Document J3bdVx86arz0apKZV176xxVZ2
MONSANTO INDUSTRIAL CHEMICALS COMPANY Visit At
SPRAGUE ELECTRIC COMPANY NORTH ADAMS, MASS. SEPTEMBER 1972
To
Review Status of Capacitor Aroclor (PCB) Dielectric Fluid
HONS Q63268
INDEX
SECTION I
II
III IV V
The Need For PCB-Type Fire Resistant Dielec tric Fluids (Excerpts from the Jan. 5, 1972 report by the National Industrial Pollution Control Council - U.S. Dept. Commerce, Washington, D.C.
A. Capacitors
B. Transformers
U.S. Government Interdepartmental Task Force Report, May 14, 1972 entitled "Polychlorina ted Biphenyls and the Environment"
A. Continued PCB use for capacitors and transformers is considered necessary
B. Disposal of scrap capacitors by burial
C. Disposal of scrap PCB fluid by incir.era- tlon
Handling and Policing PCB Dielectrics
A. ANSI Committee C107 guidelines for capacitors and transformers
B. ASTM D-27, Methodology for sampling PCBs and analysis of water and air - `
Purchase of Capacitor and Transformer Askarels
A. Pounds Aroclor Purchased by Sprague
B. Prices Table II
C. Pricing Characteristics Table III
Summary of Monsanto's Actions to Meet the Elec trical Industry Requirements and To Minimize PCB Environmental Pollution
15 charts
PAGE
1 1-3 3-5
6 6 6 6 7 7 7 8 8&9 10 11
12 12 on
MGNS 063269
o
SECTION I The Need For PCB-Type Fire-Resistant Dielectric Fluids (Excerpts from the Jan. 5, 1972 report by the National Industrial Pollution Control Council - U.S. Dept. Commerce, Washington, D.C.)
\
o
HONS 0632 70
o
G
I. The Need For PCB-Type Fire-Resistant Dielectric Fluids (Excerpts from the Jan. 5, 1972 report by the National Industrial Pollution Control Council - U.S. Dept. Commerce, Washington, D.C.)
A. The Need For PCB Type Dielectric Fluids In Capacitors
1. Widespread use of PCB capacitors
PCBs are used In more than 90^ of the electric utility (large power) type and smaller Indus trial type capacitors made today. They are needed for safety, reliability and long life, and to achieve sizes compatible with equipment and Installation requirements.
The principal types of PCB-impregnated capaci tors and their applications are high voltage power capacitors used primarily for power fac tor correction in the distribution of electric power; low voltage power capacitors installed in'industrial plants at the load (typically large motors); ballast capacitors to improve the efficiency of lighting systems; and small industrial capacltbrs for power factor improve ment in such equipment as air conditioning units, pumps, fans, etc. Almost 80 million such capa citors are manufactured annually, most of them for first-time use.
Capacitors used in lighting and air condition ing applications contain 0.005 to 0.09 gallons of PCB per unit. The largest power capacitors contain about 6.7 gallons of askarel. The most popular size contains about 3.1 gallons. The National Electrical Code requires^ that any in stallation of capacitors in which' any single unit contains more than 3 gallons pf combustible liquid shall be in a vault like that required for transformers. During 1968, the last complete "normal" year for the electrical industry, the total amount of fire resistant PCBs used in capacitors was approximately l^t.^ thousand tons.
2. Reliability, life and safety of PCB capacitors
PCBs are thermally and oxidatively more stable than mineral oils and most other dielectric fluids. Discharges, which can occur in capa citors, are less likely to generate gases from askarels than from mineral oils. The chemical stability of PCBs in the presence of capacitor
HONS 063271
o
o
G
tissue and plastic films and the favorable stress distributions between solid and liquid have made it possible to design lowcost capacitors with a life expectancy of more than 10 years life In lighting applica tions and more than 20 years In electric utility applications. In each application the first-year failure rates are less than 0,2^. This level of life and reliability had not been achieved prior to the introduction of -PCBs.
The relative non-flammablllty of PCBs signi ficantly reduces the fire hazard that might otherwise accompany those failures that re sult In rupture of the case.
