- IL t C 0:i'/ technical catalog bulletin G-2 gas fired boilers hot water or steam G-2 cast-iron gas boiler--compact, economical, easy-to-install The completely automatic G-2 gas fired boiler, for water or steam heating, provides fast, economical installation, operating efficiency and long-lasting dependability. Only 33V2" high, the G-2 requires minimum space, making it particularly suitable for residential installations where space is at a premium. Special "off the floor" jacket design prevents rust and corrosion, damage in shipment and allows boiler to be "walked" into position with jacket in place. Packaged water or steam boiler--Five popular sizes (3-7 sections) of the forced circulation or steam packaged units are shipped completely assembled and crated, ready for immediate installation. All controls, burners, accessories-even the circulator (water only)-are in stalled and wired before shipment. Forced circulation water boilers (4-7 sections) may be equipped with a spe cially built, factory-installed, l = W=H rated tankless heater. The 3-7 section sizes are also furnished as an all-purpose package without the circulator to permit either forced or gravity installations. Non-packaged water and steam boilers--Available in all sizes (3-11 sections) with flush or deluxe jacket as forced circulation water boiler or all-purpose steam or water (forced or gravity) boiler. Non-packaged boilers feature factory-assembled sections, pre-assembled manifold and pre-assembled gas controls. (Factory-installed l = W=H rated tankless heater available for forced circulation water boiler only.) ELIMlNAIRE-is an exclusive cost-saving installation feature of the G-2. This unique built-in air eliminator is integral ly cast into the left hand end section and is furnished on all boilers, speci fically for hot water installations. The ELIMINAIRE* baffle diverts rising air bubbles into a tapping connected to the expansion tank. No external device is required to separate air and waterthus reducing both costs and instal lation time. I = W = H rated, high capacity tankless water heater-is available in four sizes and factory-in stalled in boilers begin ning with the 4-section size. Designed exclusively for forced circulation boilers, the water heater fits into the large, offcenter, oversized 5" nipple port at the top of the boiler sections. Complete factory-installed manifold and wiring -- saves installation time and costs on all packaged models. Onepiece burner-mixing tube is precision fitted into manifold spud and rests se curely on rear boiler base plate. Simple regulation of the air shutter is the only adjustment required for correct firing. New drill port and ribbon-type burners improve performance. G-2 gas fired boilers 1 1- ELIMINAIRE* (not shown)--exclusive built-in air elimi nator for hot water installations eliminates need for an external device to separate air and water. 2- water heater-large, copper coil, finned tubing tanklesstype water heater has dependable l=W=H ratings. 3- controls-all controls are mounted on front and left side of boiler for easy accessibility. Controls, accessories and manifold are factory-mounted and assembled on all packaged boilers. 4- jacket-sturdy steel jacket is fully insulated with heavy glass fiber insulation to prevent wasteful heat loss and keep jacket cool. Jacket features attractive brown and beige finish with modem square-corner styling. It is ELIMINAIRE* is a trademark of AMERICAN STANDARD Inc. shipped factory-installed on all packaged boilers. 5- built-in drafthood-completely enclosed in deluxe jacket models (except G-23)-keeps boiler height at an extra low 33V2". External-type drafthood furnished on G-23-D and all flush models. 