EPRI EL7EA-5443 Volume 2 Project 2028-6 Final Report March 1988
Analysis of Polychlorinated Dibenzofurans and Polychlorinated Dibenzo-p-Dioxins in Transformers and Capacitors
Volume 2; Formation of PCOF and PCDD in Askarel and Contaminated Mineral Oil Equipment
Prepared by Sattette Memorial institul* Columpus, Ohio
MOHS 216436
REPORT SUMMARY
SUBJECTS Hazardous and toxic west* management / Transmission substation design and operation / Distribution substations
TOPICS PCB Chemical analysis Transformers
Capacitors PCDF-PCDD Insulating oil
AUDIENCE Environmental managers / Distribution engineers
Analysis of Polychlorinated Wbenzofurans and Polychlorinated Dlbenzo-p-DloxIns In Transformers and Capacitors
Volumes 1-3
PCDF and PCDD--by-products of PCB pyrolysis and combus tion--apparently cause many of the health effects originally attributed to PCB. In parallel and round-robin studies, indepen dent laboratories found that normal equipment operation and arc ing failure cause little if any oxidation and do not significantly modify PCB fluids.
BACKGROUND
Partial oxidation of aakarels--mixtures of polychlorinated biphenyls (PCS) end tri- end tetrachkwobenzenes--produces polychlorinated dibenzofurans (PCDF) and polychlorinated dibenzo-p-dloxlns (PCDD). However, analytic techniques for separating the active components in these mixtures had not matured prior to this study. Information had also been insufficient on the quantity and types of PCDP and PCDD in ae-manufactured PCB and on the formation of these by-products during normal operation or arcing failure in utility equipment. Because of these uncertainties, utilities and regulators hava assumed the worst-case PCDF-PCDD formation when there is a PC 8related accident, thereby overstating the potential toxicity. EPRi report EL/EA-48S8 describee portions ol the research performed in these protects.
OBJECTIVE To improve techniques for measuring PCDF/PCDD In the presence ol PCB
APPROACH
Five laboratories (including two whose studies are discussed in report EL/EA-4858) performed round-robin gas chromatography-mass spectrome try analyses of PCDF-PCDD samples using specially prepared carbon-13 (1SC) PCDF spiking compounds. After the first Set of analyses, each labora tory modified its techniques and analyzed a larger group ol samples Irom utility equipment. Another organization statistically analyzed all the labora tory results.
RESULTS These three volumes report the second group of PCDF-PCDD analyses Results from all participating laboratories correlated remarkably well Some ol the results follow.
EPRI EUEA-S440* Von. -}
HONS 218437
Use of the <3C compounds allowed successful separation of the com ponents in several closely eluting pairs of physiologically active PCDF and less-active compounds.
Analyses of samples from utility equipment suggested that the PCDF-PCDD present did not result from high-load, high-temperalure operation.
Volumes 1 and 2 describe several analytic techniques, with the appen dix of Volume 2 including a report on the analysis by the University of Umei In Sweden, as well. Volume 3 summarizes all the laboratory techniques, presents comprehensive statistical analyses, and provides an executive summary.
EPRI PERSPECTIVE
This research is e landmark in PCDF-PCDD analysis. One important result is the synthesis of new PCDFs tor use as piking compounds in gas chromatography-mass spectrometry analysis. The ability to sepa rate many of the active PCDF compounds from more innocuous materi als is also of great value. The high correlation of results from several laboratories indicates that researchers can exercise great flexibiiily in selecting techniques and developing facilities.
PROJECTS
RP202B-7, RP2028-6, RP2028-10 EPRI Project Managers: Gil Addis; Jacques Guertin Electrical Systems Division; Environment Division Contractors: New York State Department of Health; Battalia Columbus Laboratories: Research Triangle Institute
For further information on EPRI research programs, call EPRI Technical Information Specialists (415) 855-2411.
MONS 216*36
Analysis of Polychlorinated Dibenzofurans and Polychlorinated Dibenzo-p-Dioxins in Transformers
and Capacitors Volume 2: Formation of PCOF and PCOD in AsKarel and
Contaminated Mineral Oil Equipment
EUEA-5443, Volume 2 Research Project 2028-6
Final Report, March 1968
Prepared by
BATTELLE MEMORIAL INSTITUTE BatteUe Columbus Division 505 King Avenue Columbus, Ohio 43201-2693
Principal investigators W. M. Cooke F, L DeRoos
With contributions from
umeA university Department ol Organic Chemistry
Umeii. Sweden S-901 87
Principal Investigator C. Rappe
Prepared lor
Electric Power Research institute 3412 Hiltview Avenue
Palo Alto, California 94304
EPRI Project Managers G. Addis
Transmission Substations Program Electrical Systems (Division
J. Guertm Land and Water Quality Studies Program
Environment Division
218439
ORDERING INFORMATION
Requests tor copies of this report should be directed to Research Reports Center (RRC). Box 5W90 Pato Alto. CA 9*303. (415) 965-4081 There is no Charge tor reports requested by EPRI member utilities and affiliates, U S utility associations US. government agencies (federal, state, and local), media, and foreign organizations with which EPRt has an information exchange agreement On request. RRC wtf send a dialog of EPRI reports.
NOTICE
raooA wi piBoro oy BATTEiLE w V account of worn wonaorac tty ** Elacirc Pcw< Rtaaare*
Imtitul*. Inc
N**h*r EPfli mrrtMrt of EPftl. aATTELLE. nor any paraon acting on mW of arry of lham
(I w ffwv
o> *np*#d- wwn ragpaci 10 m uh of any mtormwon. aooasitui mathOO, or
Dtooat* oaetoaao n ma faoon or mat *uch uaa may not H*nngt onvotary ownad nQhtt: or ftfi lauanat any
babtittiat with raoaa uiMuHOf. or for oamtoat tatuamo from uaa ot. any rtotmmon aoparatui macnoo
ot proeata aactoaao -ri iru* taoort
Funnoimora .i any *am (for aiamofe a mooat. omtorvoa or iait-o*aeai aa^vafd punuant to tfw Vunrm it Shall carry ho warranty or Guarantee whatsoever including warranties op fitness FOR PURPOSE OR OF MERCHANTABILITY
HONS 218**0
ABSTRACT
A study was conducted by five Independent laboratories to evaluate Methods for the measurement of trace levels of polychlorinated dfbenzofurans (PCDFs) and polychlorinated dibenzo-p-dloxlns (PCDDs) In utility dielectric 11 quids. Each laboratory evaluated a different analytical method. The method evaluated by Battelle Involved spiking with labelled Internal standards, analyte enrichment by column chromatography, and analysis by high resolution gas chromatography/high resolution mass spectrometry (HR6C/HRMS). Baseline analyses of five dielectric fluids were conducted by each laboratory as an Initial test of their methods. The variability of results between the five methods was within expectations, and the five methods were deemed suitable for round robin evaluation. In the round robin evaluation, the five methods were used to analyze 10 liquid samples, Including seven utility dielectric fluids. The liquid samples were spiked with native PCDD/PCDF to estimate accuracy. The Battelle results were generally within 70 percent of the spike value except for KxCDF which exhibited a strong positive bias. This result was considered an outlier. The 8attel1e results were consistently lower than the average results obtained for the five laboratories. Overall, the methods proved to be both rugged and reliable when used with labelled quantification and recovery standards. The In-service liquids used In this study were found to have relatively low levels of PCDDs and trace amounts of PCDF. Liquids from transformers with more than 25 years of service had higher PCDF levels than liquids from newer transformers. Liquids from utility appliances exposed to thermal and electrical stresses did not have elevated PCDD or PCDF levels. PCDF levels Increased as the Aroclor number (and relative amount of chlorination) Increased.
HONS 216441
Ill
acknowledgments
The authors would like to thank the EPRI technical management team led by
Dr. Gilbert Addis,
Dr, Addis and his colleagues. Dr, Jacques Guertin, and
Dr. Ralph Komai, guided this program and provided encouragement to all the
participants. Dr. Thomas Rouse (General Electric Company) is acknowledged for his
contributions concerning utility use of dielectric liquids and development of the
engineering stress test protocols.
The authors are grateful for the technical assistance provided by Battel 1 e scientists who developed the methods, and performed the analyses reported in this document. Sample preparation was coordinated by Joe Hatchel, data computation was conducted by Susan Watson, and mass spectral analyses were performed by Oan Aichele, Charles Sueper, and Michael Zimmerman.
We would also like to thank our colleagues who contributed the parallel analyses to this interlaboratory collaborative study. They are Dr. Sydney Gordon (Illinois Institute of Technology Research Institute), Drs. George Eadon and David Hllker (New York State Department of Health), Ms. Maureen Kilpatrick (Radian Corporation), Dr. Edo Pelll22ari (Research Triangle Institute), and Dr. Chrlstoffer Rappe (University of Umea).
i
V HONS 218442
contents
Sg&llflfl 1 INTRODUCTION
2 EXPERIMENTAL ACQUISITION OF IN-SERVICESAMPLES ANALYTICAL TECHNIQUES SAMPLE PREPARATION ANDSPIKING ANALYTE ENRICHMENT ANALYSIS QUALITY ASSURANCE RECOVERY OF INTERNAL STANDARDS QUANTIFICATION CALIBRATION CURVE DETECTION LIMITS BASELINE ANALYSES IN-SERVICE ANALYSES
3 BASELINE ANALYSES BACKGROUND RESEARCH STANDARDS USED FOR SPIKING RESULTS Chemical Analyses Baseline Recovary Data Method Rallability
4 SUPPLEMENTAL ANALYSES CROSS CHECK ANALYSES ANALYSES FROM THE UNIVERSITY OF UMEA
5 ROUND ROBIN ANALYSES OF IN-SERVICELIQUIDS Accuracy Estimate Comparison with ParallelAnalyses
6 DISCUSSION
vli
431 1-1
2-1 2-1 2-2 2-2 2-4 2-5 2-5 2-5 2-6 2-7 2-8 2-8 2-8
3-1 3-1 3-2 3-4 3-4 3-4 3-10
4-1 4-1 4-1
5-1 5-1 5-13
6-1
HONS 218^43
Section
METHODS IN-SERVICE liquid ANALYSES SUMMARY
appendix a
APPENDIX B APPENDIX C
in-service liquid questionnaire ANALYTICAL CURVE DATA FOR THE CRDSS CHECK ANALYSES LETTER REPORT FROM UMEA
EiSfi 6-1 6-2 6-3
a-i B-l C-l
HONS 218444
vi 1 i
ILLUSTRATIONS
USUIS 4-1 Calibration curve for Z^.T.B-tetrachlorodlbenzofuran over
the range 40 pg to 2,5 ng
PiSi 4.2
lx MOMS 218445
TABLES
Table 2.1 EQUIPMENT RECOMMENDED FOR SAMPLING FOR PCDF AND PCDD ANALYSES 2.2 SURVEY OF LIQUID SAMPLES AVAILABLE FOR THE IN-SERVICE
TRANSFORMER LIQUIDS STUDY 3.1 BASELINE TEST LIQUIDS 3.2 CONCENTRATION OF PCDF/PCDD STANDARDS SPIKED INTO TRANSFORMER
LIQUIDS 3.3 BATTELLE FURAN AND DIOXIN DATA FOR THE BASELINE ANALYSES STUDY 3.4 IITRI FURAN AND DIDXIN DATA FOR THE BASELINE ANALYSES STUDY 3.5 NYSDOH FURAN AND DIDXIN DATA FOR THE BASELINE ANALYSES STUDY 3.6 RADIAN FURAN AND DIOXIN DATA FOR THE BASELINE ANALYSES STUDY 3.7 ABSOLUTE RECOVERIES OF LABELLED STANDARDS IN THE BASELINE STUDY 3.8 FIVE LABORATORY RESULTS OF ANALYSIS OF AGED MINERAL OIL 5.1 CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE ISL-02-A 5.2 CHLORINATED FURAN AND DIDXIN RESULTS - SAMPLE ISL-03-A 5.3 CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE ISL-04-0 5.4 CHLORINATED FURAN AND DIDXIN RESULTS - SAMPLE ISL-08-A 5.5 CHLORINATED FURAN AND DIDXIN RESULTS - SAMPLE ISL-I7-A 5.6 CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE ISL-23-0 5.7 CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE ISL-27 5.B CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE EZ29-53-01 5.9 CHLORINATED FURAN AND DIOXIN RESULTS - SAMPLE E729-53-02 5.10 CHLORINATED FURAN AND OIOXIN RESULTS - SAMPLE E229-53-03 5.11 ACCURACY DETERMINATION USING SPIKED BASELINE LIQUID ANALYSES 5.12 MEAN FURAN RESULTS FOR SEVEN UTILITY DIELECTRIC FLUIDS
Pace 2-2
2-3 3-1
3-3 3-5 3-6 3-7 3-8 3-9 3-11 5-2 5-3 5-4 5-5 5-6 5-7 5-B 5-9 5-10 5-11 5-12 5-14
xl
HONS 218446
SUMMARY SYNOPSIS This report describes a study to develop reliable methods for the chemical analysis of polychlorinated dlbenzo-p-dloxlns (PCDD) and polychlorinated dlbenzofurans (PCDF) In utility dielectric liquids. Prior to this study a great deal of data was available on levels of PCDD and PCDF In utility fluids; but since the methods used to obtain this data had never been rigorously challenged In a statistically valid study, the reliability of the existing data bases was suspect. Current analytical methods are affected by high levels of polychlorinated biphenyl (PCB). Since PCB Is an Interferent In most methods proposed for the analysis of PCDO/PCDF, and many existing utility test appliances contain PCB as the major dielectric fluid or as a contaminant of other fluids (due to residual PCB), Investigation of reliable analytical methods was warranted.
