Document J3mKyL5L4MLmrXY18dOgor96
UNITED STATESUNITED STATES ENVIRONMENTAL PROTECTION AGENCY
* *REGION 1
ENVIRONMENTAL
AGENCY5 POST OFFICEB OSSTQOUN,A RMAE ,0 21S0U9-I3T9E12
100
PROTECTION
Drafted Date:15 February 2022
Finalized Date:1 March 2022
Subj:Inspection Report
Clean Water Act - National Pollutant Discharge Elimination
System (" NPDES ")
City of Fall River
From:Andrew Spejewski, Enforcement Officer
Thru:David Turn
To:File
I. Facility Information
A. Facility Name:City of Fall River
B. Facility Location:1979 Bay St
Fall River, MA 02724
C. Facility Contacts: Paul Ferland
pferland@fallriverma.org
D. NPDES ID No (s).: MA0100382
II. Background Information
A. Date(s) of inspection: February 11, 2022
B. Weather Conditions: Clear, Dry, no recent rainfall
C. US EPA Representative(s):
Andrew Spejewski
D. State / Local Representative(s): none
E. Federally Enforceable Requirements Covered During the Inspection: Portions of
Administrative Order CWA-AO-R01-FY22-01 covering Combined Sewer
Overflows
ED_019088A_00019833-00001
F. Previous Enforcement Actions: Administrative Order CWA-AO-R01-FY22-01
III. Type and Purpose of Inspection
Inspection of two outfalls with screening / disinfection facilities, to assist in evaluating
compliance with portions of Order.
IV. Facility Description
Two facilities were observed, both facilities to screen and disinfect combined sewer
overflow: the Cove Street facility and the President Avenue facility.
V. Inspection
A. Opening Conference
MS scheduled the inspection in advance with Mr. Ferland. By arrangement, they met at
the Cove Street facility at 10:30 AM. Present were
Paul Ferland, City of Fall River
Jaysen Wetherbee, WWTP Manager for Veolia (which operates the City's plant under
contract)
Marc Laferriere, WWTP Assistant Manager
Matt Murphy, an engineer at Keville Enterprises, who worked on both outfall treatment
facilities.
B. Facility Tour
The Cove street facility includes a pump station and the CSO chlorination facility. The
pump station is within the building on site with the wet - well for the pump station below
the building.
The chlorination facility is northwest of the building It includes an initial tank, a
chlorination contact chamber adjacent to it, a pump tank past the chlorination chamber
and an outlet chamber. All tanks and the outlet chamber are partially buried, with access
from above.
A passive weir is upstream of the chlorination facility, which sends low flow to the pump
station, while higher flow goes over the weir to the chlorination facility.
The initial tank has an overflow connection directly to the outlet chamber, so that very
high flows are routed past the chlorination section.
The chlorination tank is an open concrete structure, ending in three channels. Each
channel leads under a concrete wall to a pump chamber. The three pump chambers pump
2
ED_019088A_00019833-00002
from the chlorine contact chamber upwards and discharge towards the outlet chamber.
According to site personnel the pumps run as - needed. They agreed that residence time in
the chlorine contact chamber would be highly variable depending on flow in and the
pump cycle. [Note that no dechlorination is done at this facility].
The outlet chamber discharges directly to the outfall pipe, which passes under route 79 to
an outfall. According to site personnel, there are no manholes or other access to the
outfall pipe, and the outfall is submerged. Additionally, access to the outfall is down a
steep rip - rap slope which can only be accessed directly from Route 79.
Personnel explained that sampling is done by lowering a sample container into the outlet
chamber.
Personnel stated that the site has on a couple occasions flooded during very heavy rain;
the site is automated and can continue functioning, but for safety operators do not access
it during flooding, so samples cannot be collected.
The facility is bordered to the northwest by a short steep slope leading to a concrete wall
supporting a ramp for Route 79. An open area about 20-30 yards across is south of the
chlorination structure, with a chemical storage open shed and an outdoor emergency
generator.
The group then drove in their own vehicles to the President Avenue station.
A passive weir upstream directs low flow to the main interceptor and higher flow to the
station. At the entrance to the station, another passive weir directs very high flow
directly to the upper end of the outfall pipe, with the rest going to the station.
The station tanks are underground and covered by pavement, access hatches and the
station building. Station personnel showed a flow diagram, indicating chlorine addition,
a serpentine contact chamber for residence time, and a small tank for adding
dechlorination. The outflow from the dechlorination tank then dicharges to the upper
end of the outfall pipe (joining any very high flow passing over the second weir).
The outfall pipe runs out to a usually submerged outfall at the far end of the park.
Sampling is done by manually taking samples from a manhole near the upper end of the
outfall pipe.
C. Records Review
No records were reviewed as part of this inspection.
D. Closing Conference
Mr. Spejewski thanked the group for their time and left at approximately 11:30 AM.
Picture List:
Cove Street
3
ED_019088A_00019833-00003
IMG 2596.JPGFacing NW towards the initial chamber.
IMG 2597.JPGFrom the top of the initial chamber over the chlorine contact
chamber and towards the pump chamber
IMG 2598.JPGNear end of the chlorine contact chamber
IMG 2599.JPGFar end of the contact chamber, leading to pumps
IMG 2600.JPGAbove the pump chamber
President Avenue:
IMG 2601.JPGFacing towards outfall, from upper end of outfall pipe.
*
Unless otherwise noted, this report describes conditions at the facility / property as
observed by EPA inspector(s), and / or through records provided to and / or information
reported to EPA inspector(s) by facility representatives and as understood by the
inspector(s). This report may not capture all operations or activities ongoing at the time
of the inspection. This report does not make final determinations on potential areas of
concern. Nothing in this report affects EPA's authorities under federal statutes and
regulations to pursue further investigation or action.
4
ED_019088A_00019833-00004