INTRODUCTION TO DIELECTRIC HEAT TRANSFER FLUIDS
O/FF-24
V
Monsanto
-- *tf
IS
0288620 TOWOLDMONOQ28461
INTRODUCTION TO DIELECTRIC HEAT TRANSFER FLUIDS
O/FF-24
"Nothing contained herein is to be construed is i recommendation lo use any product Inconflict with tny patent MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS OR MERCHANT ABILITY Of ANY PRODUCTS REFERRED TO, no guarantee ol utlslectory results Irom reliance upon conMined Information or recommendations, end dlsclaimsall liability for any resulting loss or damage." Organic Chemicals Division/800 N. Lindbergh Blvd./St. Louis, Missouri 63166
*568^1
TOWOLDMONOQ28462
Preface
The information in this booklet is intended as an introduction to the subject of dielectric heat transfer fluids. Additional information can be obtained from any of the several textbooks covering this subject matter. For heat transfer these would include:
Elements of Heat Transfer - - Jakob & Hawkins Heat Transmission -- W. H. McAdams Introduction to Heat Transfer -- Brown & Marco While the above textbooks contain some information on flow dynamics, more complete information on this subject is available from the following: Handbook of Fluid Dynamics -- V. L. Streeter Design of Hydraulic Control Systems -- Lewis & Stern Fluid Power and Control Systems -- E. C. Fitch, Jr. In addition, the various mechanical and chemical engineering hand books have sections devoted to heat transfer and fluid dynamics. In the following pages, reference is made to many of the physical properties of fluids such as viscosity, specific gravity, density, etc. For additional information on these properties and their method of measurement consult, "Introduction to Hydraulic Fluids" by R. E. Hatton or any of the engineering handbooks. The particular test method for each physical property determination is indicated in the Coolanol technical data bulletin. A complete descrip tion of most test methods can be found in the ASTM Standards Handbook (Part 29, Electrical Insulating Materials).
R. A. Steenrod September 1,1970
^ae^
TOWOLDMONOQ28463
Contents
Subject
Page
Functional Properties.............................................................................. Density.................................................................................................. Viscosity................................................................................................ Thermal Conductivity.......................................................................... Specific Heat.......................................................................................
6 6 6 6 6
Velocity................................................................................................. 7 Pumpability........................................................................................... 8 Pour Point........................................................................................... 9 Surface Tension................................................................................... 9 Coefficient of Thermal Expansion...................................................... 9 Dielectric Strength.............................................................................. 9 Dielectric Constant.............................................................................. 10 Volume Resistivity............................................................................... 10 Power Factor........................................................................................ 10
Operational Properties............................................................................ 10 Neutralization Number........................................................................ 10 Vapor Pressure..................................................................................... 11 Foaming............................................................................................... 11 Hydrolytic Stability.............................................................................. 11 Radiation Resistance........................................................................... 12 Thermal Stability.................................................................................. 12 Oxidative Stability............................................................................... 13 Corrosion............................................................................*........ * 13
Safety Properties..................................................................................... 13 Auto Ignition Temperature................................................................. 13 FlashPoint........................................................................................... 14 Fire Point.............................................................................................. 14 Flammability......................................................................................... 14 Toxicity................................................................................................. 14
Units of Measurement and Conversion Factors................................................................................. 15
Heat Transfer Calculation....................................................................... 16
Pressure Drop Calculation...................................................................... 18
Pumping Power....................................................................................... 18
0238823
TOWOLDMONOQ28464
Q(
INTRODUCTION TO DIELECTRIC HEAT TRANSFER FLUIDS
Dielectric heat transfer fluids are similar to conventional heat transfer fluids with the added capability of operating in direct contact with the electrical circuit. Their major application is in airborne military electronic apparatus where, for technical reasons, water and air are not satisfactory (water because of its low boiling point, high freezing point and corrosiveness -- air because of its poor heat transfer capability). Selection of a particular dielectric heat transfer fluid involves considera tion of the many technical parameters related to the product. As a matter of convenience, these have been divided into three main categories:
FUNCTIONAL (heat transfer, pumpability and dielectric properties)
OPERATIONAL (materials compatibility and service life)
SAFETY (flammability and toxicity).
