location of Nearest listener to a Supply-Grille