Five Independent laboratories participated In this program. Each laboratory employed a different analytical procedure to measure trace levels of PCDF and PCDD in dielectric liquids. The method used by Battelle Involved spiking with labelled Internal standards, analyte enrichment by multiple column chromatography, and analysis by high-resolution gas chromatography/hlgh-resolutlon mass spectrometry (HRGC/HRMS).
BASELINE ANALYSES The first phase of this study, baseline analyses. Involved comparing methods for analyzing difficult matrices; e.a.. Arodor. Baseline analyses of five dielectric fluids were conducted by each laboratory as an Initial test of their methods. The variability of results among the five methods was within expected levels. The five analytical procedures proved to be rugged and reliable when used with 1sotoplcal 1 y labelled, quantification end recovery standards. Use of labelled standards is especially Important In the Askarel and mineral oil matrices since the high organic burden found In these materials requires secondary partitioning to remove Interfering PCB and background hydrocarbons.
S-l HONS 218447
The relative average deviation is the absolute difference between individual results and the mean (or true value), divided by the number of determinations. For samples such as Aroclor 1242< Aroclor 1016, and mineral oil, the average deviation for baseline samples was often less than 50 percent. This result was found in individual laboratory replicate analyses and In grouped data from different laboratories. All five mothods were deemed suitable for use In the second phase of the program.
ROUNO ROBIN STATISTICAL ANALYSIS
The second phase of the study involved a more severe test, a round robin
statistical evaluation that employed field samples collected from in-service
utility applications.
In the round robin evaluation, the five Independent
laboratories used different methods to analyze 10 liquid samples, including seven
utility dielectric fluids. The in-service dielectric liquid samples were collected
from four Askarel-fl1 led network transformers, one arc furnace transformer, one
electrostatic precipitator (ESP) transformer, and one capacitor.
The Battelle results were generally within 70 percent of the spike value except for hexachlorodlbenzofurans, which exhibited a strong positive bias. This result was considered an outlier. The Battelle results were consistently lower than the average of results obtained for data from all five laboratories.
All samples of the in-service liquids tested had relatively low amounts of PCOD. This result supports the hypothesis that dioxins are not a major constituent of Askarel and PCB-contalning fluids. Except for the mineral oils, trace amounts of polychlorinated dibenzofurans were found In all of the Aroclor samples tested. The mineral oil samples had extremely low amounts, if any, of PCDF. Even the in service liquid from Transformer 4, a network distribution transformer that was involved in a high-energy excursion, had minimal amounts of PCDD and PCDF.
Transformer 4 had visible carbon, and major signs of scorching on the case and In
the area of the electrodes.
The Askarel transformers with more than 25 years of service tended to have higher levels of PCDF than the appliances put Into service for a shorter time. It is possible that manufacturing controls Improved as the production of Askarel matured in the 1960s such that Askarel was produced with lower levels of PCDF in the as* delivered fluids.
5-2
HOHS 216448
Two utility appliances were selected by the EPRI Technic*! Advisory Committee for spec fat attention: *n AskereT-filled ESP tr*nsformer and an oil-filled arc furnace transformer, These two samples were the "worst case" for testing service stress on the dielectric fluids. The arc furnace had essentially no PCDF or PCDD, and the PCDF levels In the ESP transformer appeared to be dictated by the age of the unit (27 years of service) and the fluid composition (Aroclor 1260). This extended period of stress did not appear to elevate the PCDF levels above typical Aroclor 1260 levels.
One capacitor was tested in the In-service liquid screening program. It was found to have relatively low levels of PCDF compared to the other Askarel-filled units.
CONCH'S IONS The in-service liquids used In this study were found to have minimal levels of PCDD and only trace amounts of PCDF. Liquids from transformers with more than 25 years of service had higher PCDF levels than liquids from newer transformers. Liquids from utility appliances exposed to thermal and electrical stresses did not show elevated PCDD or PCDF levels, indicating that high-energy events (electrical and thermal excursions) do not appear to generate PCDD or PCDF in utility electrical appliances that employ PC6. PCDF levels increased as the Aroclor number (and relative amount of chlorination) Increased.
This study was successful In developing a set of methodologies that reliably determine trace levels of PCDF and PCDO In a very difficult matrix -- chlorinated organic oil. The development of commercially available reference standards, and the statistical validation of reference methods that can be used to analyze utility fluids was a major contribution to the quality and defens 1b111ty of data. The method verification program showed that a range of instrumentation can be successfully used to measure trace levels of PCDF and PCDD In utility fluids. In general, the methods employing low-resolution mass spectrometry (LRHS) require additional column chromatography to Isolate PCDF/PCDD-enrlched fractions for final HRGC/LRMS analysis. The precision of blind, spiked samples was superior to that expected by experienced analysts who had previously performed these analyses. The availability of labelled quantification standards helped Improve method performance and lowered data scatter.
MONS 218449
Section 1 INTRODUCTION
The Electric Power Research Institute Initiated this program to Investigate the
chemistry and analysis of polychlorinated dlbenzofurans (PCDF) and polychlorinated
dibenzo-p-dioxins (PCDD) as they relate to the utility use of Askarel, a dielectric
liquid which contains polychlorinated biphenyl (PCB), frequently diluted with
trl/tetra chlorinated benzene. Askarel Is sometimes contaminated with traces of
PCDF/PCDD,
The program had three goals; (I) to develop reliable, well
characterized analytical methods to measure PCDF/PCDD, (2) to measure PCDF/PCDD
levels in typical dielectric liquids used in utility operations, and (3) to
investigate possible PCDF/PCDD production in unusual transformer events such as
high energy arcing.
This report describes analytical methodology and results of chemical analyses conducted by Battelle Columbus Division In support of EPRI Research Project 2020 6, "Formation of PCDD and PCDF in Askarel and Contaminated Mineral Dll Equipment". Chemical laboratories of four additional organizations conducted parallel measurements during this program: the Illinois Institute of Technology Research Institute, the New York State Department of Health, Radian Corporation, and the University of UMEA (Sweden). The data presented In this report were replicated by these four laboratories and separate reports ere available from each of the study participants. Combined data from the replicate analyses conducted by the five collaborating laboratories (Including Battelle), are presented In a summary report prepared by the Research Triangle Institute. The summary report examines pooled data and gives a rigorous statistical analysis, Including variability and reliability of analytical results reported by laboratories routinely conducting PCDF/PCDD analyses In Askarel, mineral oil, and related sample matrices.
Reliable analytical methods are especially difficult to develop for Askarel since PCB constitutes the major Interference In most PCDF/PCDD analytical methods. In Askarel, the normal PCB concentration Is 60-70 percent by weight. Thus, Askarel presents perhaps the most difficult matrix for these analyses. Parts-per-bl 11 ion (ppb) levels of PCDF, and even lower concentrations of PCDD must be measured. When this program was Initiated In early I9B4, the accuracy of PCDF analyses was hampered by a lack of accurate quantification standards. A major product of this
1-1
MONS 218450
i
study was the synthesis of a series of I3C-label led PCDF standards that allowed use of sensitive Isotope dilution techniques to measure PCDF. Quantification end recovery measurements based on labelled standards permit the chemist to measure accurate mass spectral response ratios for naturally occurring PCDF (and PCDD) compared to the response factors of labelled standards spiked Into the sample matrix.
The method development phase Involved testing methods proposed by the five participating laboratories; Battelle, the Illinois Institute of Technology, Research Institute (IITRI), the New York State Department of Health (NYS). Radian Corporation, and the University of Umea. These five methods were challenged by analyzing PCDF/PCDD In baseline liquids, a series of five typical sample matrices Aroclor 1260, Aroclor 1242, Aroclor 1016, chlorobenzene, and mineral oil containing approximately SO ppm of Aroclor 1260. The baseline Askarel liquids contained native PCDF/PCDD, and the mineral oil was spiked with labelled PCDF.
The presence of PCDF/PCDD In typical utility liquids was Investigated by measuring characteristic compounds and congener groups In samples provided by EPRI member utilities. A report was generated by the General Electric Company which outlined the main types and distribution of PCB containing liquids (I). A repository was established at Battelle where samples of transformer oils provided by several EPRI members were stored. A questionnaire was developed, and a data base was accumulated on the repository samples. Seven of these liquids were selected by the EPRI Technical Advisory Committee. The seven samples, along with three control liquids, were analyzed by the participating laboratories. The seven "In-service" liquids selected for analysis represented either high energy operation, or utility applications that typify PCB usage. The data collected In the In-service liquid study were analyzed by chemists and statisticians at the Research Triangle Institute (RT1). A separate report will be generated by RTI that summarizes the results of all five laboratories. In summary, the Independent methods worked well, Indicating that good results can be expected when appropriate quality control procedures are applied.
Arcing experiments were conducted by General Electric. Transformer test units were fabricated out of the normal materials of transformer construction. These test units were exposed to high electric energy such as might be expected >n catastrophic transformer failure. In the engineering tests, final PCDF/PCDD levels were either the same or lowered from Initial levels, indicating that short ten*
1-2
MONS 218461
lectrlcil dt.ch.rw, ire ret . prl.ir, seerce
trjnsformer liquids.
prrdrctl.r f,, pcDf/KM '
1-3
HONS 218*52
Section 2 EXPERIMENTAL
ACQUISITION OF IN-SERVICE SAMPLES The selection of In-service dielectric fluids for this study was coordinated by the EPRI Technical Advisory Committee with the assistance of Or. Thomas Rouse of the General Electric Company. It was important to select a series of in-servke liquids that represented a range of utility applications, In the early planning for this program, Dr. Rouse prepared a criteria document that discussed the distribution of Askarel among different types of electrical devices, the relative chemical stresses expected from these devices In normal usage, the dispersion of Askarels, heating processes In transformers, and situations that represent the worst case for Askarel usage. He estimated that the United States has 140,000 Askarel-flUed transformers In service, 30 million oil-filled transformers, and S10 million power capacitors. The oil-filled transformers constitute a large number; however, only about 50,000 are considered PCB-contalnlng (>500 ppm (w/w)). and another approximately I million are PCB-contamlnated (50-500 ppm). Since PCDf and PCDD are minor constituents of PCB, PCB-containlng and PCB-contamlnated transformers are expected to contain very low concentrations of PCDF/PCDD (perhaps not measurable). Dr. Rouse published an EPRI report (1) In which he recommended establishing a repository of 30-40 In-service samples that would be reviewed by the technical advisory group to select a final set of In-service liquids for exhaustive testing by the methods developed In this program.
The samples recommended by Or. Rouse for Inclusion In the final test group are given In Table 2-1.
In order to acquire suitable samples for this study, several participating utility representatives were asked to survey their records on available samples, searching for dielectric materials that met the criteria established by Or. Rouse. To prescreen the available samples, a questionnaire was developed and a data base of questionnaire Information maintained. A copy of the questionnaire Is given in Appendix A.
2-1 MONS 218453
TABLE 2.1
EQUIPMENT RECOMMENDED FOR SAMPLING FOR PCDF AND PCDD ANALYSES
ASKAREL-FILLED Load Center/Network Transformers Rectifier Transformers Precipitator Transformers Capacitors
8-10 1-2
2 4
OIL-FILLED WITH PCB Load Center/hetwork Transformers
4
After gathering completed questionnaires on a large number of candidate fluids, a repository was established, that contained the samples listed In Table 2.1. As shown In Table 2.2, suitable dielectric liquids were collected from each of the categories of Interest. A final selection was made using Information in the repository data base, and the materials listed In the last column of Table 2.2 were selected for Inclusion In the In-service testing program.
ANALYTICAL TECHNIQUES
The following method description gives the procedures that were used by Battelle to analyze all Askarel and mineral oil samples In this program. The samples preparation procedures, the spiking protocols, the Instrumental conditions, and the equations used to calculate final results are given here. The oil samples (five ''baseline" samples) were spiked with labelled Internal standards prior to distribution to the participating laboratories. The sample preparation and spiking procedure* for the baseline liquids are given In a separate report In this series prepared by Radian Corporation (Austin, TX).
SAMPLE PREPARATION AND SPIKING
The seven In-service liquids were diluted to a concentration of approximately 2 pg/mL with hexane prior to spiking with Internal standards. Aliquots of eacn liquid were weighed by difference Into 100 mL volumetric flasks which were then filled to the mark with Oistl1 led-In-Glass hexane. The flasks were placed on a
HONS 218454
s u m ti r 1 1 4 m s im u s m a iiw u fo in t iu .m m iu TM m roM R liquids sw ot
HONS 2 1 8 4 5 5
S8 StSfSSr s S ? # ^ 3*^
s 3
8l
** =
8
>i si
BB
1! B illmmis
ss
S=8*28 I isffssHHs
!