In the FUNCTIONAL category, the following properties are included:
Density Pour point Viscosity Thermal conductivity Specific heat Surface tension Coefficient of expansion Dielectric strength Dielectric constant Volume resistivity Power factor Lubricity
Under OPERATIONAL the following:
Neutralization number Vapor pressure Foaming Hydrolytic stability Radiation resistance
Water content Thermal stability Oxidative stability Corrosion
Under SAFETY, are included:
Auto Ignition temperature Flash point
Fire point Toxicity
(
4
025882''
TOWOLDMONOQ28465
HEAT TRANSFER
The major function of a dielectric heat transfer fluid is to transfer heat. The amount of heat transferred can be calculated from the expression:
Q = U A A Tj = M CP A T2
(EQUATION I)
Where:
Q = Heat flow U = Overall heat transfer coefficient A = Area of heat transfer surface A Tj -- Temperature difference between surface and fluid M = Hate of mass flow Cj. = Specific heat of fluid AT2 = Temperature change of fluid
Of major interest is the overall heat transfer coefficient, U, which determines the effectiveness of the fluid in the system. U, is composed of many factors including the very important one of film heat transfer coefficient, h. In many forced convection systems, h, is a controlling factor of the amount of heat that is transferred. Thus, an understanding of h, and its calculation is important. Many equations are available for the calculation of h, (depending upon the nature of the fluid and the system). For purposes of illustration, the following equation has been selected. It is an average expression for a low viscosity fluid in a turbulent, forced convection system for both heating and cooling. It is quite probable that this equation would not be correct for all situations. Thus judgment is required for the selection of the correct equation for a particular design problem.
h = ^ 0.0223
(^)" (EQUATION II)
Where:
h = Heat transfer coefficient D = Diameter p = Density V = Velocity p - Viscosity Cp = Specific heat K - Thermal conductivity
(The greater h, the greater the heat transfer capability of the fluid.)
The following is a discussion of the contribution of the functional properties to the heat transfer capability.
0^588^5 5
TOWOLDMONOQ28466
D
Functional Properties DENSITY Density is the ratio of mass to volume and is an indication of the amount of matter contained in a specific volume of material. Since heat transfer involves the collision of molecules, it would seem logical that the more molecules available in a specific volume, the more heat transferred. This is the case; and is so expressed by Equation II in which heat transfer varies directly with the density. Thus, the greater the density the greater the heat transferred by the fluid.
VISCOSITY Viscosity is a measurement of the resistance to flow of a particular material. Since heat is transferred through the flow of material it would appear that the greater the viscosity or resistance to flow the less heat that would be transferred. This is borne out as indicated by the reciprocal nature of heat transfer to viscosity in Equation II. Thus, the lower the viscosity the more heat transferred. Viscosity is a most important property of a fluid. Viscosity usually changes more with temperature than any other physical property of a liquid. Thus, a consideration of the viscosity at the particular operating temperature of the liquid is necessary. For example: High viscosity usually limits the low temperature capability for a particular liquid. (This fact is the primary reason for the lower viscosity fluids in the Coolanol fluids product line.) Viscosity, and the variation of viscosity with temperature, will vary widely with different types of liquids. The Coolanol fluids have ex cellent viscosity temperature characteristics and function well down to extremely low temperatures.
THERMAL CONDUCTIVITY Thermal conductivity is an indication of the capability of matter to transfer heat by conduction. Thus, the greater the thermal conduc tivity the greater the heat transfer capability. There is not a wide variation in thermal conductivity between dif ferent types of organic liquids nor within any particular class of organic liquid. For example, all of the Coolanol fluids have about the same thermal conductivity. Thus, this property is of lesser im portance in determining the heat transfer capability of a particular fluid. The Coolanol fluids do possess good thermal conductivity.
SPECIFIC HEAT Specific heat is an indication of the amount of heat required to change the temperature of a material. Thus, specific heat is an indication of
oz^azb
6 TOWOLDMONOQ28467
the ability of a substance to store heat. As indicated by Equation II, the greater the specific heat the greater the heat transfer capability of the material. Specific heat, like thermal conductivity does not vary greatly from class to class or within the class itself. For example; the specific heat of all of the Coolanol fluids is about the same rela tively high value of 0.45.
VELOCITY
While velocity is not a physical property of a fluid, it should be noted that the velocity of the fluid in the system is of prime importance in determining its heat transfer capability. For maximum heat transfer, the first consideration is that the velocity be great enough to insure turbulent flow in the system. Then once turbulent flow is established, the greater the velocity the greater the heat transfer capability of the fluid.
Of course, penalties are involved in creating high velocity in the fluid. The first of these is that more pumping power is required as the velocity increases. The second is that the pressure in the system must increase as the velocity increases. This aspect will be discussed in greater detail in the section concerned with pumpability.
In summary, regarding heat transfer capability in convection systems, the single most important physical property is the viscosity of the fluid. This is illustrated in the following table for heat transfer coeffi cient at 100F for the various Coolanol fluids:
h, (heat transfer coefficient), BTU/hr. Ft.2F.