6- lifetime cast iron sections-have multiple pin-like pro jections for maximum heat extraction. End sections are extended at base to form supporting legs of boiler-elimi nating the need for a separate base. Sections are water tested at 80 psi (2V2 times rated capacity of relief valve). 7- factory-assembled manifold and controls-are installed on all packaged boilers. They are completely enclosed by the jacket on deluxe models. American-Standard G-2 gas boilers have ratings approved by the Institute of Boiler and Radiator Manufacturers and are constructed to the specifications of the American Society of Mechanical Engineers. The boilers are design certified by the American Gas Assertion for all gases. They also have the design certified by A.G.A. for installation on combustible flooring with a special floor shield 3 and for close clearance installations. All sizes of the G-2 are available in models for forced hot water, gravity and steam systems. AMERICAN STANDARD 3 boiler number for installations from sea level to 2000 ft A.G.A. ratings' : net l = B = R ratings,* input output. (Btii/hr) (Btu/hr) . water steam:. * stearrfc (Btu/hr) (sq. ft.); (Btrt/h'ry chimney height? diameter above(inches) U1 41 l^. ((ee$ water content (gallons) water boiler steam boiler G-23 G-24 G-25 G-26 G-27 G-28 G-29 G-210 G-211 60,000 90,000 120,000 150,000 180,000 210,000 240,000 270,000 300,000 48,000 72,000 96,000 120,000 144,000 168,000 192,000 216,000 240,000 41,700 62,600 83,500 104,300 125,200 146,100 167,000 187,800 208,700 150 225 300 375 450 525 600 675 750 36,000 54,000 72,000 90,000 108,000 126,000 144,000 162,000 180,000 4 5 5 6 6 7 7 7 7 10 7.6 4.9 10 9.6 6.2 10 11.7 7.6 10 13.7 8.9 10 15.7 10.2 10 17.7 11.5 10 19.7 12.9 10 21.7 14.2 10 23.7 15.5 built-in tankless heaters (optional)"' |=W=H ratings--(gpm)A_ heater 218* _ 2Vi -- -- -- -- -- -- -- heater 222* _ -- 3 3V.i 37z 372 372 372 3V2 heater 226-' _ -- -- -- 4 47a . 4V4 474 4V2 heater 232* _ _ ___ ___ ___ ___ 472 4% 5 For attitudes above 2000 ft, ratings should be reduced at the rate of 4% for each 1000 ft. above sea level. Net l = B = R ratings shown are based on a piping and pick up al lowance of 1.333 for steam and 1.15 for water. American-Standard should be consulted before selecting a boiler for installations having unusual piping and pick up requirements. Heaters have been tested with G-2 boilers and are available only factory installed in the above sizes except for the all purpose boilers. Gallons water per minute heated from 40#F to 140PF with 200*F boiler water temperature. Last two digits designate lineal feet of Tru Fin tubing in heater coil.' Domestic hot water connection size is W for all heaters. Note: The following suffixes, if added to G-2 boiler number, represent: F-flush jacket; D--deluxe jacket; T--with tankless heater; P-packaged shipping; C-with floor shield approved for combustible flooring. For example--to order a deluxe G-25 complete with heater, combustible flooring shield and completely packaged--the following boiler designation would apply (G-25-DPTC). . standard equipment | al| boilers^?;, r v23 ' additional standard equipment (cont.) packaged--ILpurpose on ly (DPG)--water, limit control. Litff Rite-manifbld gas^lve incirjrding mairvofferatbrf mair^/ bSluie: instated jacket, thermostat. . ual shut-oft ya lve,,;pi lot; fil terj pressure regulatog (except; LE7 gas)and pilostat.;- v;,: .- ,'.. .>. -'V norti-packaged--all purpose - i G-210 Snd'ff211riaturaf and LP gas-- . : .G-27thhiG-211 mixed gas-- - " ,-?V > - ,Vi~ ' - , & Water (forced) With heater (WT) . Diaftragm fis^ve:'gaSpressure regulator(ertcept LF?gas):; -;- 'fanWeSs heater, triple Aquastat (high and low limits, circu- --c-.-Ss.iV- .... ~ . lator. relay); flush or deluxe insulated jacket, less heater (Wi} . , : 3r Deluxe insulated jacket;, immersion limit control. I^^Sfw^^^i.ii^.insijI'at^jacketVj^ ' v pfiona I: eq u.ipm e rit:'*~ all ppiiers*'^.