S kkfcfcfcfcfcfckfcfefckkfchhfchV MM M MMMM MM M M M MM MM MM MM
ii
n I 11311131133111113211wmwxm
liiliiiiitiliiiiiiii
M M mmmmmmmmmMMMmmmMmm IIIIIIIIIIIIIIIIIIII
IM
2-3
mechanical shaker and mixed overnight. After approximately 12 hours of mixing, the flesks were removed from the shaker and spiked with the five Isotoplcally labelled internal standards. The Internal standards were: ?,3,7,8-TCOD-13C!2 2,3.7,8TCDF-l3Cl2, l,2.3.7,8-Penta-CDF-13Clz, l^J^^.S-Hexa-COF-l3^, and Qcta-CDD13Ci2.
ANALYTE ENRICHMENT
One-milllllter aliquots (containing `250 mg of the original fluid) of each sample were transferred to separatory funnels and diluted with 49 L of hexane. The hexane solutions were washed with 10-mL portions of concentrated sulfuric acid until the washes were only slightly colored, A maximum of five acid washes were used. Following the acid washes, each oil was washed with 20 mL of distilled water to remove any residual acid. The hexane solutions were transferred to glass collection tubes and concentrated to approximately 2 ml using gentle streams of nitrogen gas.
The hexane solutions were transferred to multilayered silica gel columns containing activated silica gel, 44 percent concentrated sulfuric acid on silica gel, and 33 percent 1M sodium hydroxide on silica gel. The purpose of these columns was to remove acidic and basic compounds from the solutions as well as materials that were easily oxidized. The silica gel support provided a large surface area for contact with the sample solutions thus Improving the cleanup efficiency. The PCDO/PCDF Isomers were eluted from the columns using 70 mL of hexane and the entire eluents, Including the original sample volume, were collected.
The eluates from the multilayered silica gel columns were concentrated to approximately 1 ml using gentle streams of nitrogen and transferred to the top of columns containing 5 g of activated basic alumina. These columns were eluted using hexane, hexane/methylene chloride (97:3, v/v) and hexane/methylene chloride (1:1, v/v) as elution solvents. The 1:1 hexane/methylene chloride eluates were collected, solvent exchanged Into hexane, and transferred to the top of alumina columns containing approximately 2 g of activated basic alumina. These columns were eluted with hexane, hexane/methylene chloride (97:3, v/v), and hexane/ methylene chloride (1:1, v/v). The 1:1 hexane/methylene chloride eluates were collected, concentrated to near dryness with nitrogen gas, and spiked with 10 ng of 1,2,3,4-TCOD*33Cj2 These solutions were stored at 0C until they were analyzed.
Several, of the sample solutions were still too contaminated with Interferences to
be analyzed.
These solutions (41159-11*12.13,14,17 and E729-53-02,03) were
2-4
HONS 218456
chromatographed through florisil columns to provide additional analyte enrichment. Each of the florisil columns was prepared using 5 g of activated florisil (60-100 mesh) which was slurry packed with hexane. The sample solutions were diluted with approximately 5 mL of hexane and transferred to the florisil columns. The columns were eluted with hexane, hexane/ethyl ether (94-,6, v/v), and hexane/methylene chloride (25:75, v/v), The 25:75 hexane/methylene chloride fraction was collected and concentrated to approximately 20 pL. These solutions were stored at 0C until they were analyzed.
ANALYSIS
The sample solutions were analyzed and quantified for PCDO/PCDF using combined capillary column gas chromatography/high resolution mass spectrometry (HRGC/HRMS). The HRGC/HRMS consisted of a Carlo Erba Model 4160 Gas Chromatograph Interfaced directly into the Ion source of a VG Model 7070 high resolution mass spectrometer. The chromatographic column was a 60 M OB-5 fused silica column using helium carrier gas at a flow velocity of 30 cm/sec. The mass spectrometer was operated In the electron Impact (El) Ionization mode at a mass resolution of 9000-12000 (M/ M, 10 percent valley definition). All HRGC/HRMS data were acquired by multfpie-iondetection (MID) using a VG Model 203S Data System.
QUALITY ASSURANCE
The operation of the HRGC/HRMS was evaluated each day by analyzing standard
mixtures of selected PCDD/PC0F compounds.
These were used to define the
chromatographic elution windows, the compound resolution of the chromatographic
column, and to verify the quantitative accuracy of the analyses. The mass focus
accuracy of the MID unit was evaluated at least every four hours by observing
selected Ion masses from perfluorokerosene (PFK) which was introduced continually
Into the ion source as a reference compound. Mass focus stability was assured by
using a reference PFK "lock mass" to correct for any mass focus drift.
Native spike and laboratory method blank samples were also processed during the
extraction and cleanup of the samples.
The native spike samples were used to
evaluate the accuracy of the quantification while the laboratory method blank
sample was used to demonstrate freedom from laboratory contamination.
RECOVERY OF INTERNAL STANDARDS
The recoveries of the Internal standards were calculated by comparison to an
external standard, l,2,3,4-TCDO-^Ci2 which was added following the column cleanup
steps.
Relative response factors were determined from triplicate analyses of a
2-5
HONS 218457
standard mixture containing the libelled internal standards and the J ,2,3,4-TCOD13c^j The equation used to calculate the recoveries was;
Recovery (%)
Als x Urs x IpO Ars x Qi s x Rf
Where;
Ais * Sum of integrated areas for internal Qrs - Quantity of recovery standard In ng; 01s - Quantity of internal standard In ng; Ars - Sum of Integrated areas for recovery
Rf Response factor.
standard; standard;
and
QUANTIFICATION
The PCDO/PCDF isomers and congener class concentrations were determined by comparing the sum of the two Ion masses monitored for each class to the sum of the two ion masses monitored for the corresponding internal standard. It was assumed that the response factors for each of the individual isomers In a class were the same as the response factors calculated for the specific isomers present in the standard solutions. The response factors were calculated from six replicate analyses of standard solutions at four concentrations. The sum of the two most intense Ion masses in the molecular Ion region of eachisomer were used to generate the response factors.
The formula used for quantifying the PCDO/PCDF isomers was:
Quantlty/Sample (ng/g) * Aif^Rf^W
Where;
Quantity Total quantity In ng of target Isomer or congener class Ac Sum of integrated areas for the target Isomer or congener class
Qis * Quantity of internal standard in ng Als Total integrated areas for the Internal standard
Rf Response factor.
Each pair of resolved peaks in the $elected-1on-current chromatograms was evaluated manually to determine if it met the criteria for a PCDD or PCDF isomer. By examining each pair of peaks separately, quantitative accuracy was improved over what is obtained when all of the peaks in a selected chromatographic window are averaged. When averaged data are used, It ts possible for pairs of peaks with high and low chlorine Isotope ratios to produce averaged data that meet the chlorine Isotope ratio criterion. For example, two pairs of peaks having chlorine Isotope ratios of 0,56 and 0.96, both outside of the acceptable range, would have ar.
2-6
HONS 218458
average ratio of 0.76. By checking the isotope ratio of these peaks separately, they would be eliminated from the class total.
The criteria that were used to identify PCOD and PCOF Isomers were:
1. Simultaneous responses at buth Ion masses. 2. Chlorine isotope ratio within +/-35S of the theoretical value. 3. Chromatographic retention times within windows determined from analyses of
standard mixtures. 4. Signal-to-nolse ratio equal to or greater than 2.5 to 1.0.
The Individual isomers for which an Isotoplcally labelled analog was available Included the additional criterion that they eluted within 2 seconds of the Internal standard.
The limit of detection (LOO) was calculated for samples in which isomers of a particular chlorine congener class were not detected. The formula used for calculating the LOD was:
LtuOuD//ga (tnngajl -- HCHisX x RS fJ1x2W15
Where: LOD Single isomer limits of detection for a congener class in ng; He Height of congener class isomer; Qis > Quantity of internal standard in ng; His - Peak height of Internal standard; Rf - Response factor; and W Weight In grams of sample.
CALIBRATION CURVE Calibration curves were generated for each of the native/1sotopically labelled isomer pairs. The calibration standards were analyzed at least five times at each of four concentration levels between 0,04 and 2.5 parts-per-mfllion (ppm). The response factors were calculated by dividing the sum of the areas for the two most abundant ion masses In the molecular Ion cluster of each native PCDD/PCDF Isomer by the sum of the areas for the corresponding ion masses from the Isotoplcally labelled standard. The Isomer pairs for which response factors were calculated Included:
2-7 MOMS 218459
2.3.7.8-TCDD vs 2,3,7,8-TCD0-J3C12
2.3.7.8-TCOF ys 2,3,7,8-TCDF-13CJ2
OCDD vs OCOO-"Ci2 OCOF vs OCDD-13Ci? 1.2.3.7.8-Penta-CDF vs 1,2,3,7,8-Penta-CDF- 3Cj2 2.3.4.7.8-Penta-CDF vs i,2,3,7,8-Penta-CDf-13C12 1.2.3.4.7.8-Hexa-CDF vs i,2,3,4,7,8-Hexa-CDF-J3Ci2 2.3.4.6.7.8-Hexa-CDF vs 1,2,3,4,7,8-Hexa-CDF-l3C,2 1.2.3.4.6.7.8-Hepta-CDF vs OCDD-13C12
It was assumed that each of the Isomers of a particular chlorine congener class had the same response factor.
DETECTION LIMITS
Detection limits were calculated for samples that did not contain PCDD/PCDF isomers
in a particular class.
These detection limits were calculated using the
quantification equation with the addition of a factor of 2.5 to account for the
signal-to-nolse criterion.
The noise level was measured as the average of the peak to peak noise that occurred in the baseline of the particular MID channel. If at all possible, the noise was measured at the retention time of the Isotoplcally labelled internal standard. The height of the Internal standard peak was measured to the average of the noise that occurred on the peak top. The reported limits of detection are for single PCDO/PCOF isomers and have been corrected for recovery losses during sample workup.
BASELINE ANALYSES
The three baseline samples, Aroclor 1260, Aroclor 1254, and Arodor 1016, were analyzed using the methodology described above. The Aroclor 1016 presented the greatest analytical problem due to the relatively high amount of the sample that passed through the column cleanup steps. Even after the four column cleanup steps, a noticeable PCB background was evident in the single Ion current chromatograms.
IN-SERVICE ANALYSES
The seven In-service samples were also analyzed using the methodology described above.
2-8 HONS 218460
Section 3 BASELINE ANALYSES
This section describes the baseline analyses performed by til five laboratories partlclpating In this study. The baseline analyses were designed as a rigorous blind analysis of authentic Aroclor and mineral oil samples. If the proposed analytical methods performed well in the baseline tests, the additional steps of method validation, and screening of In-service utility fluids could be performed with confidence In the reported results. Consequently, the baseline analyses were critical to the success of this program.
BACKGROUND RESEARCH
Before the baseline analyses could be performed, five test liquids were obtained by Radian Corporation and a combination of native and labelled (*3C) PCDF/PCDD were spiked into the test liquids to ensure a rugged test of the proposed analytical techniques. The test liquids selected for the baseline study are listed In Table 3.1.
Dielectric Fluid Aroclor 1016 Aroclor 1242 Aroclor 1260 Chlorobenzenes
Aged Mineral Oil
TABLE 3.1
BASELINE TEST LIQUIDS
Composition
Narrow boiling point fraction of Aroclor 1242.
42% Cl (w/w)
60% Cl (w/w)
-Synthetic Mixture
1.2.4-Trichlorobenzene
(51.2% (w/w))
1,2,3-Trlchlorobenzene
(13,4% (w/w))
I,2,4,5-Tetrachlorobenzene ( 2.6% (w/w))
1.2.3.4-Tetrachlorobenzene (28.4% (w/w))
Pentachlorobenzene
( 4.4% (w/w)}
-Spiked Aroclor 1260 (500 ppm (w/w)} Trl/Tetrachlorobenzene Mix Listed Above
(500 ppm (w/w))
3-1 MOHS 218461
These five liquids ere a good challenge set of utility dielectric fluids since they represent the major Aroclor types found in utility operations along with a synthetic mineral oil spiked with 500 ppm (w/w) Aroclor 1260 end tr i / tetrachlorobenzenes. These five test liquids were selected to contain the major interferents end contamination problems that an analyst would face in handling any utility dielectric liquid.
STANDARDS USED FDR SPIKING
To challenge the five Independent analytical methods proposed by the participating
laboratories, a series of PCDF and PCDD standards were obtained. Since it is
advantageous to have at least one calibration standard for each congener class,
several compounds, both native and Isotoptcally labelled PCDF, were synthesized for
this program.
The labelled compounds were used by most participants as
quantification and recovery standards. The labelled PCDF/PCDD standards, in this
case all labelled standards incorporating Isotopically enriched carbon-13, were
added to the sample before laboratory extractions and isolation of the PCDF/PCDD.
Having an Isotopically labelled standard characteristic of each congener class
maximizes the accuracy of the final determinations. Since the labelled standard
corrects for any losses during sample preparation, the labelled standard should be
similar to the congener class being analyzed. In the ideal case, the analyst will
select a labelled standard for every analyte. Since only a few such standards are
available, one labelled standard may be used to quantify an entfre chlorination
number envelope. The standards and spike levels used In the baseline study are
given In Table 3.2.