Fluid
Coolanol 45 Coolanol 40 Coolanol 35 Coolanol 25 Coolanol 20 Coolanol 15
h, at 100F.
210 270 270 340 440 460
Viscosity, cs @ 100f\
14 6.5 6.5 4.2 2.0 1.6
(This heat transfer coefficient is for forced convection, turbulent flow (Reynold's Number greater than 2300) for a flow rate of 10 gallons per minute in one half inch smooth tubing.)
This table illustrates the dependence of heat transfer capability on viscosity; for the thermal conductivity, density and heat capacity are about the same for all of the Coolanol fluids and the only significant variable is the viscosity. However, just the variation in viscosity produces a difference of over 100% in heat transfer capability of the various fluids.
0258827
7
TOWOLDMONOQ28468
PUMPABILITY
Pumpability is primarily concerned with the amount of power required to circulate the fluid through the system. This is dependent upon the quantity of the fluid, the pressure losses created by flow of fluid through the system and lubricating qualities of the fluid. In the functional category, our main concern is with the power required to circulate the fluid. The following equation relates pumping power to fluid and system parameters.
Pw = A P x Ac x V
(Equation III)
For turbulent flow: AP
And:
4f -- iXl D 2 gc
(Equation IV)
f = 0.08
(Equation V)
Thus: Power (Pw) is a function of density (p) and viscosity (m).
Where: Pw = Power
A P = Pressure drop f = Friction factor L = Length p = Density Ac = Area of cross section V = Velocity gc = Gravitational constant D = Diameter
Excepting the system parameters, it can be seen that pumping power is related to the pressure drop and the flow volume of the fluid. Further more, the pressure drop is directly dependent on the viscosity and the density; that is, the higher the viscosity and density, the more pumping power required.
The following is a brief discussion of the relationship of the functional properties to both the heat transfer capability and pumpability of the fluid.
DENSITY High density is desirable from the heat transfer viewpoint but may be undesirable in regards to pumping power. Thus a tradeoff may be involved; and each system must be analyzed in order to determine the desirable density for the fluid. If the prime consideration is heat transfer capability and adequate pumping power is available, then a high density fluid would be desirable. If pumping power is limited, as it may be in an aerospace application, then a less dense fluid may be more beneficial.
#
0258828
TOWOLDMONOQ28469
POUR POINT Pour point is directly related to the low temperature capability of the system. In most applications, it is undesirable to allow the fluid to freeze; and the pour point would represent the absolute minimum temperature capability of the fluid.
VISCOSITY Low viscosity is desirable from both the heat transfer and pumpability viewpoint. That is, the lower the viscosity the greater the heat transfer capability and the less pumping power required. However, lubricity may be adversely affected by low viscosity. In many instances, lubricity is inversely related to the viscosity so that as the viscosity decreases the lubricating qualities of the fluid tend to decrease also.
In most dielectric heat transfer systems, the lubricating requirements of the pump and components are modest and only minor consideration need be given to the lubricating qualities of the fluid. (The most com monly used heat transfer liquid is water, which is a poor lubricant but is still successfully used in many systems.) Lubricity is a complex function and cannot be easily related to fluid properties. Instead, bench and performance type tests are used to describe the lubrication qualities of a fluid. The Coolanols are considered to be good lubricants and should present no lubricity problems for most systems.
SURFACE TENSION Surface tension is a fundamental property of a liquid and is related to its molecular structure. It is the tendency of the molecules of a liquid to draw together at the surface to form the smallest area possible. Surface tension is related to many aspects of fluid performance (lubric ity, leakage, heat transfer, etc.) but theory has not been refined to the point where simple equations are available to quantify the relationship of surface tension to fluid performance. Both high and low surface tension fluids are used successfully in heat transfer applications and there does not appear to be an overwhelming advantage to either. The Coolanol fluids possess low surface tension.
COEFFICIENT OF THERMAL EXPANSION The coefficient of thermal expansion is a measurement of the change of volume of a material with temperature. This property usually dictates the reservoir size for a particular system since, as the temperature of the fluid increases, its volume will also increase. Thus, allowance must be made in the system reservoir to accommodate the increased volume of the fluid at elevated temperatures. Since increased size and weight of the reservoir is required to accommodate the thermal expansion of the fluid, it is therefore desirable to utilize fluids with low thermal expansion coefficients.
