Document GKZbLZZEkJYeO02XQ1eoMZzRv

Mr. L. J. 1 'right February 24, 1966 L. E. Clark, Jr. L. C. McLean Fairfield Works Standards for Roofing and Siding The attached "Fairfield Works Standards for Roofing and Siding" baa been prepared in order to submit it to American Bridge Division in response to their request. Please review it and indicate your approval or recomnended changes. LCMcLean/bf Enel. cP -'PkT Chief Engineer USHO 002861 PATHPIELD WORKS STANDARDS FOR ROOFING AND SIDING 1. TYPE 1.1 - Pre-painted, galvanised, corrugated sheets will be used for all new buildings, and for replacement of roofing and siding on delet ing buildings when complete roofing and/or siding is replaced. Sheets will be furnished by Fairfield Works in 27-1/2" widths for roofing end 26" widths for siding. Only touch-up field paint ing will be required. 1.2 - Standard 1.23 ounce coated 27-1/2" wide roofing and 26" wide siding shall be used for repairs that include partial replacement of roof ing and siding. These sheets shall be field painted. 1.3 - In special cases, 2.5 ounce coated 38" .wide roofing and 37" wide siding; stainless steel; or coated sheets may be required. Fairfield Works will provide American Bridge with the necessary specifications in these particular situations. 2. MAXPfifti AVAILABLE LENGTHS 2.1 - 27-1/2" wide, 24, 22 and 20 gauge - 14' length 2.2 - 27-1/2" wide, 18 gauge - 12* length 2.3 - 26" wide, 26, 24, 22 and 20 gauge - 14* length 2.4 - On special orders 16* lengths may be obtained in 26 through 20 gauge. 3. ERECTION OF CORRUGATED ROOFING AND SIDING 3.1 - Attached general specification "Removing and Erecting Corrugated Roofing and Siding" dated June 18, 1964 provides Fairfield Works erection standards. LCHcLean/bf 2-24-66 USHO 002862