The choice of standards In this program was governed by several considerations. PCDD levels are typically very low In PCB-contalnlng liquids. Also contaminated mineral oil contains Aroclors at <500 ppm. The expected PCDF levels In Aroclors would be a few millionths by weight of the Aroclor content. Very low PCDF levels and less PCDD would be expected In the aged mineral oil sample tested. The expected low concentrations of native PCDF/PCDD permitted use of native PCDF/PCDD standards in the mineral oil sample. Very little Interference would occur from native PCDF/PCDD In the mineral oil. The "Special PCDF/PCDD Mix" provided by Dr. Chrlstoffer Rappe (U. of Umea, Sweden) was only used to spike the mineral oil samples since all of the standards In his mixture were native furans.
3-2
HONS 21M2
TABLE 3.2
CONCENTRATION OF PCDF/PCOD STANDARDS SPIKED INTO TRANSFORMER LlQUIOS(ppb(w/w))
Compound
Total TCOO OCOD-13Cii 1,3,4-TrCuF ,, 2.3.7.8- TCDD-nCiZ
2.3.7.8- TCOO ,, 2.3.7.8- TCOF-l3Ci2 (3) 2.3.7.8- TCDF 2.3.4.8- TCDF 2,3,4,7,B-PnCDF ],2,3,7.8-PnCDF-l3C12 (3)
1.2.3.7,6-PnCOF (.3) 1.2.3.4.8- PnCDF 1.2.3.4.7.8- HxCDF 13) 1.2.3.4.6.7.8- HpCDF (3) Aroclor 1260 T/TCB
CD Spike Level Radian Mix
(2) Spike Level
Raooe Mix
100
100 0-100
100 0-150 0-150
100 0-150
0-150 0-150
116
100 100 100 510 530
Mineral Oil SaJKi-U+2)
100 116 100 UNK (4) 300 UNK {4} UNK (4) 100 100 UNK (4) 100 UNK (4) UNK (4) 510 530
(J) program. The spiking levels are shown for the "Baseline" experiments.
(2) These ere standards provided by Professor Chrlstoffer Rappe (U. of Umea, Sweden).
(3) Standards synthesUed for this program by Radian Corporation
(Austin, TX).
t<) UNK - Unknown. These standards were spiked blind end the statistical performance of blind data will be treated in another
volume in this series.
MONS 218463
3-3
RESULTS Chemical Analyse* The results of chemical analyses performed by Battelle on the baseline samples are given In Table 3.3. All results are given as parts-per-bil 1 Ion by weight in the original oil (ng/g).
These data are interesting because they show the expected trends in the Aroclor PCDF/PCDD concentrations. PCDD are not found it the detection limit of the high resolution mass spectrometer used for this analysis, approximately 10 ppb (w/w) in the mineral oil samples. Trice levels of PCDF are observed with the concen trations Increasing as the level of chlorination increases in the supporting Aroclor. The PCDF levels increase as the Aroclor number (and relative amount of chlorination increase), Aroclor 1260 >Arodor 1242 >Aroclor 1016. Even though Aroclor 1016 is similar in composition to Aroclor 1242, the wider distribution of PCB congener groups in Aroclor 1242 would produce higher quantities of the high chlorination number PCB, 6-10 chlorine atoms per molecule, which are believed to be the precursors of PCDF when HC1 elimination is the route for PCDF formation.
An increase in PCDF concentrations is shown In Table 3.3 as the total high chlorine PCB concentration Increases. Total PCDF levels increase from 280 ppb for Aroclor 1016, to 1,710 ppb for Aroclor 1242, to 10.4 ppm for Aroclor 1260. Oita for three of the participating laboratories are given in Tables 3.4 through 3.6. These data show the same trends observed in the Battelle data. The measured levels of spiked PCDF/PCDF were also similar among the reporting laboratories.
Baseline Recovery Data The recovery of labelled standards is used to determine how much of the native PCDF/PCDD present In the sample is lost during the sample preparation steps of candidate methods. Since the internal quantification standard corrects for method losses, the reported value should be accurate within the measured precision of the method: however, excessive loss of analytes during sample preparation will have a profound affect on both method sensitivity, and precision. Recoveries for s* labelled PCDF/PCDD standards spiked into the baseline samples are given in Tab'e 3.7.
These data are interesting because they show the outliers that can affec: individual data points.
HONS 218464
TABLE 3.3 BATTELLE FURAN ANO DIOXIN DATA FOR FHE BASELINE ANALYSES STUOY (ppb (*/*))
Compound Polychlorinated Diben^ofurans
Aroclor 1016
Aroclor
_
Aroclor 1260
Tri and Tetra Chlorobenzene
Mineral Oil
Run No. I
Mineral Oil
Run No.
Total TCDF Total PnCDF Total HxCOF Total HpCOF OCOF Total PCDF
Polychlorinated Dibenzodioxins
0 5 190 85 NR* 280
990 400
84 184
52 1710
640 2100 3100 2100 2500 10440
0
2
62 100 NR
184
119 IIS 270 228 278 246 128 113 152 157 947 859
Total TCDO tIn OCDO
0 00 NR NR NR
o NR
Specif it Molecules and Unresolved Molecular Clusters
2,3,7,8-TCOO 2,3,7,8 /2,3,4.8 TCDF 1.2>3,7,8-/1,2,3,4,8-PnCDF 2,3.4.7,8 PnCDF l,2,3,4,7.8-HxDF l,2,3,7,8,9-HxCDF 2,3,4.6,7,8-HxCDF 1,2,3.4,6,7,8-HpCDF
* NR-Not Reported.
0 00 0 84 150 0 54 480 0 00 190 84 1700 NR NR NR
NR NR NR
85 147 680
o 0 0 o
82 NR NR
too
32 34 NR NR
32 34 119 115 170 143
98 95 246 262 NR NR
NR NR 113 120
*ONs
TABtE 3.4 11IRI FURAN AMO OlOXIN DATA FOR THE BASELINE ANALYSES STUOY (ppb (w/w))
CoavowJ
Total TCOF Total PnCDF Total HxCOF Total HpCOF OCOF Total TCOO OCOO 2.3,7,8-TCOO 2.3,7,8/2,3,4,8-TCOF 1,2,3,7,8-/1,2,3,4,8-PnCDF 2,3,4,7,8-PnCDF 1,2,3,4,7,8-HxCOF 1,2,3,7,8,9-HxCOF 2,3,4,6,7,8 HxCOF 1,2,3,4,6,7,8-HpCDF
Aroclor
1016
30 42 92 81 20
0 0 0 8 11 0 76 0 0 58
Aroclor 1242
866 353 105 109 127
0 0 0 227 42 51 63 0 0 77
Aroclor 1260
612 1037 1433 1985 4154
0 1 0 193 231 88 601 0 0 684
Tri and Tetra
Chlorobenzene
0 0 103 98 0 0 l 0 0 0 0 103 0 0 98
Mineral Oil Aaed
70 165 207 40 393
42 0
42 70 112 52 206 0 0 68
HONS 2184*6
TA8tE 3.5 NYSOOH FURAN AMO DIOXIN DATA FOR THE BASELINE ANALYSES STUOY (ppb (w/w))
CoMoound
Total TCDF
Total PnCDF
Total HxCDF Total HpCDF OCDF Total TCDO OCDO 2,3,7,8 TCDO 2,3,7,8/2,3,4.8-TCDF l,2,3,7.8-/1,2.3.4.8 PnCDF 2.3,4,7,8 PnCDF 1.2,3,4,7,8-WxCDF 1.2,3.7,8.9 HxCDF 2,3,4,6,7,8-HxCDF 1.2,3,4.6,7,8 HpCDF
Aroc1 or 1016
1 7
350
92 0 0 0 0 0 0 0 0 0 0 0
Aroc lor
JI2_
1900 584
HO 130 2300
0 0 0 150 1000 0 0 0 0 0
Aroc lor 1260
940 996
5500
2430 NA 0 0 7 190 220 0 0 0 0 0
Tri and Tetra Chlorobenrene
3
13
1000 91 0 0 0 0 0 1 0 0 0 0 0
Mineral Oil Aqed
95 0
1100
0 0 42 0 43 34
140 0 0 0 0 0
HONS
TABLE 3.6 RAOIAH FURAH ANO DIOXIN DATA FOR THE BASELINE ANALYSES STUDY (ppto (w/wj)
Conoound
Aroclor 1016
Aroclor 1242
Aroclor 1260
Tri and Tetra Chlorobenzene
Mineral Oil Aqed
Total TCDF Total PnCDF Total HxCDF lotal HpCDF OCDF
Total TCDO
00
0
0 0 47 7
97 60 872
80 46 807
0 24 1786
00
0
0 0 161
170 0 0
1?5
226
1 78 36
1 ?6 o
OCDO
00
0 386
o
2,3,7,8-TCDO
00
0
0
0
2,3,7,8/2,3,4,8-TCOF
00
0
1,2,3,7,8-/1,2,3,4,8-PnCDF 0 0 477
2,3,4,7,8-PnCDF
00
0
0 0
0
125
159 66
WI
1,2,3,4,7,8-HxCDF 1,2,3,7,8,9-MxCOF
97 60 872
00
0
161
o
1 77
Q
00 2,3,4,6,7,8-HxCDF
00
0
a
ft
1,2,3,4,6,7,8-HpCDF
80 46 807
170
36
HONS 218**8
2.3,7,8 IC0F-I3C|2 1,2,3,7,8-PCOF-1zC|2 2,3,7,8-TCOO-l3C]2 ocoo-13c)2 I^.S^.F.B-HxCOF-13^ 1,2,3,4,6,7,8-HpCDF OuLtiers
TABLE 3.7
ABSOLUTE RECOVERIES OF LABELLED STANDARDS IR IHE BASELINE STUOY (UNIVERSITY OF UMEA)
Sp i ke Level Ififibl
Aroclor Aroclor Aroclor
1016
1247
1260
Chloro benzenes
Mineral Oil____
100 93 95 95
97 116
100 III 134 140
97 114
100 67 86 86 101 118
100 102 89 157
86 121
100 83 90 317 no NA
100 57 45 1224* 68 HA
HONS 218469
One effect 1$ evident In these date, the recoveries from chlorobenzene and mineral oil appear to be superior to recoveries from Aroclors. The Aroclors contain the major Interferents In the analysis of PCDF and PCOD. It appears that there may be matrix dependent difficulties in the analytical preparation of complex samples. Method Reliability The baseline data are grouped to show the relative performance of the four laboratories reported here. A compilation of data for aged mineral oil, baseline sample results Is given In Table 3.8. Method reliability Is compared by computing the Student's-t variability for four independent determinations around the mean value, the known spiked amount of standard PCOF/PCDO. In the four determinations shown the Student's-t variability of the mean varies from 20 to 167 percent. This is the degree of expected scatter in a group of four PC00/PC0F determinations conducted by Independent laboratories using the Student'st distribution to approximate variance at the 95 percent confidence level.
3-10 HONS 2L8V?0
TABLE 3.8 FOUR LABORATORY RESULTS OF ANALYSIS OF AGED MINERAL OIL (ng/g (w/w))
Compound
Total TCOF Total PnCDF Total HxCOF Total HpCOF Of OF Total TCDD 2,3,7,8-TCOO 2,3,7,8-/2,3,4,8-TCDF l,2,3,7,8-/l,2,3,4,8-PnCOF 2,3,4,7,8-PnCOF 1,2,3,4,7,8-HxCDF 1,2,3,4,6,7,6-HpCDF
Battelle
115 278 246 113 157
34 34 115 143 95 262 120
1TTRI
70 165 207 40 393 42 42 70 112 52 206 68
NYSDOH
95 0
1100 0 0
42 43 34 140
0 0 0
Radian
125 226 178
36 126
0 0 125 159 66 177 36
Group Mean
101 155 433 47 169 30 30 86 139 53 161 56
Native Spike
Level
Confidence Interval (95X1
200 109X
ISO I67X
100 20% 100 4IX
u -e
NOUS 218471
Section 4 SUPPLEMENTAL ANALYSES
CROSS CHECK ANALYSES To validate the analytical curve for each method proposed by the participating laboratories, a series of calibration runs were performed to establish the variability, linear dynamic range, and the limit of detection for each instrument. The calibration range is different from the method range. The validation of the calibration curve range only deals with standard solutions eluted through a tuned gas chromatograph or mass spectrometer (GC/HS) system. The quantities used to develop the calibration curve were 40 pg, 150 pg, 500 pg, and 2.5 ng. Each concentration level was analyzed with five replicates. The analytes used for the calibration curve validation were 2,3,7,8-TCDD, 0CD0, 2,3,7,8-TCDF, l,2,3.7,8-Pa>E. 2.3,4,7,8-PCOF, 1,2,3,4,7,8-HxCOF, 2,3,4,6,7,8-HxCDF, and 1,2,3,4,5,7,8-HpCDF.