DIELECTRIC STRENGTH Dielectric strength is a measure of the ability of the fluid to withstand voltage stress and the higher the dielectric strength, the higher the
02 58829
TOWOLDMONOQ28470
voltage that can be impressed upon the fluid. In a dielectric heat trans fer fluid, high dielectric strength is desirable and is usually the electrical property of greatest interest to the design engineer. It should be noted that the dielectric strength of a liquid is usually quite dependent upon contaminants present in the liquid such as water or entrained air or gas. Water will have a deleterious effect upon di electric strength particularly if ionizable impurities are present in the liquid for the water will allow these impurities to ionize and be affected by the electrical field. Gas bubbles will also degrade the dielectric strength of a liquid pri marily because the dielectric strength of a gas is so much lower than for a liquid. The Coolanol fluids do have high dielectric strength and because of their chemical nature are quite exceptional in their toleration of water.
DIELECTRIC CONSTANT Dielectric constant is a measure of the ability of the liquid to store electrical energy. This property is usually not of interest in dielectric heat transfer applications. The Coolanol fluids have relatively low dielectric constants.
VOLUME RESISTIVITY This property describes the ability of the liquid to act as an insulator. If a fluid has very low volume resistivity it would be a conductor of electricity and not suitable for dielectric heat transfer applications. However, relatively low volume resistivity can be tolerated in most dielectric heat transfer applications. In most cases, the only result of the low volume resistivity is a slight additional heating of the liquid. The design engineer is usually not too interested in volume resistivity. His main concern is with dielectric strength and if the dielectric strength is adequate then the volume resistivity would usually also be adequate for the application. The Coolanol fluids have high volume resistivities and are good electrical insulators.
POWER FACTOR This property is a measurement of electrical loss in the liquid. As the power factor increases, the electrical losses also increase; the net result being a heating of the liquid. In most instances, power factor is not of concern in dielectric heat transfer applications.
OPERATIONAL PROPERTIES The second category, operational properties, is concerned with ma terials compatibility and service life of a fluid and system. The following is a brief discussion of the importance of various operational fluid properties on the performance of the fluid.
NEUTRALIZATION NUMBER This number is an indication of the acid or base content of the system, the higher the number, the more acid or base in the system. This
0258830
I
TOWOLDMONOQ28471
number is obtained by titrating a sample of the fluid with a standard acid or base solution and noting the amount of acid or base required for neutralization. Thus the neutralization number can be either acidic or basic. When acid it is often referred to as the acid number or when basic, the base number. The acid content of the fluid usually increases with use due to thermal, oxidative and hydrolytic breakdown of the fluid. A high neutralization (acid) number is undesirable because it would indicate high acid content, which could lead to metal corrosion in the system and/or loss of dielectric strength in the liquid.
VAPOR PRESSURE Vapor pressure is a measurement of the tendency of a liquid to evap orate. It also indicates the boiling point of the fluid (which is the temperature at which the pressure of the vapor equals the pressure of the atmosphere in contact with it). High vapor pressure indicates that the fluid would evaporate rapidly if exposed to the atmosphere. It would also indicate that boiling could take place at relatively low temperatures. This boiling could be undesirable in many liquid phase heat transfer systems. Also, high vapor pressure could tend to promote cavitation of pumps. Thus, in liquid-phase systems low vapor pressure fluids, such as the Coolanol fluids, are desirable.
FOAMING Foaming is an indication of the tendency of a liquid to entrain or encapsulate air or gas present in the system. Foam generation is undesirable because it degrades both the heat transfer capability and pumpability of the liquid; and excessive foaming could lead to damage of the pump in the system. It should be noted that the presence of a gas or vapor is necessary for foam generation. Thus, if the liquid is gas and vapor free or if conditions in the system are such that all of the gas will remain in solution, then foaming will not occur. Foam generation is undesirable in the system. The Coolanol fluids are low foaming liquids and should present no problems in most systems. Where foaming is a problem, thorough degassing of the fluid should be considered.
HYDROLYTIC STABILITY Hydrolysis is the chemical reaction of the fluid with water. Hydrolysis could be harmful -- or beneficial -- depending upon the nature of the products of hydrolysis. If acid were formed, then hydrolysis would be detrimental to the fluid and system. On the other hand, hydrolysis could be a desirable reaction if it re moved water from the system and no harmful reaction products were generated for removal of the water would help maintain the dielectric strength of the liquid and system. This is the case with the Coolanol fluids.
TOWOLDMONOQ28472
The Coolanol fluids are formulated silicate esters and hydrolysis of a silicate ester produces alcohol and a silicon containing polymer. Fortunately, both these reaction products have good dielectric strength. Thus, a silicate ester has the ability to consume water in the system and in doing so, maintain the good dielectric strength of the fluid.
Among all common dielectric fluids, this behavior is unique to the silicate esters. With most dielectric fluids, water has a very adverse effect on the dielectric strength of the liquid. For example: BO PPM of water in a transformer oil or in askarel is sufficient to reduce the dielectric strength from a dry-fluid value of 50,000 volts to less than 5,000 volts (per a 100 mil gap).
