Document J3Ez5xQ0dq9GL4dEONQ7eRYzZ

714 CHAPTER 44 1965 Guide And Data Book gain characteristics of the conditioned space oh the capacity characteristic of the cooling system often will be of value in determining the degree of complexity actually required to meet the objectives of the system. : v- - . \ 'While-the component balancing process-b essential:to the dptaulftd-teehnieal- pmhlema of component selection,'it also helps in the development of an overall appraisal of system performance. The designer may consider thc'system as merely an assembly of components,- each having a known sensitivity to the variables which affect its performance, thereby over looking the fact that the sensitivity of the system as a whole to the external variables b generally of a lower order. This can result in unwarranted system and control complexity, which will have an important influence on the cost and reliability of the overall system. A study'of the. way in which components balance <mt when combined will yield valuable information bn the overall response of the system to its environment This information can be applied to the more detailed considerations of determining the extent to which specific refinements are . warranted. .. TYPICAL COMPONENT BALANCE EXAMPLE -.The typical pressure-enthalpy (Mollier) diagram shown is Fig.. 7 illustrates a component balance used through a com plete refrigeration cycle: - The refrigerating capacity (line AB) is determined from Fig,. 1, and represents the evaporator capacity, minus the refrigeration effect. . Point C is determined from Part B of Fig. 2. The length of line CD is determined by the condenser heat rejection found from Part A of Fig. 2. The relative position of system points A, B, C, and D are subject to limited change, as indicated in the preceding text, due to fine pressure drops, compressor and expansion device characteristics, and other factors. A similar approach to load balance for heat pump systems is discussed in Chapter 66. CHAPTER 45 REFRIGERANT CONTROL DEVICES CONTROLLERS; Pressure Confrotfers, Temperature Controllers, Differential Controllers, Float Switches; CONTROL VALVES: Thermostatic Expansion Valves, Constant Pressure Exportsion Valves, .Discharge Bypass Regulators, Evaporator Pressure - Regulators, Suction Pressure Regulators, Condenser Pressure Regulators, Condenser Bypass Valves, High-Side Root Valves, Low-Side Root Valves, Solenoid Valves, Refrigerant Reversing, Valves, Condensing Water Regulators, Check Valves, Relief Devices; CAPILLARY TUBES: Theory, Design Factors, Application, Preliminary Selection, Simplified Calculation Procedure THE control of refrigerant flow b an essential feature' of proper area a-sufficient -force can be produced to operate any refrigeration system. Part I of thb chapter discusses heavy switches, water valves, or even refrigerant valves. In the operation and selection of controllers, including: (1) these heavy-duty controllers the minimum differential b pressure controllers, (2) temperature controllers, (3) differ necessarily quite large because of the massiveness of the bel ential controllers, and (4) float switches. Part U discusses lows and opposing spring system. the operation and selection of control valveB, including: (1) thermostatic expansion valves, (2) constant pressure expan , TEMPERATURE CONTROLLERS sion valves, (3) discharge bypass regulators, (4) evaporator pressure regulators, (5) suction pressure regulators, (6) condenser pressure regulators, (7) condenser bypass valves, (8) high-side float valves, (9) low-side float- valves, (10) solenoid valves, (11) refrigerant reversing valves, (12)-con densing water regulators, (13) check valves, and (14) relief devices. Part III discusses capillary tubes. For further infor mation on automatic control, see Chapter 13. Temperature controllers for refrigeration are basically, pres sure controllers in which the pressure responsive power ele ment b replaced by a temperature responsive power'element. The exact temperature-pressure relationship, of the fluid used in the power element allows the temperature of the bulb to accurately control the pressure: Operation of the controller results from these chknges in pressure. PART I: CONTROLLERS DIFFERENTIAL CONTROLLERS Controllers used to maintain a given difference in pressure The controller b a device which operates one or more sets or temperature between two pipe lines or spaces are known of electrical contacts and, in some cases, water or refrigerant as differential controllers. A typical example of tins type of valves, in response to changes in pressure, temperature or controller b the oil safety switch used with reciprocating com liquid leveL Pressure and temperature responsive controllers pressors having forced feed pressure lubrication. These con have one or more power elements which may utilise bellows, trollers, since they must sense conditions in two different diaphragms, or bourdon tubes, to produce the force needed to locations, must have two elements, either pressure- or tem operate the mechanism. Level responsive controllers utilise perature-sensitive. either a float or an electronic type probe to directly or in Tig. 1 b a schematic diagram of a differential-pressure con directly operate one or more sets of electrical contacts. troller using bellows as power elements. PRESSURE CONTROLLERS The refrigerant pressure b applied directly to the power element which moves against a spring that can be adjusted to control any operation at the desired pressure. If the controller a to operate in the subatmospheric, or vacuum, range the bellows or dbphragm force will be reversed and act in the me direction as the adjusting spring. To counteract an additional spring must be used to overcome the reversed bel lows force, in which case the force of both the bellows and the spring oppose the adjusting spring. forc available for doing work in a controller of thb vP b dependent first upon .the pressure in the system and secondly upon the area of the bellows or diaphragm. With 715 Rg. 1.... Differential-Pressure Controller j