3. Consideration of other dielectric fluids for PCB-type capacitors
a) Mineral oil
The 3lngle most important property of a liquid to be used in a capacitor Is its dielectric constant (the ratio of its ability to store electrostatic energy relative to air). The dielectric constant of the capacitor-grade PCB (Aroclor 12^2) is 5.85 while that of mineral oil Is 2.25. Reverting to an oil-paper dielectric system would increase the average capacitor volume (size) by approximately 50056, the weight by 50056, and the cost by approximately I10056. At the present levels of demand for capaci tor KVAR, there would be a shortage of elec trical grade paper and a shortage of capa citor factory facilities further tending to increase the cost to the utility, and ultlmately to the consumer.
b) Castor oil
The dielectric constant of castor oil is ^.5 and this material Is useful as an lmpregnant In D.C. energy storage capacitors. However, A.C. capacitors filled with this liquid have relatively short lives and are not very stable under A.C. discharges and in the presence of water derivable from the celluloslc paper.
-2-
AONS 063272
c) Dibutyl Sebacate
This ester Is especially useful in high frequency parallel plate capacitors because of Its low, flat loss characteristics over a broad frequency range. In this type of con struction the liquid is the sole dielectric material. When used In conjunction with paper this ester Is also unstable.
d) Silicone Fluids
These materials have a dielectric constant of 2.7 and would generally be subject to the
same disadvantages as mineral oil.
Monsanto developed Capacitor Aroclor 1016 to achieve a higher degree of environmental compatibility.
As the environmental studies indicated that the higher boiling (the higher chlorinated) PCB isomers persist in the general environment, Monsanto sub stantially removed these persistent components from commonly used capacitor Aroclor 1242.
This Aroclor 1016 capacitor dielectric has the same
fire-resistant rating assigned to Aroclor 1242 by the Underwriter's Laboratory.
Replacement of Aroclor 1242 with Aroclor 1016 in
capacitors involved no handling, process nor capa
citor design changes. This work done by Monsanto
In collaboration with the capacitor industry was
culminated by universal adoption of Aroclor 1016
for capacitors in mid-1971.
:
The Need For PCB-Type Dielectric Fluid In Transformers
Because of the nonflammability of transformer askarel fluids, their vapors, and their arc-formed gaseous products, transformers filled with PCBs are free of fire and explosion hazards and may be used in locations where failures of oil-insulated transformers would pre sent a potential danger to life and property.
Most of these transformers are located inside public, commercial, or industrial buildings; on the roof tops of such buildings or in close proximity to such build ings, and require no special enclosures other than what are necessary to prevent accidental hazardous mechani cal or electrical contact of persons with the equipment
-3-
KONS 063213
The amount of Aroclor used In various types of trans
formers ranges from 40 to 500 gallons (516 to 6,450 lbs.) with an average of about 235 gallons (3,032 lbs.). During 1968, the last complete "normal" year for the electrical industry, the total amount of PCBs used in
transformers was approximately 1.3 million gallons (8.4 thousand tons).
The only present alternatives to Aroclor-insulated transformers are mineral oil-insulated transformers or dry-type transformers (either those open to the atmos
phere or those that are gas-filled and sealed).
Alternatives
1. Mineral oll-lnsulated transformers
a) If one disregards safety considerations, there
are no technical reasons why mineral oll-lnsulated transformers could not be directly sub stituted for PCB-insulated transformers. The
size of the unit would be unchanged; the weight and cost would be less.
b) But one cannot disregard safety considerations, which are often embodied in legal codes.
Obviating the safety hazards Involves serious
economic and space constraints, that would occur
either by the use of protective vaults, or use
of insulated buses (with the transformer loca
ted outdoors). Either solution, if the space
is available, could cost $5,000 - $50,000 per
transformer.
2. Dry-type transformers
-
In most locations, dry-type transformers (either those open to the atmosphere or those that are gas-filled and sealed) could not be directly sub stituted for PCB-insulated transformers. There are several restrictions to such a direct substitution:
a) The reliability of dry-type transformers is
less than that of comparably rated liquid-insu lated transformers. An EEI survey of failures in network transformer banks showed a 7% per year failure rate for dry-type units compared to 0.256 for llquld-lnsulafed units.
-4-
MGNS 063274
o
o
b) Furthermore, llquld-lnsulated transformers have a much greater overload capability. Many llquld-lnsulated units can sustain a 100# overload for 8 hours and a 200# over load for 2 hours. These transformers arc able to maintain continuity of electrical service during periods of temporary mal function of related equipment.
c) Some dry-type transformers are larger by 10 to 30# than comparably rated liquid In sulated units, and most are more expensive.
d) Dry-type transformers are nolser by 5-10 dB than are llquld-lnsulated transformers.
e) Open dry-type transformers, which are cheaper than sealed dry-type transformers, cannot be used In certain corrosive or hazardous atmos pheres, e.g. on furnaces or on electrostatic precipitators near hot stacks.