Thus, great care must be taken with other dielectric fluids to minimize their contamination with water. If these fluids are contaminated with water, then processing is required to remove the excess water.
With the silicate esters, this great care and concern is not necessary for they tend to heal themselves when exposed to contamination by water. Likewise, they will tend to dry other materials in the system such as paper or plastic insulation. This behavior is quite beneficial in the maintenance of dielectric strength in the liquid and system.
RADIATION RESISTANCE Radiation resistance is the ability of the fluid to withstand high frequency radiation. The source of radiation could be nuclear, or a high power transmitting tube. (Many transmitting tubes - and even some receiving tubes such as rectifiers in color TV sets - emit X-ray and other types of radiation.)
The behavior of a fluid under radiation is quite similar to its behavior under thermal stress. Thus a fluid that can withstand high tempera ture can usually withstand higher levels of radiation also.
Radiation resistance is usually not of great concern in most dielectric heat transfer applications. It may be where high power transmitting tubes are involved. In that case, high radiation resistance in the liquid would be desirable. The Coolanol fluids possess good radiation resistance.
THERMAL STABILITY This property is an indication of the ability of the liquid to withstand heat in an oxygen-free environment. Fluids with poor thermal stability would break down rapidly at high temperature leading to the formation of volatile material, gels, and possibly acid. Good thermal stability is desirable in a dielectric heat transfer fluid.
There are many tests in existence used to measure the thermal stability of a liquid and judgment is required in applying the results of any particular test to a particular application for the product. The Coolanol fluids have excellent thermal stability.
TOWOLDMONOQ28473
OXIDATIVE STABILITY Oxidative stability is a measure of the ability of the fluid to withstand heat in the presence of air (oxygen). Jt differs from the thermal sta bility in that the fluid is kept saturated with air at all times so that abundant oxygen is available for the oxidation of fluid. Poor oxidative stability could lead to the rapid formation of sludge and acid in the fluid.
Good oxidative stability is desirable, but it is usually possible to design around poor oxidative stability in most dielectric heat transfer applica tions. A common means is to enclose the system and prevent entrance of air. In extreme cases, it may be necessary to evacuate the air from the liquid and operate the liquid in an inert environment.
Again, there are many tests in use to measure the oxidative stability of a liquid. Judgment is required to relate the results of a particular oxidative stability test to an individual application. The Coolanol fluids have good oxidative stability.
CORROSION Corrosion is a measure of the affect of a liquid on various metals that might be in a system. Corrosion is usually measured in conjunction with the thermal or oxidative stability of the fluid. Corrosion is directly related to the rate, amount and type of acid formed in the liquid under thermal or other stress. Corrosion is usually undesirable in the system as it may interfer with heat transfer. It could also lead to wear and deterioration of the metal components in the system. There are a number of tests used to measure corrosion and judgement is required in the application of test results to a particular system.
The Coolanol fluids are essentially non-corrosive.
SAFETY PROPERTIES The last category is the safety characteristics of the product, par ticularly its flammability and toxicity. It is desirable to have a product with low flammability and a low order of toxicity. The properties usually selected to judge these characteristics are the auto-ignition temperature, the flash point, the fire point, and the toxicity of the product. A brief discussion of each follows:
AUTO IGNITION TEMPERATURE The auto ignition temperature (AIT) (sometimes referred to as the autogeneous ignition temperature; and also as the spontaneous ignition temperature (S.l.T.)) is the temperature at which the liquid will ignite in the presence of air, but in the absence of an ignition source such as a spark or flame. It is used to indicate the behavior of the liquid coming in contact with a hot surface. The AIT is usually considerably higher than the flash and fire points of the fluid. A high AIT is desirable and the Coolanol fluids do have relatively high AlT's. It should be noted that the AIT depends upon the test method used. The AIT
13
TOWOLDMONOQ28474
does not represent the minimum temperature at which combustion would take place in the absence of an ignition source. Under certain conditions combustion may occur below the AIT for the fluid.
FLASH POINT The flash point is the temperature at which the liquid will just begin to ignite in the presence of air and a flame. A high flash point is desirable.
FIRE POINT The fire point 'is the temperature at which the liquid will ignite and continue to burn in the presence of air and an ignition source, such as an open flame. A high fire point is desirable. The Coolanol fluids have relatively high flash and fire points.
