CHAPTER 22
1954 Guide I
of 150 milinches per foot, or 600 milinches for 4 ft. If the first floor radi ators are located 3 ft above the mains, second floor radiators 12 ft above the mains, third floor 21 ft, and fourth floor 30 ft, the heads are 450, 1800, 3150, and 4500 milinches, respectively.
In forced circulation systems flow is produced mechanically by means of a pump driven by electricity, steam, or other source of energy. As
Hot Water Heating Systems
--Table 1. Iron and Copper Elbow Equivalents*
FITTING
Iron Copper!
Pipe TubinqJJ
Fitting
Elbow, 90-deg................ Elbow, 45-deg...............
Elbow, 90-deg long turn. Elbow, welded, 90-deg... Reduced coupling.......... Open return bend.......... Open gate valve............. Open globe valve.............
1.0 0.7 0.5 0.5 0.4
1.0 0.5
12.0
1.0 Angle radiator valve.......
0.7 0.5
Radiator or convector . .. Boiler or heater..............
0.5
|0.4 | Tee, per cent flowing
1.0 through branch:
0.7 | 100......... ..............
17.0 50................................
25...................
*
.
ln ne ?0.de* standard elbow is
Sb^ "d M
ol
525
fig*
milinches per foot of pipe
Fio. 1. Heads Resultjnu from Temperature Differf.nce (Gravity Systems)
forced circulation velocities are higher than those in gravity systems, and as the friction in a heating system varies almost as the square of the velocity, a given error in the calculation or assumption of the velocity is less im portant in a forced circulation system than in a gravity circulation systenh and, consequently, it is easier to design a satisfactory forced circulation system than a satisfactory gravity circulation system.
FRICTION LOSS Values of friction loss due to flow of water in the various parts of a heal ing system must be known in order to design either gravity or forced circu lation systems. The friction loss of fittings is customarily expressed ih'.eqihp