Document G6r9m04bBoQwxyj7Vo3jQ4VVq

CONTROLS FOR ATM3SPHERIC CONTAMINATION Page 5 1. An exhausted hood covering two-thirds of the periphery of the storage container will maintain airborne lead at a safe limit in dry compounding. A minimum inward draft of 100 feet per minute across the top of the con tainer is required. 2. A bottom door or baffle on No.l mixer discharge in dry compounding will increase the inward draft or a 3-sided enclosure may be considered. 3. Side baffles on the exhausted transfer from blender to hammer mill will increase the inward draft. Provision of the baffle would not interfere with material flow. 4. Hopper charging on No.6 backing machine in the Rolling Department requires a partial cover to reduce the airborne lead contamination. Moreover, consideration should be given to enclose the feed chute. -- LIBERTY MUTUAL INSURANCE COMPANY SPNY 000374