GPR packaged gas-fired boiier--a new concept for low-cost hydronic heating
The revolutionary GPR is a new circular cast Iron boiler that's amazingly compact in size and light in weight The secret of its efficiency is the high heat transfer rate of the vertically-stacked THERM-O-GRID sections, an exclusive American-Standard design. With A.GA ap proved outputs of 60,000 and 80,000 Btuh, the GPR is ideal for residential application-especially in new home con
struction. The GPR is available completely packaged in three and four section sizes. All controls are mounted and pre-wired for continuous forced hot water circula tion. This new low-cost boiler is easy to handle, quick to install. One man can position it on the job-in a 2 x 2 foot area of floor space. The GPR is a little boiler that does a big heating job!
1-:.-3Tthocc-features low silhouette design for stream
lined appearance.
2-.:urav steel conooi'-features integral asbestos gasket for gas-tight seal and is easily removable for servicing.
3- nsuici'o stoei locxet--is composed of four basic pieces-- top, front, back and bottom-with attractive gray finish. Top and front panels are easily removable for access to section assembly and combustion chamber.
4-scmrcis--are factory-mounted, pre-wired, and easily ac cessible for service. Extremely sensitive limit control, de veloped exclusively for GPR, features quick-response to prevent excessive boiler water temperature.
5-cry cose ossemoiy--reduces boiler weight. Three steel legs support section assembly. Enclosed type combustion chamber provides compact design, superior performance.
6-.'inner sra.ier issemciv--incorporates burners, manifold brackets, and rear burner supports into a single, compact unit that slides in and out for quick maintenance and E-'t adjustment Pilot burner is attached directly to combustion chamber for easy access. Combination gas valve features built-in gas regulator (except for LP gas) and thermocoupletype safety pilot switch.
The exclusive THERM-O-GRID section is a compact (12 x 12 x 3 inch) lightweight (30 pound) cast iron sec tion designed by American-Standard to produce a remarkably high ratio of heat output per pound through the use of tubular-finned surfaces. When the THERMO-GRID sections are assembled, the tubes and fins oppose each other to
increase flue gas turbu lence and further im prove heat transfer. This staggered arrangement also permits quick, thorough cleaning of sec tion assembly. The sec tions are tested at 2Vi times normal water work ing pressure. Top section functions as an internal air separator, thereby eliminating the need for
an additional device.
W J " \
packaged gas-fired boilers
GPR ratings
boiler number
far installation! from saa level to 2000 fia
A.6JL ratings
input (Btu/hr)
output (Btu/hr)
net i=B=R ratings e (Btu/hr)
chimney
SiZO (Inchts)
height (fast)
water content (gallons)
natural, mixed or manufactured gases
GPR-60
75,000
60,000
45,000
5
20 2.1
GPR-80
100,000
80,000
60,000
5
20
2.7
LP gases
GPR-60
70,000
56,000
42,000
5
20
2.1
GPR-00
95,000
76,000
57,000
5
20 2.7
For altitudes above 2000 ft., ratings should be reduced at the rate of 4% for each 1000 ft- above sea level. a Net l = 8 = R ratines shown include allowance for normal piping loss and pick up load. American-Standard should be consulted before selecting a boiler for installations having unusual piping and pick up requirements. Nate: GPR packaged boiler furnished for forced hot water circulation only.
crated dimensions
boiler
dimensions (inches)
approx. shipping
number
H
W
L
weight (pounds)
GPR-60 GPR-80
27% 25 28% 30V. 25 28%
205 235
front ^rt:.-nrc3VgTUsrm.!t
minimum clearance for closet installation
Notts Are# of each opening -- 1 sq. In. for eacn 1000 Btuh input-with a mini mum of 100 sq. In.
Cir i 'i*1 4"
ESS
front'
ventilating
4" inlet air opening
d, fl
D
side view
GPR packaged gas-fired boilers are designed and built to comply with the American Society of Mechanical Engineers' Code, and bear their approval symbol. Ratings have been approved by the Institute of Boiler and Radiator Manufacturers. The GPR has been approved by. the American Gas Association for all gases. It also bears A.G.A. approval for installation on combustible flooring and for close clearance installations.
Standard
3
12014
OPR packaged gas>fired boilers
near boiler piping
Procedure for fllllnf series Imp Heatrim System!
1. Close all zone valves except zone to be purged. 2. Open boiler drain valve. 3. Open fill valve. 4. Close purge valve. 5. Vent air from boiler by manually opening relief valve. 6. Open second valve to be purged. Close first zone. After
second zone is purged, open third zone valve and dose second zone. Repeat for as many zones as in system. (Note: Always have one zone valve open). 7. When alt zones have been purged, close boiler drain cock. 8. When water appears at relief valve, release lever and allow to close. 9. Continue filling until pressure gauge reads approximately 12 Ibs./sq. in. Close fill valve. 10. Open purge valve.
Note 1: Where multiple circuits am used without zone valves, balancing velvet should be installed for balancing. These can be shut off to purge each circuit valve individually.
Note Zi For a single loop Heatrim System, no additional vents, valves, drains or other accessories are required.
4
heller number
input specific
burner Btuh
gravity tf gat
Mtural, mixed and manufactured pus
ustwar.ga*as/'J$g
530a Btu cart.
550 Btu ca.lt
800 Btu ca.lt
800 cBatuft
1000 cBatfut
1100 Btu cafL
1200 Btu ca ft
500 Btu caft
550 Btu caft
700 Btu caft
750 Btu caft
800 Btu caft
2500 Btu caft
3300 Btu caft
25,000 0.40 25,000 0.50
V, Vfc
25,000
25,000 GPR-60 25,000
25,000 25,000 23,300 23,300
0.60
0.65 0.70 0.80 0.90 1.53 2.00
-- X. 36 38 X. 43 44 27 -- 35 37 41 42 -- 27 34 37 40 X. 43
-------- ---- --
----
-- -- ___ ___
29 Vt 31 31 28 30 Vh 31 X. 29 30 Vb
32 31 31
54 55
33,300
33,300
33,300 33,300
GPR-80 33,300 33,300 33,300
31,600
0.40 0.50 0.60 0.65 0.70 0.80 0.90 1.53
26 26
-- X. -- ___ 19 32
19 -- V. 31 -- 19 30 31
_ _ _-
35 35 38 33 35 33 34 36
--
___
__ ___
X. 26 28 29 20 24 26 28 19 21 24 26
30 29
28
31,600
Both 0.40 and 0.65 gases are required by supplementary utility requirements.
53
pressor* tabls
i
-gas -
heating ; value a
flat. . -
manifold pressure In HiO
city 525-550 city 800-1200 LP 2500 & 3300
sewage 600-800
2.5 3.5
11.0 3.0
e Heating value of gas at sea level (60*F and 30 in. Hg.)
Note: Table shows orifice sizes by numbered drill sizes. Sea level ratings are to be used for eleva tions between 0 and 2000
ft. For altitudes above 2000 ft., sea level ratings should be reduced 4% for each 1000 ft. above sea level.
Form No. 92-01 2 **. 2 !