Document G6jVM0yjLJO1wdMBD0nvZQOq
American Society of Heating and Ventilating Engineers Guide, 1937
The amount of infiltration that may be expected through simple walls used in farm and other shelter buildings, is shown in Fig. 2. The infil tration indicated in Figs. 1 and 2 is that determined in the laboratory and should be multiplied by the factor 0.80 to give proper working values. .
WINDOW LEAKAGE
The amount of infiltration for various types of windows is given in Table 2. The fit of double-hung wood windows is determined by crack and clearance as illustrated in Fig. 3. The length of the perimeter opening or crack for a double-hung window is equal to three times the width plus two times the height, or in other words, it is the outer sash perimeter length plus the meeting rail length. Values of leakage shown in Table 2 for the average double-hung wood window were determined by setting the average measured crack and clearance found in a field survey of a large number of windows on nine windows tested in the laboratory. In
Chapter 6--Air Leakage
Fig. 3. Diagram Illustrating Crack and Clearance
addition, the table gives figures for a poorly fitted window. All of the figures for double-hung wood windows are for the unlocked condition. Just how a window is closed, or fits when it is closed, has considerable influence on the; leakage. The leakage will be high if the sash are short, if the meeting rail members are warped, or if the frame and sash are not fitted squarely to each other. It is possible to have a window with approximately the average crack and clearance that will have a leakage at least double that of the figures shown. Values for the average doublehung wood window in Table 2 are considered to be easily obtainable figures provided the workmanship on the window is good. Should it be known that the windows under consideration are poorly fitted, the larger leakage values should be used. Locking a window generally decreases its leakage, but in some cases may push the meeting rail members apiart and increase the leakage. On windows with large clearances, locking will usually reduce the leakage.
Wood casement, windows may be assumed to have the same unit leakage as for the average double-hung wood window when properly fitted. Locking, a normal operation in the closing of this type of window, maintains the crack at a low value.
For metal pivoted sash, the length of crack is the total perimeter of the movable or ventilating sections. Frame leakage on steel windows may be
134
Fig. 4. Infiltration through Sash Perimeter of Window with and without Storm Sash--IHU-in. Crack and M2-IN. Clearance
neglected when they are properly grouted with cement mortar into brick work or concrete. When they are not properly sealed, the linear feet of sash section in contact with steel work at mullions should be figured at 25 per cent of the values for industrial pivoted windows as given in Table 2.
Leakage values for storm sash are given in Figs. 4 and 5. When storm
Fig. 5. Infiltration through Sash Perimeter of Window with and without Storm Sash--J^-in. Crack and J^-in. Clearance 135
'. 1