Document GRbo0xJej2GYGD8ZZQL0MZ1N

Section Number Issue Number Origination Date Revision Date Section Test Ethanolamines/Glycol Ethers In Plant Training (IPT) :15 :1.3 :09-01-91 : 12-23-97 :15 Author: Mike Viator Ethanolamines/Glycol Ethers Control Module Line-O-Logic Answers: 1. State what EBV-1036 is. Incoming ethylene oxide emergency block valve. 2. State at what pressure EBV-1036 will alarm on low pressure. 70 psig. 3. State at what pressure EBV-1036 will trip on low pressure. 50 psig. 4. State what EBV-1041 is. Incoming propylene oxide emergency block valve. 5. State at what pressure EBV-1041 will alarm on low pressure. 50 psig. 6. State at what pressure EBV-1041 will trip on low pressure. 20 psig. 7. State what EBV-2072 is. Aqua ammonia emergency block valve at MX-201. 8. State two ways to open EBV-2072 after it trips. Put on manual in the field or go on bypass and hit reset button. 9. State at what percent of chart will EBV-2072 trip on aqua ammonia low flow. 10 percent. 10. State what determines R-201 low NH3/EO ratio trip. Date Printed: April 18,1998 Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File: T:\ORIGINAL\IPT\EAGECONT\LINOLOG\ASOSLOG.DOC Page 1 of 3 ^ 058627 CONFIDENTIAL HIC-2075A 11. State what the low NH3/EO ratio trip setting should be. No less than 1.6. 12. State what valves trip when P-201 shuts down. EBV-2077 and EV-2071 (oxide control valve). 13. State what happens when TS-2072 is energized (the total emergency shutdown button). A. P-212 continues running on total recirculation. B. EBV-2072 closes at MX-101. C. P-201 shuts down D. EBV-2071 closes (EO emergency block valve at MX-201). E. EV-2071 closes (EO control valve at MX-101). F. P-205 shuts down G. Anhydrous ammonia to D-210 closes (emergency block valve). H. Anhydrous ammonia to D-210 closes (control valve). I. Suction valve (EBV-2009) closes. 14. State everything that will shut down P-101. A. Low oil pressure B. High vibration (if not bypassed) C. High discharge temperature D. P-106 shuts down E. P-104 shuts down F. Low catalyst flow 15. State two things that will shut down P-106. A. Catalyst line differential pressure (10" of water). B. Catalyst line high temperature (alarms at 50 degrees, trips at 75 degrees). 16. State what the low pressure alarm/trip is on the feed to R-101. A. Alarms at 240 psig B. Trips at 188 psig 17. State what the low pressure alarm/trip is on the feed to R-102. A. Alarms at 125 psig B. Trips at 100 psig 18. State what the high temperature alarm/trip is on the catalyst line to MX-101. A. Alarms at 50 degrees B. Trips at 75 degrees 19. State what the high pressure alarm/trip is on the feed to R-101, R-102, R-103. 650 psig alarm and 700 psig trip on all three. Date Printed: April 18,1998 Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File. T:\ORIGINAL\lPT\EAGECONT\LINOLOG\ASOSLOG.DOC Page 2 of 3 00 A 058628 CONFIDENTIAL 20. State what the high temperature alarm/trip is on P-101 discharge to R-101. 60 degree alarm and 80 degrees trip. 21. State R-201 high/low pressure trip settings. High pressure 975 psig, low pressure 500 psig. Revisions: Revision No. 1 07-15-93 Yearly Review Revision No. 2 12-18-94 12-18-94 Yearly Review Added 14F & changed 16A & 17A Revision No. 3 12-23-97 Yearly Review Date Printed: April 18,1998 Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File: T:\ORIGINAL\IPT\EAGECONT\LINOLOG\ASOSLOG.DOC Page 3 of 3 DO A 058629 CONFTDFNTTAL