CHAPTER 36
` 1949 Guide
condensate from the cooling coil is sprayed over the condenser surface and vaporized, thus eliminating the need for drain connections. 'A simple dampering arrangement is generally provided for exhausting some air from the. room, in addition to introducing outside air and recirculating required amounts of air. It is possible to remove the equipment for winter storage or utilize the ventilating features for winter operation;
Controls for Room Cooling Units
Control devices for self-contained cooling units are generally provided to include all necessary means for automatic. operation: : Provision is also made for adding auxiliary external controls when desired: Remote units are not generally equipped with controls. Control systems for remote units, and auxiliary controls for self-contained units, are covered in the general treatment of Controls in Chapter 34.
Fio. 7. Self-Contained Aib-Cooled Unit
Am CONDITIONER
RATINGS OF UNIT AIR CONDITIONERS
There are two codes governing the rating and testing of unit air con ditioners. The first code, Standard Method ofi Rating and Testing Air Conditioning Equipment1, covers alttypes of air-conditioning units except the self-contained type. The latter is covered-by the second code, The Standard Method of Rating and Testing Self-Contained Air Conditioning Units for Comfort Cooling2. The two codes are- necessary because of the basic difference caused by the heat given up by the self-contained units. The standard rating conditions for self-contained unit air conditioners, as given in the code, are set forth in Table 1.
The standard rating of a self-contained unit for the conditions specified in Table 1 includes all.items which apply to the function of a.unit as: (1) name of unit, (2) functions.which unit performs, (3) data on cooling, (4) data on heating, (5) data on air flow, and (6) data on humidification.
. The standard rating conditions for unit air conditioners, other than the self-contained type, are identical with those in Table 1 except the entering wet-bulb temperature for cooling is expressed-; as 50 per cent relative humidity (66.7 F wet-bulb) instead of 67 F wet-bulb temperature. In
Unit Air Conditioners, Unit Air Coolers
705
addition, the saturated ;suction refrigerant temperature for comfort cooling is specified at 40 F. This condition is omitted from Table 1 for self-contained units as immaterial in the rating of a unit .that includes the
evaporator and condensing unit.
Table 1. - Standard Rating Basis fob Self-Contained Am Conditioning Units
Functions
Types of Units
Item
. Rating Condition Description
Value
All
All a Barometric Pressure
29.92 in.-Hg.
b Unit Ambient, and Air Entering
Water-Cooled,
Room--Air Inlet
Air-Cooled
(1) Dry-Bulb
80 F
and Evapora-
(2) Wet-Bulb
. 67 F.
tively-Cooled
Condensers c Ventilation Air
See Note
Cooling .
Water-Cooled d Water Temperature Entering Unit e Water Temperature Leaving Unit
75 F 95 F.
Air-Cooled and Evapora?.
tively-Cooled Condensers ''
t
Air Entering Outside Air Inlet (1) Dry-Bulb . ... (2) Wet-Bulb
95 F 75 F
Heating
All Types
Provided with Heating
Function
g Unit Ambient and Total Air. Enter ing Unit
70 f ;
h. Heating Medium, Pressure or Temperature (1) Dry Saturated Steam
(2).Water In (3) Water Oiit
16.7 lb per sq in. abs
180 F 160 F
All Types i Unit Ambient.
Provided with
Humidifying Humidifying
Total Air Entering Unit
Function '
(1) Dry-Bulb
(2) Wet-Bulb
70 F
70 F. ' 53 F
Air Circulation '
All
k Filters
J New and Clean
Note: Rating shall be based on .both ventilation and recirculated room air entering at 80 F dry-bulb
and 67 F wet-bulb temperature- (The Note as given in the code has been condensed in order to remove ma terial not pertinent to this chapter). *
APPLICATION OF UNITARY EQUIPMENT
One of the chief advantages resulting from use of factory produced units is the saving in installation and field assembly labor, a factor that should always be kept in mind when selecting a location for these units. Because of their compactness, the tendency exists to put them in closets, storage rooms, and other inaccessible places; where- installation is so difficult that much of this cost advantage is lost.
Access panels are provided on units for the proper servicing and main tenance of the equipment. Adequate outside clearance at/these panels is