An illustration of the type of calibration plot generated In this study Is given in Figure 1, which shows the standard curve for 2,3,7,8-TCDF,
The complete set of calibration curve plots, along with statistical parameters describing calibration precision are given in Appendix B. The standard deviation and the relative standard deviation at each point show the variability of response which increases at higher concentrations. The calibration curves were linear over the range of concentrations measured.
ANALYSES FROM THE UNIVERSITY OF UMEA Under a subcontract to Battelle, the University of Umea participated In the baseline and round robin analyses. A letter report of the data from Umea Is included as Appendix C.
4-1 MOHS 218472
Figure 4-1. Calibration curve for 2,3,7,8-tetrachlorodiberuofuran over the range 40 pg to 2.5 og HONS 218*73
Section 5 ROUND ROBIN ANALYSES OF IN-SERVICE LIQUIDS
The main thrust of this study was to evaluate a series of congeners and individual molecular species in typical in-service utility transformer and capacitor liquids. Ten (10) liquid samples, including the seven utility dielectric fluids, were analyzed for PCDD/PCDF using the methods developed In this program. All five participating laboratories contributed Independent data sets, which will be statistically analyzed by an Independent contractor, the Research Triangle Institute. The results of the Battelle analyses are given In Tabla 5.1 to 5.10.
Accuracy Estimate The in-service analyses were designed with a quality control check on accuracy of reported PCDD/PCOF concentrations. The "Baseline" liquids Included with actual utility operating fluids were spiked with known amounts of several PCDO/PEDF standards. These known spike concentrations allowed an estimate of accuracy using the mean of three determinations performed by each participating laboratory compared with the "true" or spiked concentration. The "Baseline* analyses revealed that the aged mineral oil sample and the Aroclor 1016 had minimal concentrations of the PCDD/PCDF standards present as contaminants. Thus, native PCDD/PCDF were suitable spike materials.
The Battelle results for in-service liquids are presented In Table 5.11 for the mineral oil and Aroclor 1016 samples. Table 5.11 gives the spike levels and compares the percent difference In spiked levels with measured levels of PCDD/PCDF.
The Battelle results are generally within +70 percent of the spike value except for one notable exception. HxCDF exhibited a strong positive bias. Most of the elevated HxCDF levels were 2,3,4,6,7,8-HxCDF. The HxCDF measured levels were <38 percent higher than the HxCDF spike levels in mineral oil, and 1325 percent higher in Aroclor 1016, even after subtraction of the native HxCDF found In the earlier baseline investigations. These HxCDF data are deemed to be outliers.
5-1 MQNS 218474
TABLE 5.1
CHL01UNATE0 FURAN ANO OIOXIN RESULTS {ppb (w/w), ng/g) SAMPLE ISL-02-A
^__________ Conqener
Determination Det 1 Det 2 Det 3
Mean
Standard Deviation
Relative Standard
Deviation
PCDF Congeners
Total TCDF Total P,,CDF Total HxCDF Total KpCDF OCDF
360
69 8,100 1,600 4,300
230 72
19,000 1,400 4,BOO
290
71 20,000
2,000 5,100
293 71
15,700 1,667 4,733
53 1
5,389 249 330
18X
2X 34 S 15*
7X
Total PCDF Furan Compounds
14,429 25,502 27,461 22 ,464
5,738
26*
2.3.7 ,8-/2 ,3,4 ,8-TCOF
2 ,3,4,7,8-PnC0F
l,2,3,7,B-/l,2,3,4t8-PnCDF 1.2.3.4.7 ,B-/1 ,2,3,4,7,9-HxCDF
1.2.3.6.7 ,B-HXCDF 2.3.4 ,6,7 ,0-HxCDF 1.2.3.4 ,6,7 ,B-HpCDF 1.2,3,4,7,6,9-HpCDF
190
300 69
2,700 760
1,100 180
280
Dioxin Conoeners
140
260 72
6,400 2,300 3,400
230 250
180 290
71 6,400 2,700 3,800
320 320
170
283 71
5,167 1.920 2,767
243 283
22 17
1 1,744
836 1,190
58 29
13X 6X
25 341 44:
43* 24:
10X
Total TCDD OCDO
NA NA NA NA
NA
NA
18 18 10 15
4 25*
PCDD Compounds
2,3,7,6-TCDD
NA NA NA NA
NA
NA
5-2
HONS 218475
TABLE 5.2
CHLORINATED FURAN and DIOXIN RESULTS {ppb (w/w), ng/g) SAMPLE 1SL-03-A
Convener PCDF Conoeners
Determination
Det 1 bet t Det 3
Mean
Standard Devtatio
Relative Standard Deviation
Total TCDF Total PnCDF Total HxC0F Total H,,CDF OCDF
Total PCDF
Furan Compounds
170
2.300 52,000
3,800 22,000
no
2,100 11,000
13,000 28,000
40
720 9,700 11.000 22,000
170 1,707 24 ,233 9,267 24,000
80,270 54,210 43,460 59,313
53 702 19,641 3,951 2,828
15,455
50* 411 Bit 431
12*
26*
2,3 ,7 ,8-/2 ,3,4,0-TCOF
31
2 ,3,4 ,7,8-PnCDF
130
1,2,3 ,7,8-/1,2,3,4 ,8-PnC0F
35
1.2 ,3 ,4,7 ,8-/1,2 ,3,4 ,7,9-H, CDF 29,000
1,2 ,3 ,6,7 ,8-HxCDF
6,000
2 ,3,4 ,6,7,6-HxCDF
1,2,3 ,4,6,7 ,6-HnCDF 1,2,3,4,7,8,9-HpCDF
1,800 1,100 1,200
Dioxin Conoeners
30
130 49
6,100 1,100
240 4,500 2,600
40
110 26 5,100 1,200 210 3,100 2.6DO
34
123 37
13,400 2.767 750 2,900
2,133
4 9 9 11,038 2,287 743 1,395 660
13* 8*
26*
82* 83* 991 48*
311
Total TCDO OCDD
PCDD Compounds
NA NA NA NA 18 12 NA 10
NA NA
7 75*
2 ,3,7,0-TCOD
NA NA NA NA NA NA
HONS 218476 5-3
TABLE 5.3
CHLORINATED FURAN and DIOXIN RESULTS (ppb (w/w), ng/9) SAMPLE 1SL-04-0
Conqener
Determination *1 Oetl DetT
PCDF Congeners
Total
Total Total Total OCDF
TCDF
PnCDF hxCDF NpCDF
NA NA NA
NA NA NA NA NA NA NA NA NA NA NA NA
Total PCDF
NA NA NA
Furan Compounds
2 ,3,7 .8-/2 ,3 ,4 ,8-TCDF
NA NA NA
2 .3 ,4 ,7 ,0- PpCDF
NA NA NA
1.2 ,3,7 ,8-/1,2.3,4 ,8-P,,CDF
NA NA NA
1.2.3.4.7.8- /1,2,3,4,7,9-H,,CDF NA NA NA
1.2.3.6.7.8- HXCDF
NA NA NA
2 ,3 ,4 ,6,7 ,8-HxCDF
NA NA NA
1,2,3 .4 ,6,7 ,8-HqCOF
NA NA NA
1.2 ,3 ,4 ,7 ,8,9-HpCOF
NA NA NA
Dioxin Congeners
Total TCDD OCDO
NA NA NA
NA 13
11
PCDD Compounds
2,3,7 ,8-TCDD
NA NA NA
Mean
NA NA NA NA NA NA
NA NA NA NA NA NA NA NA
NA 8
NA
Standard Oevlation
Relative Standard Deviation
NA NA? NA NA* NA NA* NA NA* NA NA*
NA NA*
NA NA*
NA NA* NA NA*
NA NA* NA NA* NA NA* NA NA* NA NA*
NA NA* 6 71*
NA NA*
HONS 218477
TA8LE 5.4
CHLORINATEO FURAN AND OIOX1N RESULTS (ppb (w/w), ng/g) SAMPLE ISL-08-A
Conqener PCDF Congeners
Determination oetl Det 2 Det 3
Mean
Relitive Standard Standard
Deviation Oevlatl
Total TCDF Total PnCDF Total HXCDF Total RpCDF OCDF
Total PCDF
Furan Compounds
62 79 1,500 1,500 4,000
7,141
64 230 1,300 2,100 4,800
8,494
99 310 990 2,700 4,900
8,999
75 206 1,263 2,100 4,567
0,211
17 96 210 490 403
784
23* 465 175 235
95
105
2,3,7,8-/2,3.4,8-TCDF
20 20 30 23
2,3,4,7,8-PnCDF
39 41 37 39
1,2,3,7 ,8-/1,2,3,4 ,8-PnCOF
22 25 34 27
1,2,3,4,7 ,0-/1,2,3,4,7,9-Hx CDF 880 740 640 753
l,2,3,6,7,e-HxCDF
54 50 36 47
2,3,4 ,6,7,8-HxCDF
47 25 43 38
112 ,3 ,4 ,6,7,8-HnCDF
350 530 750 543
1.2,3,4 ,7,0,9-HpCDF
340 450 580 457
Oloxln Congeners
5 2 5 90 8 10 164
98
201
45 195 131
175 255
305 215
Total TCDO OCDD
PCOD Compounds
NA NA NA NA NA NA NA NA
NA NA5 NA NA5
2,3,7,0-TCDD
NA NA NA NA
NA NA5
HONS 218478
5-5
TABLE 5.5
CHLORINATEO FURAN ANO DIDXIN RESULTS (pp& (w/w), ng/g) SAMPLE ISL-17-A
_____________ Congener_________ PCOF Congeners
Determi nation Dot 1 Oet 2 Det 3
Mean
Standard Deviation
Relative Standard Oevfation
Total
Total Total Total OCDF
TCDF
PnCDF H,,CDF HpCDF
K
Total PCOF
Fpran Compounds
970
11,000 14,000
3,100 150
580
6,700 36,000
2,800 170
610
6.500 16,000
4,200 220
720
8,067 22.000
3.367 180
29,220 46 ,250 27,530 34,333
177 2,076 9,933
602 29
8,455
25* 26', 45* 18* 16;
25*
2 ,3 ,7 ,B- /2,3 ,4,8-TCOF
2.3.4.7.8- PpCOF
1.2.3.7.8- /l,2,3,4,8-PnC0F
1.2.3.4.7 ,8-/1,2 ,3,4,7,9-H CDF 1.2.3.6.7.8- HxCOF
2.3.4.6.7.8- HxCDF
1,2 >3 ,4,6,7,8-HnCDF 1,2,3,4,7,8,9-HpCDF
400
2,300 870
4,700 1,800
620 920 740
Dioxin Congeners
380
2,400 900
7,200 3,200 6,800
560 860
350
1.800 780
4,100 2,300
930 1,300
990
377
2,167 850
5,333 2,433 2.783
927 863
21
262 51
1,342
579 2.832
302 102
5*
12', 6*
25T 24;
102* 33* 12*
Total TCDD OCDO
PCPD Compounds
NA NA NA NA NA 18 NA NA
NA NA* B 141*
2.3.7 ,8-TCDD
NA NA NA NA NA NA*
HONS 218479
TA8LE 5.6
CHLORINATED FURAn AND DIOXIN RESULTS (ppb (*/w), ng/g) SAMPLE ISL-23-0
Conaener
Determination Tien SeTT Det 3
PCDF Congeners
Total TCDF Total P,,CDF Total HXCDF Total HnCDF DCDF
NA NA NA
NA NA NA NA NA NA NA NA NA NA NA NA
Total PCDF
NA NA NA
Furan Compounds
2,3,7 ,0- /2,3.4,0-TCDF
NA NA NA
2 ,3 ,4 ,7 ,8-PnCDF
NA NA NA
1,2,3,7 ,0-/1,2 ,3,4,8-PnCDF
NA NA NA
1,2.3,4,7,0-/1,2,3,4,7,9-HxCDF NA NA NA
1,2,3,6,7,0^^
NA NA NA
2 ,3,4 ,6,7,0-HxCDF
NA NA NA
1,2 ,3,4 ,6,7,0-HpCDF
NA NA NA
1.2 ,3 ,4 ,7,6,9-HpCDF
NA NA NA
Dioxin Conaeners
Total TCDD OCDD
PCDD Compounds
NA NA NA 12
NA NA
2 ,3,7 ,0-TCDD
NA NA NA
Mean
Relat ive Standard Standa rd
Deviation Deviation
NA NA NA NA NA NA NA NA NA NA
NA NA
NAt NAt NAt NAt NAt
NAt
NA NA
NA NA NA NA NA NA NA NA NA NA NA NA NA NA
NAt
NAt NAt NAt NAt NAt NAt NAt
NA NA
NAt
4 6 141X
NA NA
NAt
5-7 HONS 218480
TABLE 5.7
CHLORINATED FURAN AND DIOXIN RESULTS (ppb (w/w), ng/g) SAMPLE ISL-27
Congener
Determination Det 1 Det 2 SeTT
PCDF Congeners
Total TCDF Total PnCDF Total H,,CDF Total HpCDF OCDF
580 570 350
250 270 220
140 13D 160
26 28
6
46 44 10
Total PCDF
1,042 1,042
746
Furan Compounds
2 ,3 ,7 ,8-/2,3 ,4 ,0-TCDF
300 28D 270
2,3,4,7,8-PnCDF
71 74 53
1,2,3 ,7,0-/1,2 ,3 |4 ,0-PnCDF
580 570 350
1.2 .3 .4 ,7 ,8-/1,2,3.4 ,7 ,9-HXCDF
37
16
31
1,2,3,6,7,0-HxCDF
15 15 27
2 ,3,4 ,6,7,0-H,,CDF
25 17 39
1,2,3,4.6,7,0-HpCDF
7 92
1,2,3,4 ,7,8,9-HpCDF
5 51
Dioxin Congeners
Total TCOD OCDD
NA NA NA NA NA NA
PCDD Compounds
2 ,3,7,8-TCDD
NA NA NA
Mean
Standard Deviation
Relative
Standard De v i a 11 o n
500 1D6 247 21 143 21
20 10 33 17
943 140
211 81 91
511 501
151
283 12
66 9 500 106
28 9 19 6 27 9
63 42
41
145 211 325
301 341
501 451
NA NA NA NA
NA! NA1
NA NA
NAt
HONS 218481
TABLE 5.8
CHLORINATEO FURAN AND DIOXIN RESULTS (ppb (w/w). ng/g) SAMPLE EZ29-53-01 (Spiked Mineral Oil)
Congener
Determination Det 1 Det 2 Det 3
Mean
Standard Deviation
Relative Standa rd Deviation
PCDF Congeners
Total TCDF Total PnCDF Total H,,CDF Total HnCDF OCDF
220 160 310 550 680 6,600 530 33
NA NA
190 190
260 373 390 2,557 220 261
31
24
127
2.862 205 1
131
341 1121
79* 1411
*w-- CD
CJ
Total PCDF
1,740 7,343 1,063 3,382
831
Furan Compounds