^'v ;.r-; . ... V.-4'-^' - SfheSffgeiignjsetrag.'fizei(n2g4Vc..o.;.na-tn-rdo-l-Ss-*.EfloJ- oforrsphai-eclkdagfoerdcaolmlpbuurpstoibsfeeaftnSd&'hriofing-; 4k- ->- ^^'4alfHeq|fibbirers> - .f v ,, o ^ For selection of built-in tankless heater for forced'circulatiori/; ^ /u.'.'iA* 0 * se ratings table above. o 4 gas fired boilers 9 forced circulefion l-purpcse 2"flow^ D front view*" .-.fix:''${< r-.$t; "r 'location' tappings ?M.-' '';vwater K," 5s Sesize'^r? $2!&k .. c.r forced ..-1Ut.:. - .V --- *r ->g*.ravity A % immersion limit control immersion limit control ' B Vz temperature and altitude gauge temperature and altitude gauge C % reverse acting control -- D % pressure relief valve <Eliminaire) pressure relief valve E % combination operating controls; high and low limit, relay control -- F % high limit, circulator operation control -- G 3 -- gravity flow H Vz -- -- iG-23-DPG packaged boiler furnished with left end section without heater opening but tapped iv for combination control. LH. side view (water and stearaK front view'rr| *y-- tt .* . ' steam pressure gauge . -- safety valve -- -- flow or blow-off gauge glass : rruJlss.- I;1- boilernumber natural gas G-23 G-24 G-25 G-26 G-27 G-28 G-29 G-210 G-211 Vi Vi Vi Vi Vi % Vi % Vi mxd.V. 'f LP gas... , gas Vi Vz Vi Vz Vi y2 Vi Vz Vi Vz Vi Vz Vi Vz Vi Vz Vi Vz Note: Connection sizes shown apply to both flush and deluxe jacket assemblies. ScomEt^ible'f?oof and'ori combustible floor when equipped wfttv bottom- pah and ^Bdiat^6^TshleldA,rf,'*'''', AMERICAN STANDARD G-2 gas fired boilers not water boilers. balancing cocks of zone valves . jzone !r .3 zone I zone ikWlJ -G.. it--!*&? IT. 3 check valve (If used) fill valve. (manual).- /A ' purge valuer;'7-' . (gate) .. . HXfc-'- -^1 for multiple zone,,, j-.i.: '..) circuit'qpe'fatio'n*f.V:' ''?7 near boiler piping. reducing elbow: equalizerHartford loop ii-Vj:' '/:. *o'n a single cfrcurt job balanctng; - cocid'iM zoiifCvalvts not needdd- return sream Doners - riser (mm. height 18'')-,)i V. >S|rft'f . ' --a ...if Procedure for filling series loop Heatrim System: It Close all zone valves except zone to be purged. - 2,_Open.boiler)drainValve. , . 3, Operi.fill valve^-^ - /;)?*:;- : ' '.v' 4,_ciose purge yalve.^) , 7 ' ') ... -v-.. " .'5'."Venf*aif. from' t>piief; by manually.)opening, relief valve. 1 6. Opefriecond'yaive'td be pUrged.t Close) first zone. After ; . ,, .- second zone'is purged .opien,.third,zone, valve and close ^v; second zone;-;Repeat, fon aftriiahy. zones as in system) */. 7 (Note:T;Always. havjj '/o.ha^z?n^alyaXof>en.) v. 7. When; all, zones, fiave bdentpu'rgedV;.dose boiler drain ...cock;,).'..'-:" ' 8. When water);appears at relief`Valve,- release lever and allow.to close: - ft.-.-'v:'.- ..- 9. Continue,'filling, until pressure gaugedreads approxi-. ,- mately 12 lbs./sq.; in. Close fill'valve: ;-5; -. . .. ' 10. Open purge'valve.-1 boiler riser/ number \ Ori.)}f G-23 G-24; ' S-251. ) . G-26: )Gr2Z ;. G-28-. <. G-29' G--210 . ; G-211 3 3 3- ' 3': 3 - v. 3 -V 3,--3. 3' return (in.) 2 2 2 2 2 2 2 2 2 equalize^ iVz,7^: m?zpMm MM2M : 22 `: 2 Note 1: Where multiple, circuits are used without zone-- valves;;* square head `cocksr should be installed for balancirigJiJheseUit.'', square head cocks can be shut off to purge each circuit irf turff;^" Note 2:. For a single loop-Heatrim System, no additional: vehtsr-:r--.. cooncekseA,MxcAveAanplavtiteAoMsn,.;' dIIdfra4ta*innask1,/lIeaos*rs okhtnehiateitAreara1ics^ceBulsessAeo^dfneaesnnddarUHeeeeareftrrqiimmuijrS>ee/dar-wbuKbwAviSUth^r.-r;-*.^-;-'*)Z - the boiler outlet, a flow check valve must be installed.to preventt^ gravity^ circulatiorw ri||aj(atseP *eYe!I- ^ . n ; Fnrn Nh 7 1 fl.7 IQ wv W d I 7 It AMERICAN STANDARD PLUM Bl NC / H E AT I N G P.O. BOX 2003, NEW BRUNSWICK, N. J. 08903 J Lit ho in U.5.A.