3. Other fluids
The fire underwriters will not accept the use of oils, silicones and other flammable liquids for indoor transformers. No currently available liquid which will replace askarels in existing transformers Is known.
Q MCNS 063275
SECTION II
U.S. Government Interdepartmental Task Force Report
May 14, 1972 Entitled "Polychlorinated Biphenyls and
the Environment"
.
'
HONS 06327<>
II. U.S. Government Interdepartmental Task Force Report May 14, 197? Entitled "Polychlorinated Biphenyls and the Environment
This report is available from the National Technical Information Service, U.S. Department of Commerce, Springfield, Va. 22151. The task force included opera ting units of five Executive Branch Departments:
Department of Agriculture Department of Commerce Department of Health, Education & Welfare Department of Interior Environmental Protection Agency
These government agencies are fully appraised of Mon santo's voluntary actions to discontinue sale and supply of PCBs for all non-electrlcal uses.
The Task Force Report states:
A. "The use of PCBs should not be banned entirely. Their continued use for transformers and capacltors in the near future is considered necessary because of the significantly increased risk of fire and explosion and the disruption of electri cal service which would result from a ban on PCB use. Also, continued use of PCBs in transformers and capacitors presents a minimal risk of environ mental contamination. The Monsanto Company, the sole domestic producer, has reported voluntarily eliminating its distribution of PCBs to all ex cept manufacturers of electrical transformers and capacitors."
B. Disposal of Scrap Capacitors
'
"Most capacitors presumably have been disposed of In landfills. PCB-containlng material buried in
soil fs not expected to migrate but should remain In place. In the past, many fluids containing PCBs have been disposed of in sewers. More appro priate means of disposal such as high temperature (at least 970C) Incineration must be used instead
C. Disposal of Scrap PCB Fluid
Monsanto is one of several to provide proper high temperature incineration and HC1 neutrallzating facilities to completely destroy PCB liquids. Monsanto charges 3 cents a pound and shipping charges are to the sender's account.
-6-
MQNS 063277
SECTION III Handling and Policing PCB Dielectrics
MONS 063218
III. Handling and Policing PCB Dielectrics
A. The American National Standards Institute
ANSI Committee C107 composed of a capacitor
section and a transformer section, on behalf of all parties interested In PCB dielectrics, is scheduled to publish guidelines for hand
ling and disposal of capacitor-grade askarels and transformer-grade askarels.
B. PCB analysis
Methodology developed by Monsanto and others is in process of documentation at ASTM D-22 for sampling and analyzing of PCB from water and air.
C. Need to Avoid Environmental Contamination
While the continuing need for PCBs in closed elec trical applications is conclusive, the electrical Industry must well understand that continued use of these materials requires unusual protective measures and exceptionally clean "house keeping!'.
EPA plans to regulate the controllable sources of
PCBs to the water environment. Pish and shellfish will be examined to reveal locations with high PCB content. The PDA guideline allows no more than 5 ppm PCB in the edible portion of fish.
It Is not believed necessary to regulate PCBs in
air, at this time.
'
The Industry goal is "zero" concent-ration of PCB In plant water effluent streams. However, it is recognized that existing drain systems in (for example) capacitor manufacturing plants are prob ably contaminated as a result of past practices and PCB traces may continue to show up in effluent streams for some time.
MCNS 063279 -7-
Section IV Purchase of Capacitor Aroclor
ONS 063280
. . J.
o
IV. Purchase of Capacitor Aroclor
A. Pounds Aroclor Purchased by Sprague Electric Co.
As Sprague Is one of the early manufacturers of Aroolor capacitors, their Initial use of Aroclor 1254 must date back to the 1940s.
Over the past twenty years Sprague's use has ranged from 2.O56 to 7.756 of the total annual amount of ca pacitor Aroclor used In the USA. The annual pounds used by Sprague has ranged from 250,000 to 767,000 pounds per year during the 1950s, to the 2,002,800
peak used In 1969. when the dollar volume was also a maximum at $300,999.
The pounds of capacitor Aroclor purchased by Sprague over the past five years ard shown in Table I.
B. Prices
The historical sales prices per pound for capacitor Aroclor sold to Sprague are given In Table II.
