CHAPTER 24
1956 Guide
inside'design temperature is other than 70 F, the values determined from Fig. 12 must be corrected by values obtained from Fig. 13. The follow ing example illustrates the use of Figs. 12 and 13.
Example S: The outside walls of a room have a coefficient of heat, transfer U = 0.15. Inside and outside design air conditions are 68 F and --20 F, respec tively. Determine the inside surface temperature of the wall.
Solution: From Fig. 12 the inside surface temperature for 70 F and --20 F, and a U value of 0.15 is found to be 61.5 F. Then from Fig. 13, for a At = -- 2 deg and a U value of 0.15, the correction is --1.8 deg. As the correction is negative, the inside surface temperature will then be 61.5 -- 1.8 = 59.7 F. The total panel output can
then be determined from Figs. 9, 10, and 11.
`
Panel Heating
581
1. Selection of Design Conditions
a. Outside design temperature/ --10 F.
b. Inside design room air temperature, 70 F.
c. In this problem a floor panel heating system will be no basement. Insulation will be used between slab and fill.
d. Heating medium, hot water.
e. Floor surface temperature, 85 F (Maximum).
used,
There is
The heat transmission coefficients of the room surfaces are given in Fig. 14. They would usually be obfcained from Chapter 9. The room heat Toss can be calcu-
t *!
Fig. 13. Inside Wale Surface Temperature Correction for Inside Air Temperatures Other Than 70 F
A! = t, - 70 If At ia positive.' tw* hr + correction If At is negative: ' hr -- correction
* inside air temperature hr = intide wall surface temperature based on t* = 70 F t*' > actual inside wall surface temperature
After the various wall surface temperatures have been determined, as described, the unheated mean radiant temperature UMRT of the space may: be calculated as illustrated in Step 3 of the following section on Floor Panel Design Illustration.
Panel Edge Loss
, Refer to the section, Heat Losses from Floor Slabs, in Chapter 12. These' losses will affect slab temperature and water temperature near outside, walls, and must be included in either the room loss or the panel input. In the following example, Item 5, Part 4 can be considered to include this loss, but if the edge loss exceeds the amount allowed by Part 4, the larger loss should be used.
FLOOR PANEL DESIGN ILLUSTRATION
The several steps in the design of a panel heating system are listed and illustrated in the following example of the design of a. floor panel for the room shown in Fig. 14.
Fig. 14. Room Plan fob Illustration of Method of Designing, a Panel Heating System
. Data: Values of overall heat transfer coefficients as calculated:
1. Outside walls V = 0.10
3. Floor
U = 0.36
2. Ceiling
17 = 0.08
4. Windows
U = 0.55
'
lated in the conventional manner, as outlined in Chapter 12. The calculations are shown in Table 1. The he t loss through the surface areas containing the heating medium is not included in the calculation.
The calculated rate of heat loss will determine the amount of heat which must be supplied by the heating panels to the room.
Table 1. Calculated Heat Loss of Room (Fig. 14)
Surfaces
Area Sq Ft
Outside walls......... - 272
Glass......... .............. 80
Inside walis....... 352
Ceiling.
480
Fioor
480
Infiltration
.
Total heat loss
V
0.10 0.55 -- 0.08 --
Calculation
272 x 0.10 x 80 80 x 0.55 x 80 No heat loss 480 x 0.08 x 80 Heating panel 3,840 cu ft x .1.50 x 80 x 0.018
Heat Lobs Btu/hb
2,176 3,520
0 3,072
0 8,295
17,063
3. Determination of UMRT
The calculations for determining UMRT are shown in Table 2. The inside sur face temperatures shown in the fourth column were determined from Fig. 12: