CHAPTER 44
1965 Guide And Data Book
gain characteristics of the conditioned space oh the capacity characteristic of the cooling system often will be of value in
determining the degree of complexity actually required to
meet the objectives of the system.
: v- - . \
'While-the component balancing process-b essential:to the dptaulftd-teehnieal- pmhlema of component selection,'it also
helps in the development of an overall appraisal of system
performance. The designer may consider thc'system as merely
an assembly of components,- each having a known sensitivity
to the variables which affect its performance, thereby over
looking the fact that the sensitivity of the system as a whole
to the external variables b generally of a lower order. This can
result in unwarranted system and control complexity, which
will have an important influence on the cost and reliability of
the overall system. A study'of the. way in which components
balance <mt when combined will yield valuable information bn
the overall response of the system to its environment This
information can be applied to the more detailed considerations
of determining the extent to which specific refinements are .
warranted.
..
TYPICAL COMPONENT BALANCE EXAMPLE
-.The typical pressure-enthalpy (Mollier) diagram shown is
Fig.. 7 illustrates a component balance used through a com plete refrigeration cycle: - The refrigerating capacity (line AB) is determined from Fig,. 1, and represents the evaporator capacity, minus the refrigeration effect.
. Point C is determined from Part B of Fig. 2. The length of line CD is determined by the condenser heat rejection found from Part A of Fig. 2.
The relative position of system points A, B, C, and D are subject to limited change, as indicated in the preceding text, due to fine pressure drops, compressor and expansion device
characteristics, and other factors. A similar approach to load balance for heat pump systems
is discussed in Chapter 66.
CHAPTER 45
REFRIGERANT CONTROL DEVICES
CONTROLLERS; Pressure Confrotfers, Temperature Controllers, Differential Controllers, Float Switches; CONTROL VALVES: Thermostatic Expansion Valves, Constant Pressure Exportsion Valves, .Discharge Bypass Regulators, Evaporator Pressure - Regulators, Suction Pressure Regulators, Condenser Pressure Regulators, Condenser Bypass Valves, High-Side Root Valves, Low-Side Root Valves, Solenoid Valves, Refrigerant Reversing, Valves, Condensing Water Regulators, Check Valves, Relief Devices; CAPILLARY TUBES: Theory, Design Factors, Application, Preliminary Selection, Simplified Calculation Procedure
THE control of refrigerant flow b an essential feature' of proper area a-sufficient -force can be produced to operate any refrigeration system. Part I of thb chapter discusses heavy switches, water valves, or even refrigerant valves. In the operation and selection of controllers, including: (1) these heavy-duty controllers the minimum differential b
pressure controllers, (2) temperature controllers, (3) differ necessarily quite large because of the massiveness of the bel
ential controllers, and (4) float switches. Part U discusses lows and opposing spring system.
the operation and selection of control valveB, including: (1) thermostatic expansion valves, (2) constant pressure expan
, TEMPERATURE CONTROLLERS
sion valves, (3) discharge bypass regulators, (4) evaporator pressure regulators, (5) suction pressure regulators, (6) condenser pressure regulators, (7) condenser bypass valves, (8) high-side float valves, (9) low-side float- valves, (10) solenoid valves, (11) refrigerant reversing valves, (12)-con densing water regulators, (13) check valves, and (14) relief devices. Part III discusses capillary tubes. For further infor mation on automatic control, see Chapter 13.
Temperature controllers for refrigeration are basically, pres sure controllers in which the pressure responsive power ele ment b replaced by a temperature responsive power'element. The exact temperature-pressure relationship, of the fluid used in the power element allows the temperature of the bulb to accurately control the pressure: Operation of the controller results from these chknges in pressure.
PART I: CONTROLLERS
DIFFERENTIAL CONTROLLERS Controllers used to maintain a given difference in pressure
The controller b a device which operates one or more sets or temperature between two pipe lines or spaces are known
of electrical contacts and, in some cases, water or refrigerant as differential controllers. A typical example of tins type of
valves, in response to changes in pressure, temperature or controller b the oil safety switch used with reciprocating com
liquid leveL Pressure and temperature responsive controllers pressors having forced feed pressure lubrication. These con
have one or more power elements which may utilise bellows, trollers, since they must sense conditions in two different
diaphragms, or bourdon tubes, to produce the force needed to locations, must have two elements, either pressure- or tem
operate the mechanism. Level responsive controllers utilise perature-sensitive.
either a float or an electronic type probe to directly or in
Tig. 1 b a schematic diagram of a differential-pressure con
directly operate one or more sets of electrical contacts.
troller using bellows as power elements.
PRESSURE CONTROLLERS
The refrigerant pressure b applied directly to the power element which moves against a spring that can be adjusted to
control any operation at the desired pressure. If the controller
a to operate in the subatmospheric, or vacuum, range the bellows or dbphragm force will be reversed and act in the
me direction as the adjusting spring. To counteract
an
additional spring must be used to overcome the reversed bel
lows force, in which case the force of both the bellows and the
spring oppose the adjusting spring.
forc available for doing work in a controller of thb vP b dependent first upon .the pressure in the system and secondly upon the area of the bellows or diaphragm. With
715
Rg. 1.... Differential-Pressure Controller j