2 ,3,7 ,0-/2 ,3 .4 ,8*TCDF
2,3.4,7,8-PnCDF 1,2,3,7,8-/1,2,3,4 ,0-PnCDF
1,2 ,3 ,4,7 ,8-/1,2 ,3 ,4,7,9-H,,C0F 1,2,3 ,6,7 ,8-HxCDF 2,3,4 ,6,7,B-HnCDF 1,2,3,4 ,6,7 ,8-HpCDF 1,2 ,3,4,7 ,8 ,9-HpCDF
220 160 170 370
140 170
310 550 14D 120 200 5,900 53D 33
NA NA
190 190
120 220 14D 150
260 373 76 112
140 2,000 220 261
NA NA
24
108 14
127 27
2,701 205 NA
131
491 91
341 241 1301
791 NA1
Dioxin Congeners
Total TCDD OCDD
19 19 23 20
NA NA
1 NA
2 91 NA 1411
PCOD Compounds 2 ,3,7,8-TCDD
19 19 23 20
2 91
5-9 MONS 218482
TABLE 5.9
CHLORINATED FURAN AND DIOXIN RESULTS (ppb (w/w), ng/g) SAMPLE E729-53-D2 (Spiked Aroclor 1D16)
Congener
Determination Set 1 "Oet'l Det 3
Mean
Relative Standard Standard Deviation Deviat1
PtlDF Congeners
Total TCDF Total PnC0F Total HKCDF Total H-CDF OCDF K
Total PCDF
57 600 5,400
65 110
6.232
67 500 2,300 150 120
3,137
66 460 780 340 120
1,766
63 52D 2,827 185 117
3,712
4 59 1,923 115
5
1,868
75 11! 6 St 62:
4
505
Furan Compounds
2 ,3,7 ,8-/2,3,4 ,8-TCDF
57
2 ,3,4 ,7,8-PpCDF
410
1,2 ,3 ,7,8-/l ,2 ,3,4 ,8-PnC0F
180
1,2 ,3,4,7,8-/1,2,3 ,4 ,7 ,9-HxCDF NA
1.2.3.6.7.8- HXC0F
100
2 ,3,4 ,6,7,8-HxCDF
5,200
1.2.3.4.6.7.8- HpCDF
65
1,2 ,3,4 ,7 ,8,9-HpCDF
NA
67
310 180
NA 84 2,100 150 NA
66 63
260 327 190 183
NA NA 81 88 680 2,660 180 132 NA NA
4
62 5
NA 8
1,887 49 NA
75
195 35
NA5 95
775 375 NA5
Dioxin Congeners
Total TCDO OCDO
46 46 44 45
1 25
NA NA NA NA
NA NA*,
PCDD Compounds
2.3.7.8-
TCDD
46 46 45 46
NA
15
5-10
HONS 218483
TABLE 5.10
CHLORINATED FURAN AND DIOXIN RESULTS (ppb {*/), ng/g) SAMPLE EZ29-53-03 (Spiked Arodor 1260)
Congener PCDF Conoeners
Determination Det 1 CfTT bet 3
Mean
Standard Standai Deviation Dev la11
Total TCDF Total PnC0F Total H^CDF Total HpCDF OCDF
Total PCDF
Furan Compounds
1,400
1,100 20,000
1.7D0 5,000
1,700
1,300 4,700 3.0D0 4,900
970
1,200 11,000
660 2,600
1,357
1,200 11,900
1,787 4,167
29,200 15,600 16,430 20,410
300 82
6,279 957
I.1D9
6,225
22* 7*
53* 54* 27*
30*
2,3,?,8-/2,3.4(8-TCDF
1,200
2 ,3 ,4,7,8-PnCDF
590
1.2,3,7,8-/1,2,3,4 ,8-PnCDF
1,400
1,2 ,3,4,7 ,8-/1,2 ,3,4,7 ,9-HxCDF 1,900
1,2 ,3 ,6,7 ,8-MxCDF
1,200
2,3 ,4.6,7 ,8-H*C0F
10,000
1,2 ,3 ,4,6,7,6-HnCOF
55
1,2 ,3,4,7 ,8,9-HpCDF
30D
Dioxin Conoeners
1,300
410 1.170 1,8D0
93 770 850 360
880
800 97D 1,600 780 6,500
49
180
1,127 627
1.357 1,767
691 5,757
318 280
179 194 300 125 456 3,805 376 75
16* 31t 221
7t
66* 118*
27*
Total TCDO OCDD
PCDO Compounds
110 IDO 80 97
NA 12 NA
4
12 13* 6 141*
2.3,7,8-TCOD
110 100 80 97 12 13*
MONS 218484
TABLE 5.11 ACCURACY DETERMINATION USING SPIKED BASELINE LiqUIO ANALYSES
Tele! tCOf foul PnCDF lout H.cor
Tot-1 lIpCDf ocor
Minerel Oil F779-53-0I
Spike MOVAt PerteotTTT
Level
Found
Difference
700 ISO 100 373 475 7557
TOO 761 0
-5 74 438
-15
Aroclor 106 C779-53-07
Spike fepfint
Percent
teel
Found
Ol f fereiKe
53 61 316 570
185 7877
576 185 137 117
19 65 1478
Corrected!*; Aroclor 1016
f779-51-07
61 515 7637 too 117
four pcof
1375
3387
146
1717
3717
706
343?
ToUl TCOO OCOO
7 ,3.7,8-TCDD
7,3,7,6-/7.1,4,8-TCOF
75 7 00
75 2
700 ISO
-9?
-97 -5
53 45 00
53 46
53 61
-15
-13 19
45 D
46
63
1,?.3,J,8-/I ,7 ,3.4,8-PnCOF
150
150
0 158 183
16
181
7,1,4,7,8-PnCDF
150 ?.'D
47 158 377
107
377
1,7,3,4.7.8-/ l.*.i.4,7,9-HC0F
1,7,3,6,7,8-lljcCDf ?,3,4.6.7,8-fuCI)r 1,7,1,4 ,6,7,8-HpCOf
1 ,7,3,4,7,8,9-HpCOf
750 37) 50 0 175 7080 400 761 -- 0
49 -100 1089 -35
00 53 88 137 7660 576 13? -- 0
66 1915 -75
-
-190 88
7660 13? -n
(1) Percent Difference = IOO (Heisured Vtlue - True Spike)/True Spike
(7) Corrected t>,
the Arcelor 1016 -fl^eMne* PCDO/PCOF toncentr.tion* fro- the .eisored *,luet.
Percpnt 0<fference
19 61 1375 -81 -11 183 IS
13 19 16 107
66 1915 -75
zrs
HONS 218489
Comparison with Parallel An^YifS The Battelle results are compared with the results reported by the other four laboratories participating In this program In Table 5.12. The data presented In this table for the other laboratories are taken from a draft statistical report (2) presented by Edo Pelllzari {Research Triangle Institute. Research Triangle Park. N.C.) at a meeting of the five participating laboratories held In Washington, D.C. on November 19, 19B6. The Battelle results averaged over three replicate determinations are presented in Table 5.12 where the average reported values by the five collaborating laboratories conducting parallel analyses are also given. The two sets of data compare favorably; except for hexachlorinated furans, the Battelle results are consistently lower overall thin the data contributed by other laboratories. The general trends in the data such as very low values for PCOD/PCOF in mineral oil samples was apparent In all the reported data. The 30-year-old network transformer containing Askarel (Sample Number 3 in Table 5.12) had the highest reported PCDF level of all the In-service samples tested, approximately 32 ppm (w/w) using the average of all reported determinations.
HONS 21&466
5-13
i wvt
5-14
Section 6
DISCUSSION
This study produced a great amount of Insight into the variability of analytical methods applied to trace analysis in a complex dielectric fluid matrix. PCB constitute the principal class of tnterferents for modern mass spectrometnc methods when used to analyze polychlorinated aromatic species such PCDF and PCDO. Several conclusions can be drawn concerning performance of the methodology and the accurate screening of In-service dielectric fluids.
METHODS
The analytical procedures proved to be both rugged and reliable when used with labelled quantification and recovery standards. The quantification standards are used to calculate errors from extraction and sorbent partitioning losses. This is especially Important In the Askarel and mineral oil matrix since the high organic burden found with this matrix requires secondary partitioning to remove interfering PCB and the background hydrocarbons from mineral oil.
Random outliers were observed in this study. Dne example was the elevated levels of hexachlorodtbenzofuran found in the in-service analyses. This kind of acute error can arise from a mistake In the gravimetric preparation and dilution of the labelled recovery standard. Another possible cause for this random error is selective partitioning losses during sample clean up. Observing this type of spurious result Indicates that the awthods should be used with enough quality control checks to "flag" this type of error during the analysis. Using a second labeled internal standard to quantify the mass recovery of the quantification standards would identify this problem if It is related to quantification standard losses.
The observed data variability in this program was smaller than the participants had anticipated before the program began. In this very difficult matrix, a chlorinated oil, most analysts would predict a variability of one to two orders of magnitude (lOx to lDOx scatter around the true value). In most cases, the relative standard dsvia-tlons were found to be less than 100 percent. The relative average deviation is the absolute difference between individual results and the mean (or true value),
divided by the number of determinations. For samples such as the Aroclor izaz,
6-1
MONS 218488
Aroclor 1016. and mineral oil, the average deviation was most often less than 50 percent. This result was seen in individual laboratory replicate analyses and in grouped data from different laboratories.
in-service liquid analyses
The in-service liquids tested in this program were found to have relatively low amounts of PCDD In all samples tested. This result supports the hypothesis held by many chemists who have Investigated Askarel and PCB-contalnlng fluids that dioxins are not a major constituent of these mixtures. Except for the mineral oils, polychlorinated dibenzofurans, however, were found in trace amounts in all of the samples tested. The mineral oil samples were found to have extremely low amounts of PCDD/PCDF if any were found at all. Even the In-service liquid from Transformer 4, a network distribution transformer that was involved in a high energy excursion, was found to have minimal amounts of PCDD and PCDF. Transformer 4 had visible carbon, and major signs of scorching on the case and the area of the electrodes.
The Askarel transformers with more than 25 years of service tended to have higher levels of PCDF than the appliances put into service for a shorter time. It is possible that manufacturing controls improved as the production of Askarel matured in the 1960s such that Askarel was produced with lower levels of PCDF in the asdelivered fluids. It would be Interesting to obtain replacement Askarel with a known lot number which matched a sample with extended service life. Analyzing samples of an unused Askarel and comparing the PCDF levels in a sample subjected to heavy load and environmental stress for an extended period would challenge the theory that utility operation contributed to elevated PCDF levels in Askarel fluids used In transformer and capacitor applications.
Two utility appliances were selected by the EPRI Technical Advisory Committee for special attention. An Askarel-fllled electrostatic precipitator (ESP) transformer, and an oil-filled arc furnace transformer. Both of these applications involve extended thermal and electrical excursions during dally operation. These two samples were the "worst case" for testing service stress on the dielectric fluids. The arc furnace had essentially no PCDF or PCDD, and the PCDF levels In the ESP transformer appeared to be dictated by the age of the unit (27 years of service) and the fluid composition (Aroclor 1260). This extended period of stress did not appear to elevate the PCDF levels above typical Aroclor 1260 contamination levels.
One capacitor was tested In the in-service liquid screening program. It was found to have relatively low levels of PCDF compared to the other Askarel-fllled units.
