Document G5kL98pQ4erLVeo2gVwaZQbvq
Heating Systems Bou
McDonnell & Miller, Inc.
Safety Devices for Steam and Hot Water Heating Boilers . . . Liquid Level Controls 3500 North Spaulding Ave., Chicago 18, Illinois
The McDonnell line consists of (1) boiler water feeders, low water fuel cut offs and combined feeders and cut-offs for low pressure steam boilers of all sizes and types, hand-fired or automatically fired; (2) pump controls, low water fuel cut-offs and low water alarms for steam boilers of any size or type with pressures ujp to 150 lbs; (3) safety relief valves (Btu-rated) for hot water heating boilers and domestic hot water heaters; boiler
water feeders and low water fuel cut-offs for hot water heating boilers; (4) make
up water feeders for receiving tanks and other liquid level controls for special
applications; (5) water level controls for humidity pans of warm air furnaces!,
. The selection of controls for usual applications is shown in the following service recommendation. Most of these
products are described in the following three pages.
Boiler Size
Service Recommendations
(1) STEAM BOILERS
Maximum Steam Pressure
McDonnell product to use
HAND FIRED JOBS
Up to 5000 sq ft
25 lbs
No. 47 Boiler Water Feeder
Above 5000 sq ft
35 lbs
No. 51 Boiler Water Feeder
Any size
75 lbs
No. 53 Boiler Water Feeder
AUTOMATICALLY FIRED JOBS
Boiler Water Feeder--Low Water Cut-off .Combinations
Up to 5000 sq ft
25 lbs
No. 47-2 Feeder Cut-off Combination
Up to 5000 sq ft
20 lbs
No. 67-101 Electric Cut-off Combination
Above 5000 sq ft
35 lbs
No. 51-2 Feeder Cut-off Combination
Any size
75 lbs
No. 53-2 Feeder Cut-off Combination
LOW WATER FUEL CUT-OFFS
Any size
20 lbs
No. 67 Low Water Fuel Cut-off
Any size Any size
50 lbs (Steam or water)
150 lbs
No. 63 Low Water Fuel Cut-off \ No. 150 Low Water Fuel Cut-off
(Industrial or Process boilers--Specific recommendations on receipt of complete data.)
(2> HOT WATER HEATING BOILERS
No. 33 Safety Relief Valve, for boilers up to 242,900 Btu per hour gross output;, open-
ing pressure 30 lbs.
___________________
(3) DOMESTIC HOT WATER TANKS AND HEATERS
Opening Pressure
Btu per Hour Capacity
McDonnell Product to use
45 pounds 75 pounds 100 pounds 125 pounds 150 pounds
321,300 308,700 423,900
513,900 605,700
No. 3345 Safety Relief Valve No. 3375 Safety Relief Valve No. 33100 Safety Relief Valve No. 33125 Safety Relief Valve No. 33150 Safety Relief Valve
1362
McDonnell & Miller, Inc.
Heating Systems Safety Devices
Boiler water ^feeders, feeder-cut-off combinations, and low water cut-offs . . . for low and moderate pressure steam boilers
McDonndl No. 47-S for heating boilers under 6000 eg *1 capacity. Maximum steam pressure, tS lbs.
McDonnell No. 61-t for heating boilers over 6000 sq ft capacity. Maximum steam pressure, 56 lbs.
McDonnell No. 47-2, shown installed
above, maintains a safe water level in boiler by feeding water whenever neces
sary. if emergencies such as priming or foaming permit water to fall to i in. in gauge glass, cut-off switch cuts cur rent to burner until emergency has passed. Has "Quick-Hook-Up" for fast,
accurate installation right in gauge glass tappings; "cool" feed valve; extra-deep sediment chamber; ASME-approved blow-off valve. Also available for hand fired boilers without No. 2 switch, as
No. 47 Feeder.
McDonnell No. 51-2, shown installed above, is same as No. 47-2 described at left, except it has greater feeding capac ity for larger boilers, and is installed with 1 in. equalizing pipes instead of "Quick-Hook-Up." Also available for hand fired boilers without No. 2 switch, as No. 51 Feeder.
For boilers operating at higher pressures, from 35 to 75 lbs, use McDonnell No. 53-2 (or No. 53, without switch.)
McDonnell No. 67 Low Water Cut-off For automatically fired steam boilers of any size
Maximum steam pressure, 20 lbs.
Has the McDonnell "Quick-Hook-Up" for quick, easy and trouble-proof installation in gauge glass tappings; deep sediment chamber with large quick-opening blow-off; packless, non-binding construction; adjustable terminal
box to make wiring neat and easy; dependable snap-action twin switches. One switch can be used to sound low water alarm, or control McDonnell No. 101 Electric Water Feeder described below. Second switch cuts current to
burner if water level drops to \ in. in gauge glass.
McDonnell No. 101 Electric Boiler Water Feeder For boilers up to 5000 sq ft capacity
For use with No. 67 Low Water Cut-off or with McDonnell "built-in" Low Water Cut-offs which are standard equipment on many modern heating boilers. It converts the cut-off into a feeder cut-off combination as described, at top of this page.
1363