FLAMMABILITY There have been many tests developed to measure the flammability characteristics of fire resistant fluids. These include the high pressure spray, the low pressure spray, and the hot manifold test. Our currently available Coolanol dielectric heat transfer fluids are not considered fire resistant fluids and thus the special flammability tests are not run. Instead, the flammability of these liquids is judged by reference to the AIT, flash and fire points of the liquid. This type of judgement is quite valid for flammable liquids, but could be quite misleading in regards to fire resistant liquids. For additional information, consult the booklet, "A review of Fire Resistant Test Methods for Aircraft Hydraulic Fluids".
TOXICITY There are numerous tests in use to judge the toxicity of a product. Of particular concern is the effect of a product in contact with the skin or eyes or when eaten or inhaled. Judgements on effects of this type are usually based upon test results with laboratory animals. This includes contact of the liquid with the skin and eyes of rabbits; ingestion and inhalation by rats and mice. In some cases, human agents are used for the skin contact work. Another characteristic sometimes considered in the safety category is the noxicity of the product. Noxicity refers to any unpleasantness associated with the use of the product -- bad odor (such as a fishy smell); eye watering (such as onion juice, for example); unpleasant feel to the skin, etc. Noxious characteristics do not necessarily indicate toxic characteristics of the product for it is possible for a product to be noxious without being toxic (for example, the taste and odor of fish
TOWOLDMONOQ28475
is noxious to many, but, nevertheless, the fish is not toxic). It is desirable for products to have a low degree of noxicity, that is, to b^ as pleasant as possible to work with.
The Coolanol fluids are not noxious and have a low order of toxicity.
PHYSICAL PROPERTIES AND UNITS OF MEASUREMENT In regards to the calculations for heat transfer coefficient and pressure drop, it is quite important that consistent units of measurement be used throughout; that is, either all metric units or all English units. This requires extreme care in the selection of data -- for physical properties are quoted in Metric and English units and sometimes in a hybrid system using features of both the English and Metric system.
The most generally used physical properties are listed in the table below in Metric units along with factors necessary to convert them into the English system.
Symbol h
Properly
Heat transfer coefficient
Metric Units cal/sec. C cm*
Conversion Factor (Metric x factor) - English Units
7373 BTU/HRT Ft.*
D
Diameter
cm.
0.0328
K Thermal
conductivity
ca!-cm/sec cm* C 242
Cp Heat Capacity cal/gm C
1
Ft.
BTU-Ft./HR. Ft*. F
BTU/lbm F
A
A AT L P V
Absolute viscosity Area Temperature Length Density Velocity
gm/cm. sec. (poise) cm* C cm gm/cm* cm/sec
242 0.00108 1.8 0.0328
62.43 118.1
lb//Ft. HR. Ft*. F Ft. Ibm/Ft* Ft./HR.
P Pressure dyne/cm*
1.45 x 10-* Ib//in*
g Gravitational
constant
1
- 32.2 M!; lb/ sec*
lbm = Pounds of mass
lbf = Pounds of force
It should be noted that the viscosity used in these calculations is the absolute viscosity (poise or centipoise) not the kinematic viscosity (stokes or centistokes) we normally deal with. In the metric system, the absolute viscosity is obtained by multiplying the kinematic viscosity by the density; that is: cp = cs x p.
0258835
\
15
TOWOLDMONOQ28476
HEAT TRANSFER CALCULATIONS (Formula taken from: Elements of Heat Transfer, Jakob & Hawkins)
As mentioned previously, in dielectric heat transfer applications the purpose of the fluid is usually to transport heat from a source (load) to a sink (radiator) in order to cool the source (usually a transmitting tube) and keep it from overheating.
The amount of heat is normally related to time and expressed as heat flow (represented by the symbol, Q). Typical units are BTU/hour. As mentioned previously, Q = U A A T; and an important part of the overall heat transfer coefficient, U, is the film heat transfer coefficient, h.
Usually Q is known (so much heat must be removed in order for the apparatus to work properly) and the U, A and AT must be adjusted to accommodate Q.
U, (and h,) is dependent on the nature of the heat transfer fluid, the pumping rate, the geometry of the system and other factors.
A is dependent on the geometry of the system.
AT is dependent on the heat source, the fluid; and the materials of construction of the system.
Very often, h, can be adjusted to obtain the necessary heat transfer and h, can be calculated through use of the many equations that have been developed for various fluids and systems. The typical equation for h, we are using is:
Where: h = Film heat transfer coefficient, BTU/hr. Ft.2F K = Thermal conductivity, BTU/hr. Ft. F D = Diameter, Ft. p - Density, lb./Ft.8 V -= Velocity, Ft/hr. n *= Absolute Viscosity,lb/hr Ft. Cp = Specific heat, BTU/lbF
The expression
er.
#
0*58836
TOWOLDMONOQ28477
This equation is recommended for turbulent flow (Reynold's Number greater than 2300) low viscosity fluids and is an average expression for both heating and cooling.
