SHELDON INDUCTION FUME HOODS
Manufacturers of Laboratory Equipment for Schools, Industry, and Hospitals.
SHELDON'S induction hoods are designed for use in air-conditioned laboratories or in any situation where it is necessary to conserve room air.
By injecting regulated volumes of "out door" air into the working areas of the hood to supplement the primary airflow from the laboratory, the following con trolled conditions may be achieved:
1. Sufficient volume of air passes through the working areas of the hood at the face velocity required to insure com plete evacuation of fumes from the system. The exhaust system of the Sheldon induction-type hood handles the same volume of air that the exhaust system of the conventional hood handles at a face velocity of 70-80 linear feet per minute.
2.
At the same time, air movement from the room into the hood has a low enough velocity to minimize turbulence within the hood and assure quiet operation, and to prevent objectionable drafts in the work area, and excessive drain on the heating, cooling, and air-conditioning systems of the room. The difference be tween the exhaust volume and the vol ume of intake from the room is provided by adjusting the supplementary-air
supply.
3. Sufficient volume of air flows into the hood from the room to carry generated fumes into the fast-moving, high-volume evacuation air currents, and also to in sure optimum laboratory air changes.
If air movement from adjacent parts of
the building to the laboratory is desired,
a condition of negative pressure in the laboratory may be induced by lowering the supply-fan capacity or increasing the
exhaust-fan capacity. Also, even if the
front sash is closed, the hood will purge of fumes because a definite part of the
exhaust capacity is still being supplied
mechanically and passes through the hood.
Except for minimum filter requirements, provided for in the hood design, supple mentary air seldom needs to be treated, since it does not enter the room.
The following table gives the velocity, velocity pressure and total entrance loss for both exhaust and supply for various lengths of hoods with duct sizes as shown in diagrams below. These values are for volumes as shown. These values are based on exhaust fan capacity capable of producing a face velocity of 75 lfm with only the exhaust fan operating and with a supply fan capable of introducing % the exhaust capacity and producing a face velocity of 25 lfm with both fans operating.
%
% -p
1412
%
Air System Equipment
Exhaust
Hoods
E. H. Sheldon Equipment Company
Muskegon, Michigan
SHELDON INDUCTION FUME HOODS
Manufacturers of Laboratory Equipment for Schools, Industry, and Hospitals.
EXHAUST @ 75 L.F.M. face Vel.
SUPPLY @ % of exhaust
Hood Length
3" 4' 5' 6' V $'
cfm
487 690 900 1087 1275 1500
Vel
1800 2000 2000 1900 2000 2000
VP
0,20 0.25 0.25 0.23 0.25 0.25
Entrance
Loss
0.30 0.37 0.37 0.42 0.44 0.44
cfm
324 460 600 724 . 850 1000
Vel
1900 1800 1650 1400 1600 1800
VP
0.23 0.20 0.17 0.13 0.16 0.20
Entrance Loss
0.34 0.30 0.26 0.20 0.24 0.30
* Total negative static developed by the hood. The conversion factor to obtain entrance loss from velocity pressure is 1.5 for 3 ft, 4 ft and 5 ft hoods, and 1.75 for 6 ft, 7.ft and 8 ft hoods.
** Total positive static developed by the hood. The conversion factor for all hoods for the supply air static is 1.5. These statics should be added to the duct resist ances when computing fan sizes.
tXMAUST 7" DIA.
rhood
o'CTO
EXHAUST
" DIA.
svmr 7- or*.
o' ox)
EXHAUST 10" OIA.
crO *o
EXHAUST D" DIA.
5' HOOD
SUPPLY 7" OIA.
O
EXHAUST 11" DJA-
SUPPLY 7'.' DIA.
^o
EXHAUST 12" DIA.
5' Hood operating under the above conditions.
The duct stubs are located on the top of the hoods as shown. The supply air can enter from below when building condi tions require such arrangement. The values given in the table, for various lengths of hood are for average condi tions.
Consultation is solicited without obliga tion on other or unusual conditions. Since the hoods use a definite volume of "conditioned" air, their requirements should be considered very early in the
work of designing and specifying heating and/or conditioning plants.