6-2
MONS 21*489
The observed distribution of PCDF seemed to follow a trend of higher concentrations of PCDF arising with the highest degree of chlorination Aroclor. The Aroclor 1260 with 60 percent chlorine by weight tended to have higher levels of PCDF in every comparable sample than Aroclor 1242, or Aroclor 1016, both of which have approximately 42 percent chlorine In the base Aroclor.
A second effect was observed in these data, the relative concentret Ions of PCDF
congeners In any sample tends to favor the analogs with higher chlorination as the
chlorination number of the underlying Aroclor increases.
For Instance the
proportion of hexa, hepta, and octachlorodibenzofurans are higher in Aroclor 1260
than Aroclor 1242. If PCDF are formed by direct internal condensation with the
addition of oxygen, HC1 elimination can occur. This reaction would preferentially
produce higher levels of chlorination in the product PCDF when high degrees of
chlorination occur in the reactant PCB.
SUMMARY
This study was successful in developing a set of methodologies that reliably determine trace levels of PCDF and PCDO In a very difficult matrix -- chlorinated organic oil. The development of commercially available reference standards and the statistical validation of reference methods that can be used to analyze utility fluid was a major contribution to the quality and defenslbllity of data in this field. The method verification program showed that a range of instrumentation can be successfully used to measure trace levels of PCDF and PCOD in utility fluids. In general, the methods employing low resolution mass spectrometry require additional column chromatography to isolate PCDF/PCDD-enriched fraction for final gas chromatography. The precision of blind spiked samples was superior to the variance expected by experienced analysts who had previously performed this analysis. The availability of labelled quantification standards helped improve method performance and lower data scatter.
Although the in-service liquids tested in this program were a very limited set, there were interesting findings about the type and distribution of polychlorinated dioxin and furan species in the systems tested. Dioxin levels were very low, or not measurable In the liquids analyzed. The mlneral-oil-filled equipment had levels that were found only at the quantification limits of the methods employed. Aroclor 1260 appears to have higher levels of PCDF with enrichment of the higher chlorine-number analogs, when compared to Aroclor 1242, 1016, or Aroclors with fewer chlorine atoms per molecule than 1260. This data base can not support the
HONS 21*490
premise that the age of Askarel transformers tends to favor higher PCQF levels in older transformers since only four units were investigated.
HONS 21*491
Appendix A IN-SERVICE LIQUID QUESTIONNAIRE
MONS 218492
Respondent:
GENERAL INFORMATION QUESTIONNAIRE EPR1 IN SERVICE LIQUIDS STUDY (RP 2028)
Samples provided
As La re I Load Center/Network Transformers Rectifier Transformer Precipitator Transformer Capacitor
Oil Filled load Center/Network Transformer
Number Shipped `
_________________ _________________ _________________ _________________
_________________
MOMS 218493
CATA SHEET FOR EACH SAMPLE
E PR I IN SERVICE LIQUIDS STUDY (RP 2028)
General information
Voltage Rating: Liquid Volume: Manufacturer and fear:
____________________ ____________________ ____________________
PC3/A$karel Manufacturer: (if available)
PCS/Askarel Type:
PC3 Levels: (for oil filled. If known)
Additional Equipment Identification: (name plate data)
Equipment Maintenance History Length of Actual Service: Major Maintenance:
Recorded Failure in Service:
A-2
HONS 21S494
DATA SHEET FDR EACH SAMPLE Was Fluid Changed at Failure: Any Record of Temperature Excursions: Are Maintenance Records Available: Any Other Pertinent Information About This Unit or the Sample Liquid:
MONS 21*495
A-3
Appendix B ANALYTICAL CURVE DATA FOR THE CROSS CHECK ANALYSES
MONS 218496
{Ml, CimilTl jrs UI{. 1,7
k-volvci T*V4CUCi
3< ffff 1*4 wo *f mo 144 *000
0 079* 0. 33*9 1. (47* 9 MOO
*-v*cwt
9-W*tW*
0 0009 0 3949 1. 1*09 9 94*0
979 OCV
0 07** 0 330* 1 1*07 9 7019
7191
0 0010 0 3*30 1 1371 4 0*90
7|| C
0 00*9 0 9*41 1 193* * *939
**
5i
>t
Mt* MIT* HCOMCT TO THl
1*910*900000 0000000000001000
0091 03*1031499f*t713*
0000 0004000|91*19997
11*a1 Of70t10*f
Mt7 UITM ftffftCCT TO TH MMllOh IINC
3091009000* 0000000000001000
0091 0491114399**1734
0000 00*010417919199*
911313 O30*9*fft
* DLOPf or 0 99*I* IIVII IN INTcacCAT or 9 03911 K or <u nH iiutt m tNTtacccT or - nm m DATA NAD a cmadlatidn cocfticicnt or o **m
0000 00041901010490** 0000 00409*17911|7149
0000 00090014910490**
000
0
0003144114913
B-l
HONS 21*497
!*r. :c#9i;? IT9 tVlvE, 1 .J.J
l'V4Cbf| v-v6cufi
60 0000 IM. 0000 l 09*0 JW ffOO
0 0*0* 0 &4V 1 310 * 3000
1-V4LUI
VV41C
0 10*1 0 9933 1 3171 9310
TO OfV
0 0*| 0 9349 1 3301 9 *900
in
0 0*3* 0 3931 1 1*49 9 9090 II C
0 0*36 0 3*09 1 1**9 9 9*00
*
OATA MftW OCMCCT *0 * V-VJN.UM
40 0000
190.0000 >00 0000 3*00 0000
0 0009
0 9441 1 1939 9 9383
0 07*4 0 0119 0 03*9 0 41 At
49 1*
9 33 9 99 7 19
0 0494
0 0103 0 0430 0 4909
OaTA 1Th fttPVCT
40 0000 190 0000 too 0000 3900 0000
0 0009 0 9441 1 IMS 9 9333
0 0419
0 0139 0 0*4* 0 1A9
91 >1 9 94
9 74 7 19
0 Ot* 0 Of *4 0 0709
0 4904
* HVI 0*
0 00393 Mft * (NT36CM* OP
A 9L0M op 49* 03*00 OlvO AN iNtmiet op
th* w'< *t cm*cl*tion cot^iciin' v
-Q 0019* 0 47917
0 0937 0 00*9 0 033* 0 99*4
0 0999 0 0109 0 0390 0 lilt
8-2
HONS 216498
ei. cgwesiH so ;um. *.j,
I-VM,Ut*
*0 944IM9999
099M099O090O000
9I-V UA
T-VM.UM
001
T
0947M3|90413*7
v-vkM
0 0743
017
99* 9II4H00
tTD Mv
Q071
07|4 0449f4t47t093
MOl
0001 031(*03399030143 4(9 1
0091 93313991941(0414 44
0 7 4 99* * WITH flCSMCT to t** v*V iU
*0
IM
9MO MO.
0000900000000000
0041 049M707003930
0401 00110909410*4904
11110497 03034334
0 9 70QAt* UlTK CI CCT
Tv* ftCMCMlOH Lit*
40
IM
9MO MO.
0000000000000000
001
*
0499704006479303
0001 090109939494044*
411417
IT
49319439
41 0 043*0 4 4 1 9 V* art OF
IVC ** n? BCKpt
9407 394 30900 41 9 **** ff OF
v INTCUCICT OF
0TH| OAT* H*t * CMML*UOn CO*"ICUNf OP
>49 0004493043
*****
000
l
O90>709l 9M71734
0001 090>049400971109
0000 0071034390779390 0000 0O713*99t7*l94?l
B-3 HONS 216499
{>;. :y+w:mi s^com. i.i.j.
K-VALWC9
V-VAL.JCI
0 0900 tH 0000 **f woo
1W 4400
0 0*03 0 3134 I 179* 9 4339
v-vauA
0 0777 o aioi 1 0739 9 77*9
970 Otv
0 0700 0 3073 l 9033 9 4700
*901
0 004* 4 *1*0 1 0947 * 40*0
4(9 K
0 0733 0 3 70# 1 0341 4 3130
*4
ktA wlTM MI7KCT to TMf
*0 0900 190 0094
900 0000 9900- 0000
0 0744 0 3*9* 1 11*9 9 *07
0 00*9 4 04T
0 0474
0 4441
hTA tfITM MI7ICT TO TMt te*(9fiON linc
0 3* |3 0*
4 09 10 19
0 0103 4 0707 0 I04 1 9790
*0 0000 190 0000 900 0000
9900 0000
0 07A4 0 3*99 1 1149
9 *973
0 0144 0 0499 0 0400 0 4441
39 4* 13 30
4 17 19 19
4 9L0Pf OP
0 00114 Olvfi *N in73*C(47 or
o 00947
* *.0P(
9* 4*00 0[v9 a* iMT|eicr OP -3 944*9
0*T* MAI * COfl*KL*r I on CSr^PlCUNT QT 0 44444
0 0314 0 0730 0 1000 1 9790
0 0490 0 4*03 0 0*04 0 0474
0 01 74 0 04 10 0 0*30 0 947*
B-4
HONS 218500
cocDffltanm
tm. cot*;n irs euwi.
l-VALUf*
V-VAlUC*
*0 0000
IW 0000 w *#*o im **o*
o om 0 1*3* l BOO* 9 !
l-VACUt
0 0*3? 0 9700 1 0**t >*70
OTO 0*V
0 0*73 o m 0 t?3 311*
*00*
0 0710 0 37*3 1 0394 4 33*0
KO 1
0 071* 0 5*0* 1 0**9 7 3*00
*R
OAT* tf|TM ftCOFCCT TO TV* V-VALUt*
*0 0000
IM 0000 too 0000 3*00. 0000
0 0**7
0 304* 1 4M3 9 ***7
0 00*9
0 0409 0 0+1*
1 0049
4 4*
13 l* 4 09
14 4*
DATA WITH iCOFICT TO Tm| ftAiMlQN ulMC
40 0000 1*0 0000 too 0000
9*00 0000
0 0**7 0 304*
1 09*3 ***7
0 094* 0 049* 0 0*9* 1 0049
30 19 14 0*
*. 09 |4 **
UPK OF O Mil) I1W9 AM INTIRCtfr OF
-0 04***
* VW OF *43 *9000 *IV| *M iHTCUCtCT OF tO 749*0
THI DATA n*0 * eQft*Cl*TlQN CMFfiClfNT OF * 44*43
0 00*9 0 0**4 0 0949 i *403
0 03*0 0 0*0* 0 0004 1 *404
0 0093 0 033* 0 0334 0 74*
0 0300 0 03*7 0 0M 0 *74*
B-S HONS 218501
imj* vo*os::e tra cuave.
I'VAUdCI
T-VA^Utl
40 0000
190 0000 444 4440
att 4*00
0 9473
1 3*74 9 9074
93 90*0
0 |0T
1 1999 4 9144 99 >74*
to orv
0 9499
1 *194 9 4309
94 0t4>
0 9904 0 9439 * 0030 99 0900
0 9049 I 1430 9 7310 >1 TOO
RC
OAT4 uJTh MOPICT 70 n rvcWC9
0 HM 190 0000 900 0000 900 0000
0 9914
91 1497 4437 91 4099
0 09*0 0 vtl* 0 0479
9 7449
19 *4 1> 91 91 *4 17 04
AT* KITH ACOPICT TO TmI C9M99ION LlMf
n4o0 0oo0o00o
900 0000 9900 0000
0 >914 1 143* 3 4437 >1 4019
9 1399
0 9041
0 04|> 3 749
93 00 17 97
99 40 17 04
A kVI 0*
0 00003 0IVC9 AM |NttCI^ OP -0 39194
A IkDPI OP l|3 90400 4lvC9 am [nT(|cK(T op f> 0*110
TM OATA MA9 A CQMCLATIQN COCPPlCltNT OP 0 44499
0 0037 0 9971 1 304 4900
O 914) 0 3399 1 *04# 9 4909
0 0074 0 0491 0 1449 0 9474
0 0314 0 047# 0 0044 0 04'7
B-6 MONS 218502
CMomteTioi
(Ml. COf^OSlfE SfC CUWI. 2,J,M.r<r|CW
*-v**u0 vvAtUt#
*0 0000 1H OOOO Iff 0900
IMf *000
o o*oa
0 9*00
40 a*7m03
o mo
0 9999
0 m*93i*
l-v*tgc
WALUt
|Ti OCV
0 0*1**
o C70a
0 0117 * 7|ff
Wt
oe 0r7u*a
0 i*7* 4 0000
HI (
0 0*77 0 ttl 7
0 *#11
*. 10*0
*t
0*7* with in^tcT ro nm. r>v*cutt
*0 0000
IK 0000 KO 0000
#000.0000
0 00*3
0 #7*0
o tan
4 *0*0
0 OOOO
0 00*1
o a#7#
0 *0*0
#7 1. 1*
a *t 1# to
0*T* WETH OCBOCCT 70 TX KOMMIQN L1X
40 0000
IK 0000 KO 0000 9*00 0000
0 0003
0 (**0
0 *10#
4 ***0
0 0#33 0 0l#O
0 0**3 0 00*7
39 10
0#
9 30
1# #0
* K0*t 0# o 001** 1141 ** IN7CRCCP7 OR
-o 03800
* *.[*1 OR 000 33*00 ilvto AH InTfnCCCt OR 17 01410
tm. 0*7* MAS * e0O*CL*7|0H C0CR*teilM7 or o ****a
0 0104 0 00*4 0 043*
0 *9*1
0 0900 0 090# 0 077*
0 *9*9
0 00*7 0 00*9 0 090# 0 014*
0 093* 0 0130 0 04** 0 AIM
B-7 HONS 218503
tm, carWSITT STB QWE. ocoo
1 COPPOOltO TO CUOVI. OCH
fWAbVtO
0 0000
40if4o**
oooo
****0*0
T-VM.UO*
09
I to.
