CHAPTER 31
1951 Guide
dampers and other fire protective details, see Pamphlet No. 90 of the National Board of Fire Underwriters.a
The recommended gages for steel (or iron) and aluminum sheet metal rectangular ducts are given in Table 8. Steel or iron sheets are specified according to the Manufacturers or U. S. Standard Gage System. Alu minum sheets are specified according to the American or Brown & Sharpe Gage System. Weights of black and galvanized steel and iron sheets per square foot of surface for various gages are given in Table 9. Similar data for 2S aluminum sheets will be found in Table 10. Weights of standard
Table 8. Recommended Sheet Metal Gages fob Rectangular Duct Construction*
Alu
minum B.&S. Gage
u.s.Steel.
Std.
Gage
Maximum Side,
Inches
Type of Transverse Joint Connections"
Bracing
24 26 Up to 12 S, Drive, Pocket or Bar Slips, on None 7 ft 10 in. centers
13 to 24 S, Drive, Pocket or Bar Slips, on None 7 ft 10 in. centers
22 25 to 30 S, Drive, 1 in. Pocket or 1 in. Bar 1 x 1 x | in. angles Slips, on 7 ft 10 in. centers* 4 ft from joint
31 to 40 Drive, 1 in. Pocket or 1 in. Bar 1 x 1 x f in. angles Slips, on 7 ft 10 in. centers* 4 ft from joint
20 41 to 60 If in. Angle Connections, or If in. If x If x f in. angles Pocket or 1$ in. Bar Slips with 4 ft from joint If in. x f in. bar reinforcing on 7 ft 10 in. centers*
18
20
61 to 90
1$ in. Angle Connections', or If in. Pocket or If in. Bar Slips
1$ x 1) x | in. diagonal angles, or 1J x lj x )
3 ft 9 in. maximum centers with in. angles
If x f in. bar reinforcing
2 ft from joint
16
18 91 and up 2 in. Angle Connections or If in. If x If x f in. diagonal Pocket or 1$ in. Bar Slips 3 ft angles, or If x If x f
9 in. maximum centers with If x . in. angles
f in. bar reinforcingd
2 ft from joint
* For normal prasura And velocities fees Table 4) utilired in typical ventilating and air conditioning sys tems. Where special rigidity or stillness is required, ducts should-be constructed of metal two gages heavier. All nnin-mlafayf ducts 18 in. and larger uhould be cross-broken. Cross-breaking may be omitted on uninsulated ducts if two gagas of heavier metal are used.
> Other joint connections of equivalent mechanical strength and air tightness may be used.
c Duct sections of 3 ft 9 in. may be used with bracing angles omitted, instead-of 7 ft 10 in. lengths with
joints indicated. ' **"Ducts 91 in. and larger require special field-study for hanging and supporting methods.
copper sheets are given in Table 11. In calculating the total weight , of d given length of duct work from these tables, it is customaiy to add 20 percent for the weight of joints and bracings.
Aluminum sheets of the 2S and 3S type alloy. And % hard temper are; readily workable, and can be used for practically all duct work. The 2S type (commercially pure aluminum) is suitable for all, except very large ducts. For large ducts, where more strength is desired, the 3S alloy with' % or hard temper is frequently used. The higher tempers, particularly full hard, do hot have the formability of the lower tempers. For verylarge ducts, where considerable strength is required, aluminum sheets
Air Duct Design Table 9. Weights op Black and Galvanized Sheets
683
U.S. Std. Gage
Black Sheets
Approximate Thickness, la.
i Weight Per Square Foot
Galvanized Sheets4
Approximate Thickness, In.
Square Foot
Steel
Iron
Ounces Pounds
Steel
Iron
Ounces Pounds
30
0.0123
0.0125
8
28
0.0153
0.0156
10
2G
0.0184
0.0188
12
24
0.0245
0.0250
16
22
0.0306
0.0313
20
20
0.0368
0.0375
24
18
0.0490
0.0500
32
16
0.0613
0.0625
40
14
0.0766
0.0781
50
12
0.1072
0.1094
70
11
0.1225
0.1250
80
10
0.1379
0.1406
90
0.500 0.625 0.750 1.000
1.250 1.500
2.000 2.500
3.125 4.375 5.000 5.625
0.0163 0.0193
0.0224
0.0285 0.0346 0.0408. 0.0530
0.0653 0.0806 0.1112
0.1265
0.1419
0.0165
0.0196 0.0228 0.0290
0.0353
0.0415 0.0540 0.0665 0.0821 0.1134
0.1290
0.1446
10.5 12.514.5 18.5
22.5 26.5
34.5 42.5
52.5 72.5 82.5 92.5
0.781 0.906
1.656 2.156 2.656
4.531 5.156 5.781
^Galvanized sheets are gaged before galvanizing and are therefore approximately 0.004 in. thicker.
should be 2 gages heavier than indicated in Table 8, and should be amply stiffened. Joints can be of any of the standard designs, and can be fabri cated in the same manner as iron; Repeated sharp bending and rebending should be avoided, as aluminum has a tendency to crack under such treat ment. Aluminum of 16 B. & S. gage or heavier can readily be welded by the metallic arc or acetylene process. Soldering is difficult and is not gen erally recommended. Riveting is. done in the same manner as in iron or steel sheet. Self-tapping screws tend to loosen because of the softness of aluminum.
HEAT LOSSES FROM DUCTS
In designing duct systems, the heat gains or losses of ducts should not be neglected. Heat gains in large duct systems'can be quite considerable, not only if the duct passes through unconditioned space, but also on long duct runs within conditioned space. Proper insulation will remedy this situation considerably, but sometimes a redistribution of the supply air to the various supply outlets is necessary in order to compensate for the heating effect of the duct surface.
The thermal transmittance U for ducts can be found as follows:
For uninsulated metal duct, 17 = ---i--
/I. 4- /I
(20)
Table 10. Weights and Thicknesses of 2S Aluminum (Density 0.098 lb/cu in.)
B. ft 8. Gage
28 26 ,24 22 20 .18 16 14 .
Thickness, Inches
Decimal
Nearest Fraction
0.012
0.016 0.020 0.026 - 0.032
. 0.040 0.051 0.064
1/64 1/64 1/64 1/32
. 1/32 3/64
. 3/64
1/16
Weight per Square Foot
Ounees
Pounds
2.7 3.6 4.6 5.4 7.2
9.0 11.5 14.4
0.169 0.226 0.282 0.353 0.452
0.563 0.72Q
0.903
1