Air Conditioning
Industrial Beating; Direct-Fired Heaters
Campbell Heating Co.
3121 Dean, Des Moines 17, Iowa
WINTER-CHASER AIR CONDITIONING SYSTEMS
EASTERN REPRESENTATIVE: Neil Adams, 22 Jefferson St, Lambertville, N. J. Tel. No. 2-0655
HORIZONTAL UNIT HEATER Oil A Gas
HI-BOY UNIT HEATER Oil A Gas
HEAVY DUTY HEATERS
For Large Churches, Schools,
(Up to 3,000,000 Btu)
Commercial & Industrial Buildings
LO-BOY Oil A Gas Fired
75 F Heating Guarantee
If the heating plant design is approved by our Engineering Department or de signed by a Registered Engineer and the heater and blower are furnished by us and are in accordance with our ratings, we will guarantee the heating of all rooms to which warm air is delivered to 75 F in the coldest and windiest weather.
10 Year Durability Guarantee
All Campbell Heaters installed as de scribed above are guaranteed for 10 years against repairs from any cause, parts to .be furnished free f.o.b. the factory., Motor, humidifier, automatic burner and controls and other parts not manu factured by us carry their manufactur ers' guarantee of one year against de fects.
Engineering Service
Our Engineering Department will be glad to help the consulting engineer or architect solve any heating, ventilating or air conditioning problems or help with layouts and specifications for any large building. Our Engineering Department consists of trained graduate engineers backed by 60 years of practical experi ence.
1268
Campbell Heating Co,
Air Conditioning Di?e"S3hedHeSter.
SPECIFICATIONS and DIMENSIONS
HEATER
Unit No.
Btu
Output
Capacity BTU/ Hr. f
Heating
Surface Sq Ft
per Sq Ft
Heat ing Sur
face
Normal cfm 135 Dischg, Temp.
BLOWERt
MAX. FUEL RATES DIMENSIONS
Assumed External Motor Oil Static In. hp gpb
Water
1000
Btu Gas cfh
LP Gas gph
Coal
Lbs Per
H in.
L in. Win.
Hr.
Hi Boy & Horizontal Unit Heater--Oil & Gas for Churches, Schools, Commerical & Industrial Buildings
HU200 200,000 HU250 250,000
83 2410 2600 83 3000 3300
H
V* 1.8 250 2.5 ?4 2.2 312 3.1
66 66
HU300 . HU350
300,000 119 2520 4000 350,000 119 2930 4600
h h
H 2.7 375 3.8 1 3.1 437 4.4
72 72
HU400 400,000 180 2220 5300 HU500 500,000 180 2780 6600
a M
1 3.6 500 5.0 m 4.5 625 6.3
84 84
HU600 i 600,000 244 2460 8000 HU700 700,000 244 2870 9200
h M
2 5.4 750 7.5 2 6.3 875 8.8
99 99
HU850 850,000 333 2540 11000 HU1000 1,000,000 333 3000- L-13000
H H
3 7.6 1060 10.6 3 9.0 1250 12.5
108 108
48 48
54 54
60 60
78 78
106 106
23 23
29 29
84 34
40 40
48 48
Lo Boy Oil & Gas Fired for Large Residences, Small Churches, Schools, etc.
H200 H250
H300
200,000 100 2000 2600 250,000 125 2000 3300
300,000 136 2200 4000
Vt h h
h 1.8 250 2.5 M 2.2 312 3.1 M 2.7 375 3.8
52 41
57 85 41 61 87 50
H350 H4Q0
H500
350,000 152 2300 4600 400,000 167 2400 5300
500,000 200 2500 6600
H H a
1 3.1 437 4.4
3.6 500 5.0 U4 4.5 625 6.3
61 87 50 61 87 50 74 91 60
H600 H700
600,000 240 2500 8000 700,000 280 2500 9200
H H
2 5.4 750 7.5 2 6.3 875 8.8
76 97 72 104
60 80
8000 Series Oil, Gas, Stoker or Hand Fired For Large Schools, Churches, etc.
8075
8100 8125
840,000 280 3000 11.000 660,000 320 3000 12,500 1,080,000 360 3000 14,100
a H H
3 7.5 1050 10.5 100 3 8.6 1200 12.0 114 3 . 9.7 1350 13.5 129
93 134 95 153 97 171
76 76 76
8150 8175 8200
1,320,000 440 3000 17.300 1,440,000 480 3000 18.900
1,800,000 600 3000 23,600
H H H
5 11.8 1650 16.5 157 98 195 5 12.9 1800 18.0 171 99 202 5 16.1 2250 22.5 214 120 216
76
76 94
8250 8300 8350
2,250.000 750 2,700,000 900 3,150,000 1050
3000 29.500 3000 35,400
3000 41,300
H H H
7W 20.1 2810 28.0 268 120 243 94 7W 24.1 3380 33.8 320 132 251 104 10 26.1 3940 39.4 375 150 251 114
8000 Series Unit Heater--Oil, Gas, Stoker or Hand Fired--For Large Industrial Buildings
U8125 1,080,000 360 3000 14,100 Consult 2-1 '9.7 1350 13.5 129 97 105 76
our
U8150 1,320,000 440 3000 17.300 Engineers 2-1W 11.8 1650 16.5 157 98 118
U8175 1,440,000 480 3000 18.900
if
2-1H 12.9 1800 18.0 171 99 130
U8200 1,800,000 600 3000 23,600 duct
2-2 16.1 2250 22.5 214 120 137
76 76 94
U8250 U8300 U8350
2,250,000 750 2,700,000 900 3,150,000 1050
3000 29.500 3000 35,400 3000 41,300
is to be
used.
2-3 20.1 2800 28.0 268 120 157 94 2-3 24.1 3380 33.8 320 132 157 104 2-5 26.1 3940 39.4 375 150 157 144
Type A units include Special Oil or Gaa Heater, Casing, Blower, Motor, Drive, Filters, Humidifier, and Blower Control but less Burner, Controls and Built-in Combustion Chamber. TypeB units include same as Type A plus Oil or Gas Burner and built-in Combustion Chamber and Stand ard Controls.
t Based on 80% thermal efficiency for oil and gas and 70% for coal. Add 10% to 35% over calculated heat loss for pick-up load and 10% to 15% for duct radiation losses. The higher figure is preferable for best operating economy and life of the equipment.
A0r*0^er a*r vlumes ad static pressures consult our Engineering Department. 9 An induced draft blower can be furnished if a stack or chimney is not available. The gas passages of the
heaters are adequate so an induced draft blower is not ordinarily needed.
For Complete Specifications, See Sweet's Catalog Service