C. Monsanto Dielectric Fluids Pricing Characteristics
1. Unusual price stability through the years until 1970.
2. Increases 1970-1972 fully accounted by factors
related to the PCB environmental problem; see
Table III.
*
HGNS 063281
o
-8-
Table I
Sprague Electric 1
Purchase of Capacitor Aroclor Pounds
i2a ,000 2,002,800
1970 1,0*1,460
1971 1,1*5,800
6 Mo. 1972
628,*20
kons 063282
Table II
Historical Price of Capacitor Aroclor Sold to Snracue
Year 1953 1957 I960 1964 1966 1970 1971 1972
Price Per Pound (Bulk)
- l4.0j! Not Delivered 13.88^ Delivered l4.98j{ Delivered Ik. 50<f. Delivered 14.95^ Delivered 16.004 Delivered I8.OO5! Delivered 20.50^ Not Delivered
Product Aroclor 1242 Aroclor 1242 Aroclor 12^2 Aroclor 1242 Aroclor 1242 Aroclor 1242 Aroclor 1016 Aroclor 1016
-10-
MGNS 063283
Table III
Monsanto Dielectric Fluids Pricing Characteristics
1. Unusual-price stability until 1970 even though --
Cost Increases
Labor Costs:
197# Increase (1953-1972)
Raw Materials:
20# Increase (1953-1972)
Indirect Fixed Costs:
Ulfi Increase (1953-1972)
(e,g. Capacitor Fluids increased by only 7#, 1953-1959)
2. Increase 1970-1972 due to: A. Successful development of Aroclor 1016 B. Loss of *(5# PCB sales to other markets -- divisor loss
C. Costs of environmental control programs -
Incinerator Program Plant'Clean-up
-11-
NQNS C63284
SECTION V.
Summary of Monsanto's Actions to Meet the Electrical Industry Requirements and to Minimize PCB Environmental Pollution
-12-
MONS 063285
9e?E*>
0
az</>
MONSANTO PRESENTATION TO FEDERAL GOVERNMENT PCB TASK FORCE
MAY 15, 1972
.
OBJECTIVES
O PROGRESS REPORT ON LABORATORY BIODEGRADATION OF PCB'S
O RESIDUE ACCUMULATION STUDIES IN FISH, BIRDS AND MAMMALS
O TO SHOW REDUCTION IN LESS BIODEGRADABLE PCB'S AS A RESULT OF MONSANTO ACTIONS ON SALES AND PRODUCTS
0
MONSANTO PCB ACTIONS
O PHASE-OUT OF PCB SALES WORLDWIDE IN ALL APPLICATIONS EXCEPT DIELECTRICS
O CONVERSION OF DIELECTRIC FLUIDS TO MORE BIODEGRADABLE PCB'S
HCNS 0 6 3 2 8 7
5 oO (D
* 0)
(
MONSANTO PCB SALES IN U.S.A.
(million pounds)
' DIELECTRICS ALL OTHERS TOTAL
1969 37.0 30.0 67.0
1970 10.5 33.5 79.0
' 1972 (est.)
32.a
- 32.0
i
HONS 0 6 3 2 8 8
I
is O
MONS 0 6 3 2 8 9
EFFECT OF. PHASE-OUT POLICY
PCB SALES REDUCED IN U.S.A. BY 30 TO 33 MILLION POUNDS, . OR 45%
V (O
oo
<D
PCB PRODUCT CHANGES IN DIELECTRICS
' CAPACITORS ^ 97% CONVERSION TO AROCLOR 1016
TRANSFORMERS ELIMINATION OF AROCLOR 1260
0 6 ? E 9 0 SNOW
HGNS 0 6 3 2 9
<5> Oq
DEGREE OF BIODEGRADATION OF PCB'S
BASED ON DATA PRESENTED O TRANSITION IN BIODEGRADATION OCCURS AROUND PENTA-/HEXA-CHLOROBI PHENYL O DISAPPEARANCE OF ALL HOMOLOGS BELOW HEXA-CHLOROBIPHENYL OBSERVED O PENTA- AND HIGHER PCB DETERMINED BY SPECIFIC GLC/MS TEST METHOD
<b
HONS 0 6 3 2 9 2
I
PCB'S USED IN CAPACITORS
PCB AROCLOR 1254 AROCLOR 1242 AROCLOR 1016
MAJOR USE PERIOD
1930-1952
1952-SEPT. 1971 OCT. 1971
l PCB (PENTACHLORO- AND 'HIGHER
77.0
9.0
1.1
% PCB (HEXACHLORO- AND
HIGHER
29.0
1.0
0.1
i I
.
i "i
L [
li i k i
Oq
CAPACITOR FLUIDS
WHY CONVERT TO AROCLOR 1016 l
O 9-FOLD REDUCTION IN PCB'S OF PENTACHLORO- AND HIGHER
O 10-FOLD REDUCTION IN PCB'S OF HEXACHLORO- AND
HIGHER
O MINIMUM INDUSTRY TESTING REQUIRED
HONS 0 6 3 2 9 3
OO
' CAPACITOR FLUIDS
"
WHAT IS THE EFFECT OF AROCLOR 1016 1
u.s. CAPACITOR FLUID SALES (1972):~20 M LBS.
IF
AROCLOR WAS
Z PENTACHLOROAND HIGHER PCBs
WOULD BE*
% HEXA CHLOROAND HIGHER PCBs
WOULD BE*
1254
15.400,000 pounds
1242 1.800,000 m 1016 . ' , 220,000
'
5,800,000 pounds 200,000 20,000
THIS DOES NOT MEAN AMOUNTS OF PCB ENTERING THE ENVIRONMENT
i
{
N
MOMS 0 6 3 2 9 4
CD oo CD
WHAT IS CAPACITOR FAILURE RATE ?
o
INDUSTRY SOURCES CITE : 0.02-0.2% per year
i
MGNS 0 6 3 2 9 5
oo
IF CAPACITOR FAILURE RATE IS 0.2% PER YEAR (WORST CASE)
PCB ESCAPE TO THE ENVIRONMENT* IS --
ALL PCB HOMOLOGS PENTA CHLORO- AND HIGHER HEXA CHLORO- AND HIGHER
AROCLOR 1242
AO,000 pounds 3,600
400
AROCLOR 1016
40,000 pounds ; 440 , 40
ASSUMES U.S. FLUID SALES OF 20 M LB./YEAR
MONS 0 6 3 2 9 6
PCB CHANGES IN
,
TRANSFORMER FLUID APPLICATIONS % O AROCLOR 1260 BEING PHASED-OUT. NOW O INCINERATION OF SCRAP PCB'S - 1971
HONS 0 6 3 2 9 7
NOTE: ASKAREL (PCB) TRANSFORMERS ARE ' TIGHTLY SEALED UNITS
HONS 0 6 3 2 "
I
^
CO
WHAT IS FAILURE RATE IN LIQUID TRANSFORMERS ?
INDUSTRY SOURCES CITE: UNDER 0.2% PER YEAR* *Al LIQUID TYPES - MINERAL OIL M PCB.
(,e .z f 0
I
( IF ASKAREL (PCB) TRANSFORMERS FAIL AT 0.2%/YEAR
HOW MUCH PCB IS AFFECTED ?
ALL PCB HOMOLOGS
2A,000 lbs.
(ESTIMATED PCB TRANSFORMER FLUID SALES IN U.S. 12 M LBS./YEAR) !
^
*
;
< *WITH INCINERATION FACILITIES AVAILABLE/ NOT ALL THESE AMOUNTS :
WILL ENTER ENVIRONMENT.
. |
w
<9
o CP
MONSANTO'S PRESENT PROGRAM TO PREVENT ENVIRONMENTAL POLLUTION BY PCB'S
O NO MORE SALES WORLD-WIDE EXCEPT APPROVED DIELECTRIC USERS
'*
O RESTRICT OVER 97Z CAPACITOR FLUID SALES TO AROCLOR 1016 ONLY
O ELIMINATE AROCLOR 1260 FROM TRANSFORMER FLUIDS
'
O CONTINUE INCINERATION FACILITIES FOR SCRAP PCB'S
O ENCOURAGE DIELECTRIC INDUSTRY THROUGH ANSI
C-107 TO ENFORCE STRICT ENVIRONMENTAL CONTROL
OVER PCB'S
.
I
HONS 0 6 3 3 0 0
Monsanto has attempted to act responsibly as concern about the effects of PCBs on our environment developed. Based on cur rent knowledge about PCBs, the approach presently being taken by the U.S. Government and the continued need by our customers In the electrical industry for PCB-contalning dielectric fluids, Monsanto Intends to maintain Its policy of remaining a supplier of these materials for dielectric uses. However, should changes In present conditions occur, Monsanto may find It appropriate to revise Its policy.
MONS 063301