Document G5kL98pQ4erLVeo2gVwaZQbvq

Heating Systems Bou McDonnell & Miller, Inc. Safety Devices for Steam and Hot Water Heating Boilers . . . Liquid Level Controls 3500 North Spaulding Ave., Chicago 18, Illinois The McDonnell line consists of (1) boiler water feeders, low water fuel cut offs and combined feeders and cut-offs for low pressure steam boilers of all sizes and types, hand-fired or automatically fired; (2) pump controls, low water fuel cut-offs and low water alarms for steam boilers of any size or type with pressures ujp to 150 lbs; (3) safety relief valves (Btu-rated) for hot water heating boilers and domestic hot water heaters; boiler water feeders and low water fuel cut-offs for hot water heating boilers; (4) make up water feeders for receiving tanks and other liquid level controls for special applications; (5) water level controls for humidity pans of warm air furnaces!, . The selection of controls for usual applications is shown in the following service recommendation. Most of these products are described in the following three pages. Boiler Size Service Recommendations (1) STEAM BOILERS Maximum Steam Pressure McDonnell product to use HAND FIRED JOBS Up to 5000 sq ft 25 lbs No. 47 Boiler Water Feeder Above 5000 sq ft 35 lbs No. 51 Boiler Water Feeder Any size 75 lbs No. 53 Boiler Water Feeder AUTOMATICALLY FIRED JOBS Boiler Water Feeder--Low Water Cut-off .Combinations Up to 5000 sq ft 25 lbs No. 47-2 Feeder Cut-off Combination Up to 5000 sq ft 20 lbs No. 67-101 Electric Cut-off Combination Above 5000 sq ft 35 lbs No. 51-2 Feeder Cut-off Combination Any size 75 lbs No. 53-2 Feeder Cut-off Combination LOW WATER FUEL CUT-OFFS Any size 20 lbs No. 67 Low Water Fuel Cut-off Any size Any size 50 lbs (Steam or water) 150 lbs No. 63 Low Water Fuel Cut-off \ No. 150 Low Water Fuel Cut-off (Industrial or Process boilers--Specific recommendations on receipt of complete data.) (2> HOT WATER HEATING BOILERS No. 33 Safety Relief Valve, for boilers up to 242,900 Btu per hour gross output;, open- ing pressure 30 lbs. ___________________ (3) DOMESTIC HOT WATER TANKS AND HEATERS Opening Pressure Btu per Hour Capacity McDonnell Product to use 45 pounds 75 pounds 100 pounds 125 pounds 150 pounds 321,300 308,700 423,900 513,900 605,700 No. 3345 Safety Relief Valve No. 3375 Safety Relief Valve No. 33100 Safety Relief Valve No. 33125 Safety Relief Valve No. 33150 Safety Relief Valve 1362 McDonnell & Miller, Inc. Heating Systems Safety Devices Boiler water ^feeders, feeder-cut-off combinations, and low water cut-offs . . . for low and moderate pressure steam boilers McDonndl No. 47-S for heating boilers under 6000 eg *1 capacity. Maximum steam pressure, tS lbs. McDonnell No. 61-t for heating boilers over 6000 sq ft capacity. Maximum steam pressure, 56 lbs. McDonnell No. 47-2, shown installed above, maintains a safe water level in boiler by feeding water whenever neces sary. if emergencies such as priming or foaming permit water to fall to i in. in gauge glass, cut-off switch cuts cur rent to burner until emergency has passed. Has "Quick-Hook-Up" for fast, accurate installation right in gauge glass tappings; "cool" feed valve; extra-deep sediment chamber; ASME-approved blow-off valve. Also available for hand fired boilers without No. 2 switch, as No. 47 Feeder. McDonnell No. 51-2, shown installed above, is same as No. 47-2 described at left, except it has greater feeding capac ity for larger boilers, and is installed with 1 in. equalizing pipes instead of "Quick-Hook-Up." Also available for hand fired boilers without No. 2 switch, as No. 51 Feeder. For boilers operating at higher pressures, from 35 to 75 lbs, use McDonnell No. 53-2 (or No. 53, without switch.) McDonnell No. 67 Low Water Cut-off For automatically fired steam boilers of any size Maximum steam pressure, 20 lbs. Has the McDonnell "Quick-Hook-Up" for quick, easy and trouble-proof installation in gauge glass tappings; deep sediment chamber with large quick-opening blow-off; packless, non-binding construction; adjustable terminal box to make wiring neat and easy; dependable snap-action twin switches. One switch can be used to sound low water alarm, or control McDonnell No. 101 Electric Water Feeder described below. Second switch cuts current to burner if water level drops to \ in. in gauge glass. McDonnell No. 101 Electric Boiler Water Feeder For boilers up to 5000 sq ft capacity For use with No. 67 Low Water Cut-off or with McDonnell "built-in" Low Water Cut-offs which are standard equipment on many modern heating boilers. It converts the cut-off into a feeder cut-off combination as described, at top of this page. 1363