A typical example follows:
Fluid:
Coolanol 25
Temperature: 100F
Flow Rate:
10 GPM
Tubing size:
1 inch
Find k
From Coolanol 25 Technical Data Bulletin:
K 0.075 BTU/hr Ft. F (31.2 x 10-5 cal/c cm. sec x 242)
p 55.6 )b/Ft.s (.891 x 62.43)
p 4.2 cs x .891 X 2.42 = 9.0 Ib/hr ft
cp 0.45 BTU/lb F
10 gal. x 60 min. Ft.'
V
10 GPM = Min.
14600 ft/hr hr 7.481 gal .00547 Ft.!
0.075 0.0223 /55.6 x 14600 x .083V8 /0.45 x 9.0YS
h .083
\
9.0
) \ .075 /
h 94 BTU/hr ft2 F
Assume: Q = 100,000 BTU/hr A = 20 ft!
h =U
Find: A T Q = U A A T = 100000 = 94 x 20 x A T
A T = 53F
The second factor of importance to the design engineer is the pressure differentia] required to produce the desired flow rate. Pressure differ entia! (A P) is important because pump size, pumping power and system integrity are all a function of it.
The greater the A P the larger the pump and the greater the pumping power required. Also tubing and components are designed for a maximum A P; and if this rating is exceeded they may rupture from the high pressure.
0258837
Thus it is necessary to calculate the A P for the system. Again, many equations are available -- depending upon the fluid and the geometry of the system. A typical equation for pressure drop in tubing for a low viscosity fluid in turbulent flow (Reynold's number greater than 2300) is shown below. (This pressure drop is not the total pressure drop for the system. Other losses in the system, such as losses in fittings, would have to be considered in order to arrive at the total pressure drop.)
4 L pVi* AP 144 1 D 2gc
Where:
f = Friction Factor =
0.08
A P = Pressure drop, lb/in5 L = Length, ft.
Vi = Velocity, ft/sec.
gc _ 32.2 lb' mass {L lb. force sec.!
Assume:
Conditions same as for calculation of h.
L = 1 ft.
14600 ft V, =
hr 3600
hr 4.05 ft/sec
AP per foot)
4 .08 144 (55..6 x 14600 x ,083\
1 55.6 (4.05)B .083 2 x 32.2
A P/ft = .041 lb/in1
Assume 75 ft. of tubing: A P = .041 X 75 = 3.1 lb/in2
Pumping power would be:
Plow (GPM) X AP 1714
10 X 3.1 = 1714
HP X .018 Horse Power
f) (
025B838
TOWOLDMONOQ28479
Index
Subject
Page
Auto Ignition Temperature..................................................................... 13 Conversion Factors................................................................................. 15
Corrosion.................................................................................................. 13
Density..................................................................................................... 8 Dielectric Constant.................................................................................. 10
Dielectric Strength.................................................................................. 9
Fire Point.................................................................................................. 14 Flammability............................................................................................. 14 Flashpoint............................................................................................... 14
Foaming................................................................................................... 11 Functional Properties.............................................................................. 6
Heat Transfer Calculations..................................................................... 16 Hydrolytic Stability.................................................................................. 11
Neutralization Number............................................................................ 10 Operational Properties............................................................................ 10 Oxidative Stability................................................................................... 13
Pour Point................................................................................................ 9
Power Factor........................................................................................... 10
Pressure Drop Calculations.................................................................... 18
Pumpability.............................................................................................. 8
Pumping Power..................................
18
Radiation Resistance.............................................................................. 12
Safety Properties..................................................................................... 13
Specific Heat........................................................................................... 6
Surface Tension....................................................................................... 9
Thermal Conductivity.............................................................................. 6
Thermal Expansion.................................................................................. 9
Thermal Stability. . . . ............................................................................ 12
Toxicity..................................................................................................... 14
Units of Measurement............................................................................ 15
Vapor Pressure......................................................................................... 11
Velocity.................................................................................................... 7
Viscosity..................................................................................................6 & 9
Volume Resistivity................................................................................... 10
0258839
19
TOWOLDMONOQ28480
Additieeel District Offices
DISTRICT SALES OFFICES ALLDIVISIONS ; ere meleteieed by:
AKRON, OHIO 44313
260 Sprlngslde Drive Montrose Development Perk Tet. (216) 666*4111
ATLANTA, GEORGIA 30326
Lenox Towers Best 3400 Peechtree Pd. N. B. -- Suite 1711 Tel. (404) 577-2260
BOSTON, MASSACHUSETTS 02149 Bverett Stelion Tef. (617) 387-5010
CHICAGO, ILLINOIS 3158 Des P/elnes Ave. Des P/elnes, Illinois 60018 Tet. (312) 296-6688
\
Agricultural Division ALLENTOWN, PENNSYLVANIA 18104
J
Park Professional Building 2200 Hamilton Straat
Tal. (215) 437-5471
DECATUR, ILLINOIS 62623 207 Dacatur Professional Building
\ 363 South Main Straat
Tat. (217) 423-6031
J DES MOINES, IOWA 60310
J
312 Marla Hay Towar Tat. (616) 276-6603
FREMONT, NEBRASKA 68026
160 South Main Straat
S Tal. (402) 727-1230
J INDIANAPOLIS. INDIANA 46206
Suita 216,4002 Meadows Drive Building Tat. (317) 547-9148
KANSAS CITY, MISSOURI 64133
701 Blue Ridga Towar 4240 Blue Ridge Boulevard Tal. (816) 353-8060 * LULING, LOUISIANA 70070
P. 0. Box 174 Tal. (504) 784-6263
CINCINNATI, OHIO 45206 1501 Medlson Poed Tel. (513) 751-6707
DETROIT, MICHIGAN 600 North/end Towers West Southfield. Mich. 48075 Tel. (313) 357-0910
HONOLULU, HAWAII 96612 205 Pacific tnternetionef Bldg. 677 Ate Moene Btvd., P. 0. Box 3824 Tel. (808) 531-2744
HOUSTON, TEXAS 77027
MANKATO, MINNESOTA 66001 111 Madison East Tat. (507) 387-3406
\ MEMPHIS. TENNESSEE 38104 303 Union Plaza Building
: 1835 Union Avenue Tal. (901) 278-7811
* MUSCATINE, IOWA 62761
l
P. 0. Box 473 Tal. (319) 263-1331
Hydrocarbon* A Potymor* Divitloi
l
NEW ENGLAND AREA 730 Worcester St
* Indian Orchard, Mas*. 01051
Tel. (413) 788-6911 J Lion Oil
EL DORADO, ARKANSAS 71730
Uon Oil Building
J Tat. (601) 863-3111
1301 Post Oek Tower 505/ Westhelmer Poed Tel. (713) 621-9550
LOS ANGELES, CALIFORNIA 90022 6670 B. Flotilla St Tel. (213) 723-2492
JACKSON. MISSISSIPPI 39209
* l
P. 0. Box 10937, Westland Station Tet. (601) 362-3648
N. LITTLE ROCK, ARKANSAS 72119
410 West 8th Street P. 0. Box 6821
l Tal. (501) 376-2437
l
MEMPHIS, TENNESSEE 38113 1023 Riverside Drive, P. 0. Box 13248
Tal. (901) 948-4451
NEW YORK, NEW YORK 10017 277 Perk Avenue Tel. (212)922-4111
ST. LOUIS, MISSOURI 63166 800 N. Lindbergh Blvd. Tel. (314) 694-1000
j
Plastic Products A Rosins Division EUGENE, OREGON 97402
*
855 Seneca Road Tel. (503) 342-7201
J KENILWORTH, NEW JERSEY 07033
North Seventh St. & Monroe Ave.
\ Tet. (201) 276-2900
I
SPRINGFIELD, MASS. 01101 P.O. Box 2130,
Tel. (413) 788-6911
SAN FRANCISCO BAY AREA
2710 Lafayette, Sente Clere, Cellt. 95052 Tel. (408) 243-0414
j Taxtilos Division ATLANTA, GEORGIA 30303
* Atlanta Merchandise Mart
*
240 Peachtree St., N. W. Tel. (404) 577-2260
SEATTLE, WASHINGTON 98121 2112 Third Avenue Tel. (206) 622-4203
WILMINGTON, DELAWARE 19603 2005 Concord Pike, Fairfax Tel. (302) 658-6531
CHARLOTTE, NORTH CAROLINA 28210 J 6230 Falrview Road, Suita 400
* Tel. (704) 364-0110
GREENVILLE, SOUTH CAROLINA 29606 McAlister Plaza
P. 0. Box 6564, Station B
Tel. (803) 239-9171
* l
NEW YORK, NEW YORK 10001 350 Fifth Ave. Tet. (212) 666-51C0
MONSANTO, 800 N. LINDBERGH BLVD.. ST. LOOIS, MISSOURI 83168
\-------------- -----------------------------
3/70 ^
0258840
f
2-3102 0970 6 IITHO IN U.S.A.
TOWOLDMONOQ28481
Monsanto 800 N. UNOBERGH BLVD., ST. LOUIS. MISSOURI 63166
TOWOLDMONOQ28482