Document GOjgYGqZ5B7pEzvjrjqeyDqx
Heating Ventilating Air Conditioning Guide 1939
connection must be nearer the heater than the return connection. In a correctl
designed two-pipe system, the pressure in the flow main is higher than that in the return
main, and a slight variation in the distances of the flow and return connections from th
heater is not material; but it is generally best to have the two connections about equallv
distant from the heater.
Y
In some cases it may be advisable to take the flow connection off the top of the main
and the return connection from the side, but in most cases both connections should beat
an angle of 45 deg. This method shortens the lines and substitutes 45-deg ells u.
90-deg ells.
Ior
Preferably, connection of the flow riser to a radiator should be to the upper tappjne
and connection of the return riser to a radiator should be to the lower tapping. When
hot water enters at the top of a radiator it will distribute itself along the entire length of
the radiator, and as it cools it will.settle gradually to the bottom; the cool water may
then be taken out of the radiator at either end.
'
Fig. 11. Method of Connecting Radiator to Allow for Expansion of Pipe
With forced circulation and high velocities, it is advisable to let the water enter at the top of the radiator and leave at the bottom of the opposite end. With gravity circulation and low velocities it makes little difference whether the water leaves at the end at which it enters or at the opposite end.
The connections of the risers to the radiators should be such that provision is made for the vertical expansion of the risers. This can be accomplished as indicated in Fig. 11 by using one tee and two ells for each connection. These connections should be pitched upward or downward, whichever may be necessary to prevent the formation of air pockets and to permit draining.
PROBLEMS IN PRACTICE
1 Will altering a hot water heating system from an open to closed type system (a) increase the'circulation and (b) give more heat?
a. No. Tests conducted by the A.S.H.V.E. indicate that there is little, if any difference in the circulation when the system is under pressure. The difference in temperature between the supply and return, and the friction are the governing factors. b. With a closed system the water may be carried at a higher temperature without boiling which permits warmer radiators.
2 What tends to prevent or to retard the circulation of water in hot water heating systems?
In both gravity flow and forced circulation systems, the friction which must be overcome when the water is flowing through pipes, fittings, valves, heaters, and radiators tends to
358
Chapter 17. Hot Water Heating Systems and Piping
retard circulation. For a given pipe the friction varies approximately as the
prevent o
velocity, and for given fittings, valves, heaters, and radiators, the friction
1.7 Pw"ofoximately. as the square of the velocity. It is therefore sufficiently accurate
vanes the friction in fittings, valves, heaters, and radiators in terms of the friction gS.dd elbow, as shown in Table 3.
_ .. single radiator located 10 ft above a boiler is connected with a flow and 3 1 Mark iron pipe, what is the pressure head maintaining the circulation if
return the water m
return riser is at 180 F and that in the flow riser is at 200 F?
ir' found from Table 7, Chapter 1, that 180 F water weighs 60.61 lb per cubic foot and winV water weighs 60.13 lb per cubic foot. The pressure head is independent of the size
frhe oipe. If the two risers were each 1 ft square, the water in the flow riser would
* .tn. gQi^ lb and that in the return riser would weigh 606.1 lb. Thus the water in the "T^rn riser would weigh 4.8 lb mdre than that in the flow riser. Consequently, the
resulting pressure head is 4.8 lb per square foot.
Pressure heads are generally expressed in feet, or inches, or milinches of water of a given t mperature. In this case water is at both 180 F and 200 F, so the pressure head is exDressed ip. terms of 190 F water. Such water weighs 60.39 lb per cubic.foot, and to ,>ciire a pressure of 4.8 lb per square foot, it is necessary to have a column of water having a weight of 4.8 divided by 60.39 = 0.0795 ft, or 0.9540 in., or 954 milinches. This
is the pressure head which maintains the circulation.
the elementary system of Question 3, if the radiator dissipates 14,000 Btu per hour, what is the velocity of the water in the pipe line, if the pipes are 1 in. in diameter? .What, if they are in. in diameter?
Since the temperature drop through the radiator is from 200 F to 180 F or 20 F, every nound of water flowing through the radiators delivers 20 Btu; consequently, 14,000 divided by 20 = 700 lb of water, or for l'90 F water, 700 divided by 60.39 = 11.59 cu ft of water must flow through the radiator and through the pipe lines every hour.
The interior area of a 1 in. pipe is 0.864 sq in. The velocity in the 1 in. pipe is 11.59 divided by 0.864 and multiplied by 144 = 1932 ft per hour or 6.44 in. per second.
For % in. pipe, the interior area is 0.533, and the velocity is 6.44 multiplied by 0.864 and divided by 533 = 10.44 in. per second.
5 If, in the elementary heating system of Question 3, a 1 in. pipe line is used, what would be the friction head?
If the radiator is connected with the heater to provide for freedom of expansion, the heat ing circuit may be assumed to consist of a heater, 25 ft of pipe, 8 elbows, 1 radiator valve, and 1 radiator. From Table 3 it appears that the heater and radiator are equivalent, in friction, to 6 elbows; hence, the circuit may be placed equal to 25 ft of pipe and 14 elbows.
From the diagram of Fig. 4 it appears that the friction head for a 1 in. pipe and a velocity of 6.44 in. per second is about 25 milinches per foot. For 25 ft of pipe, the friction head will be 625 milinches.
pi
It appears from Table 3 that the friction head in one elbow is , or in this case 0.54
multiplied by 0.54 and divided by 64.4 = 0.0045 ft or 54 milinches. Hence, for the 14 elbows the friction is 756 milinches. For the entire circuit, the friction head is the sum of the 625 milinches of the pipe plus the 756 milinches of the elbows, or 1381 milinches which equal 1.381 in.
6 If the elementary heating system of Question 3 is installed with a 1 in. pipe line, how will it function?
It is found from the answer to Question 3 that the pressure head is 954 milinches and from the answer to Question 5 that the friction head is 1381 milinches when the water is flowing with such velocity that the specified 14,000 Btu will be delivered with a 20 F temperature drop through the radiators. Since the pressure head is smaller than the friction head, the system will not function as planned for the water will flow through the
359