009043**1**4000*
vvuA
095
U
0913400140*1C07
TS OCV
13030
1000 0}14*0*l90i
tni
030
*
*4109?*04300330
*10
00
a *
1111990300021090
*0
i|wril~*TfT|| Tl I ~ ~f 1------ ~------T------Til ! f f> ji > i
r**Kt* turn ftcppfCT re
40 0000
190 0000
300 too
0*000000
0 194* 0 1940
not 10 014|
0 0940
0 0*13
0 1
02090*41
t! 44
13 99 10 90 1> 30
0 0439 0 1 It* 0 9433 3 *990
O*T0 WITH icopcct TO * eHMION LlMt
40 oooo
IK 0000
900 0000 (900. oooo
0 194*
0 9944 t 1309 10 *IM
0 09*4 0 07*4
10 01*3 9004
3l 94
1013 *4
10 17 M
0 0433 0 1214 0 3433
3 *091
0(7* OP
A OCOP* OP
0 0040* OlvCO AM IfcfcacfPT op **100 Ojvtt AM iNTUCtCf QP
-0 0**99 i* 4*3*0
Tp Cat* mao a COPftllAfJON COfPPlClCNT OP 0 tW*
0 0134 0 033*
0 00 1997
0 **
0 0
0013191*
0 101*
0 704
POMS 210504
8-8
Append!* C LETTER REPORT FROM UMEA
MOWS 216505
UmeA Universitet 901 87 UmeA
86-06-2 3
Mialys results EPRl-pro jekt 2028
Formation of PCDD and PCDF in askarel and contaminated mineral oil equipment.
Contents.
Normalized raw counts for regression lines.
Levels in baseline liqids
Levels in
inservice
liqids; TCDF/TCDDs PnCDF/pnCDDs and HxCDF/HxCDDs HpCDF/HpCDDs and OCDF/OCDDs
GC/MS Conditions.
Clean-up
By Lars-Owe Kjeller UmeA Universitet 901 87 umeA Sweden.
C-l HONS 216506
LARS-OWE KJELLER UmeA Univeraitet 901 87 UMEA Sweden
UmeA 85*06-18 EPRX-prodjekt 2028
Calibration curve, raw counts normalized for ^C-internalstandard,
Concentration injected pg 2.3.7.8- TCDP 2.3.7.8- TCDD 1.2.3.7.8- PnCDP 2.3.4.7. B-PnCDF 1.2.3.4.7. B-HxCDF 2.3.4.6.78-HsCDP 1.2.3.4.6.7.8- BpCDP OCDP
10 9.5 3.4 6.0 4.9 3.9 1.7 1.4
ND
10 12.4
7.9 9.5 8.5 7.8 4.6 3.9 ND
10 10.8
7.0 8.1 7.5 7.3 4.5 3.8 ND
Concentration injected pg 2.3.7.8- TCDP 2.3.7.8- TCDD 1.2.3.7.8- PnCDP 2.3.4.7.8- PnCDP 1.2.3.4.7,B-HxCDP 2.3.4.6.7.8- BxCDP 1.2.3.4.6.7.8- BpCDP OCOP
40 38.5 18.0 24.8 17.8
8.8 5.8 0.9
I-- * y--
40 42.3 27.6 35.0 29.0 27.3 18.2 13.0
2.0
40 42.6 27.8 37.8 29.0 27.3 18.2 13.0
1.5
HONS 218507
Concentration injected pg 2.3.7,8-TCDF 2.3.7.8-TCDD 1.2.3.7.8-PnCDP 2.3.4.7.8-PnCDP 1.2.3.4.7.8-B*CDF 2,3.4.6.7.8-BxCDP 1.2.3.4.8.7.8-BpCDF OCDP
150 160.9 100.1 133.4 100.7 105 . 3
51.7 39.3
5.6
150 155.1
94.2 124.5
98.2 82.2 43.1 33.7
2.1
150 160.1 105.7 137.9 118.1 103.3
68.9 53.4
6.7
Concentration injected pg 2.3.7.8-TCDP 2.3 .7.8-TCDD 1.2.3.7.8-PnCDF 2.3.4.7.8-PnCDF 1.2.3.4.7.8-BxCDF 2.3.4.6.7. 8-BxCDP 1.2.3.4.6.7.8-BpCDF OCDP
500 545.3 370.9 470.0 403.5 339.8 214.3 182.4
23.5
500 570.0 371.0 471.0 401.0 338.0 203.0 177.0
17.0
500 550.9 359.9 467.7 402.1 341.9 216.2 181.9
17.4
Concentration injected pg 2,3.7.8-TCDF 2.3.7.8-TCDD 1.2.3.7.8-PnCDP 2.3.4.7.8-PnCDP 1 2.3.4.7.8-HxCDF 2.3.4.6.7.8-BxCDF 1.2.3.4.6.7.8-BpCDF OCDF
2500 2791.7 1925.0 2412.8 2012.5 1780.1 1118.9
973.4 166.4
2500 2769.4 1806.1 2384.7 1979.0 1760.3 1145.8
889.8 125.8
CO
2500 2767.9 1924.3 2413.1 2061.7 1793.3 1100.5
952.1 169.1
HONS 218508
Concentration injected pg 2.3.7.8-TCDP 2.3.7,8-TCDD 1.2.3.7.8-PnCDP 2.3.4.7.8-PnCDP 1.2.3.8.7.8-BxCDP 2 3.4.6.7.8-BxCDF 1.2.3.4.6.7.8-HpCDF OCDF
7500 8731.9 5966.9 7401.8 6219.0 5565.6 3532.6 3067.2
513.6
7500 8593.7 5480.0 7264.2 5897.8 5502.2 3577 .6 2790.8
419.3
7500 9037.3 5735.6 6989.2 5980.2 5494.7 3638.1 2768.4
433.1
Characterization for the regression line y a*x + b
y amont of Dioxin/furans. x normalized counts.
2.3.7.8-TCDF 2.3.7.8-TCDD 1.2.3.7.8-PnCDP 2.3.4.7.8-PnCDF 1.2.3.4.7.8-BxCDP 2.3.4.6.7.8-BxCDF 1.2.3.4.6.7.8-HpCDF OCDP1
a 0.853 1.306 1.037 1.240 1.357 0.487 2.595 0.061
b 29.89 18 .28
9.24 6.76 24.50 -21.26 31.83 -4.44
Residual standard deviation 135.7 117.5
77.5 76.1 38.0 34 .1 159.6 22.6
1 10 pg cone, not included.
C-4 MOMS 218509
MONS 2 1 0 5 1 0
eeoeeeeeeeeo<
>'VV V V VoVVvoVvVv*
I V M MB V '
leefi
' V V * <*
V V V V V ' i' Qm m*
I V P* V V
*1 "e *
b0 I
< V f V V
s
fc
i
C ?!
01 K p* #. f. : Cft *yr f* rt
| A -- n ^ mm mm mm *m <-*#**%- P* rw -- -- M fH P* N ^ -, F *
I
C-5
ft m
b o* O * B
V y* tH
V pi
at
*
e e B
-o B e B -* V VV VVV V V VVV V VV V X
mm m mm e O O O oo
* * v 9 v 9 v ft s O B O
,
/>
a * B 9 e
V e V
om V V O e
IN
IN
m # iv
IN pp pp
* O Bo
o
m e
o
ft*
ii
2
TwU
1" IN o
m pi a
VV
IN V
V IN
0i pi
IN
m V IN i
--0* K K ft*- ft.
AA
-- "
:
0*
*fioae <N V V V
V
-"
m ft*
*
- --
-
-
- ---- -
-9
v e* v v in
fOvvvyv^*v B9 ^
^On^M|neA|iriN*r rto^ *i
in
bb*o*bb'b*ob*o**-**-* ^ oVeVvoveVav*v9vv9V9NtVttVtf*l a
* wp*.*
aee0aB
VVVVVVVVVVVVI
*
f*
oOOoOop-ift<^
ieof
-- B -vO^>MOer*iV>'er*i^oo r
sH
#0r<
1
v*wwwvwVN^ipwpr%ftvrtw|(
^ * 2 2 ^,N 2 pi " J5 P
{J
S
W* t-*ft
No HiClMJ is o a tfD d e le c t c<f * D o lt c t t o n l i i t 0 .2 rq/<j
in ## N
(A
A tt o r. 4 !l^ 9 -||
C-6
ttpCDF*
123467* 1234(74 1234(84 12347(4 TOT BpCDF BpCOO
OCOP
1234(784
ocot>
1234(784 ABC l5C-OCW>
150 1000
U 40
150 1000 80 4(0
400 2500
1.7 <0,07
L .2 0,27
3.2
880 170 4 10 470
2100
<0.04
<0.06 <0.06
<0.06 NO
<0.07
<0,07
<0.07 <0.07 Nt>
HO HpCDD isomer* dttMt.d- D.l.ction lilt 0,5 ng/g
22 1.8
15 3.8
43
10000* 100QQ
<10 7.7 HD 45%
5.4 100
0.3
o- 54D0
<0.73 411
<4.7 (4%
<1.1 *lt
I.S !
<5.2 1D0I
1 All quentificationt irt **de with the 12C-copundi in AA91AH calibration standard* i*t 2 Corectlen for recovery la Hdi.
2 Coreetion for recovery ad* with l3C-l 23478 *H*Ct>P api<e.
4 The valu** er not corected for recovery.
HONS 210512
C-7
High Resolution Gas Chromatography and
Maas Spectrometry"Conditions
'
Column
SUPELCO SP-2330,
Length Diameter Film Thickness
fused Silica 60 m
0.25 mm 0.20 um
GC-Conditions
BP 5890 with Belium as carrier gas
Column pressure
40 psi
Temperatur program: 100C for 2 min splittless,
to 180C with 206C/min,
to 250C with 3C/min,
hold at 250C for 30 min.
Injections volym
1-3 ul
MS-Conditlons
instrument! VG 12-250 Low Resolution Quadrupole in El mode
Electrone Energi
37 eV
Source Potential
9V
Repeller Voltage
9V
Amplifier Gain
Low sens SIR
Multiplier voltage
2000
V
Tuning Calibrant
PFK
Source Temp.
200 C
Transfer Line Temp.
250 C
C-8
HONS 218513
Clean-up technique for the determination of PCDF in aalcarel and rniniral oil
C-9 HONS 218514
LARS-OWE KJELLER UmeA Universitet 901 87 UMEA Sweden
UmeA 86-06-18 EPRI-prodject 2028
Levels of dioxins and dibensofurans In baseline liquids
Att nr. E729-53-
2.3.7.8-TCDF 2,3,4,8-TCDF Tot. TCDF's
REC 13C-2378-TCDF
2.3.7.8-TCDD Tot. TCDD'S
REC 13C-2378-TCDD
1.2.3.4.8-/ 1.2.3.7.8-PnCDF 2.3.4.7.8-PnCDF Tot. PnCDF'a
REC l3C-12378-PnCDF
1.2.3.7.8-PnCDD Tot. PnCDD'a
1.2.3.4.7.9-/ 1.2.3.4.7.8--HxCDF 1.2.3.6 .7 .8--HxCDF 1.2.3.7.8.9--HxCDF 2.3.4.6.7.8--HxCDF Tot. BxCDF'a
REC I3C-123478-HxCDF
1.2.3.4.7.8--HxCDO 1.2.3.6.7.8-HxCDD 1.2.3.7*8.9--BxCDD Tot. BxCDD'a
1,2,3,4,6,7,8-HpCDF Tot. RpCDF'a
Tot. BpCDD'a
OCDF
OCDD
REC 13C-OCDD
01
89 100 190
60%
14 14
67%
160 160 320
59%
<1.5 ND
290 31 <2.1
170 490
59%
<2.7 <2.7 <2.7 ND
450 450
ND
VD2
ND2
ND2
C-10
02
62 <0.8 62
60%
38 38
58%
190 180 370
63%
<1.3 ND
<1.1 40 <1.1 110 150
66%
<2.2 <2.2 <2.2 ND
630 630
ND
56
<10
76%
03
1300 ND1
2900
67%
92 92
62%
400 370 ' 1800
58%
<1.6 ND
1400 370 <1.3 350
2800
69%
<2.4 <2.4 <2.4 ND
1000 2300
ND
3800
<8.1
110%
HONS 218515
The values are given in ng/g ND Not Detected. NDD1 Not detected due to interferens from the big 2 i3,7,8-TCDF peak. ND` Not detected , no singnal for 13C-0CDDn.
c-n HONS 218516
3
fl5
2
<s
vt X o X in O o Qid. O t/i
E
5 icnn 1" >.
2 ci
1
<: tu HI CL UJ