HONS 0746'*'*
THERMINOL CONVERSION BULLETIN
SP/TC-1
HONS 074645
"Nothlnt contalnod hatoln lito N conatraod as a roeommondaUon to ilia any prodad In candid with any patani. MONSANTO MAKES NO YVARRANTIES AS TO THE FITNESS OK MEKCHANTABILtTY Of ANY PROOUCT REFERRED TO, no laanntM at aatiltadoiy raaalta tram ralianea upon contained intofmatton ot focommendatloaa, and diaclalma all liability tot any taaultlni Ion u damap."
Monsanto Industrial Chotnicals Co. A Unit of Monsanto Company 800 N. Lindborgh Blvd., St. Louis. Mo. 83168
INTRODUCTION
Therminol FR* fire-resistant heat transfer fluids have long provided safe, dependable, economical performance for hundreds of users in dozens of applications. The presence of poly-chlorinated biphenyl (PCB) in the Therminol FR formulation provided fire-resistance, giving Therminol FR an added margin of safety which was especially desirable in hazardous applications.
Most recently, PCB has been identified as a potential hazard to the environment. Monsanto has accordingly elected to discontinue the manufacture and sale of Therminol FR fluids for heat transfer appli cations. This bulletin is to inform you about two alternative products sold by Monsanto which do not contain PCB, namely Therminol 66 and Therminol 66.
These products offer mast of the excellent heat transfer characteristics of Therminol FR fluids, and even a few additional advantages, such is a lower specific gravity for improved pumpability requiring less horsepower. We would point out that Therminol 66 and 66 are not fire-remtanl to the extent the Therminol FR fluids were, and due consideration must be given this fact in converting to these newer Therminol fluids. You may wish to consult with your insurers on any conversion from Therminol FR.
Conversion from a Therminol FR fluid to a Therminol 66 or 66 fluid will be a relatively simple, low-cost procedure in the majority of cases. Incorporation of proper fire protection equipment will be the only consideration of major consequence in most cases. But even this modification becomes academic, for with the discontinuation of Therminol FR fluids, fire protection equipment becomes necessary for any and all low pressure heat transfer media available today, since the Therminol FR fluids were unique in their fire-resistance.
Should questions arise with respect to the conversion from Therminol FR fluid, Monsanto's Specialty Products Group invites you to call upon its staff or qualified systems engineers for consultation at any time. Call. . .
(814) 694-2614 and ask for a Monsanto Heat Transfer Specialist.
HONS 074646
2
Therminol BS ami SI ind Your Haat Transfar Syitam
Table 1 shows the typical physical, chemical and thermal properties of Therminol FR-1, Therminol 55 and Therminol 66. As you will note, Therminol 55 and 66 are quite similar except with regard to AIT, Fire Point and density. The substantially lower density of Therminol 55 and 66 means that pumps used in a Therminol FR-1 system should be adequate for a Therminol 55 and 66 system. In most cases, pumping rates will be increased with a resultant saving in horsepower require ments.
TAILE f
TYPICAL PHYSICAL, CHEMICAL A THERMAL PROPERTIU
Composition
Maximum Bulk Tamparatura Rating (f.) Recommanded Use Ranga (*F.) Pout Point CF.) Pounds/Gilton (75T.)
Flash Point (*F.J Fire Point (*F.) AITCF.)
Boiling Songs ('F.) Moloculsr Weight Expansion Coeflfcintcc/cc/*F.
Tharmtnal FR-1
Polychlorinatad Biphsnyl
600"F.
Tharminni N
Modified Torphenyl
65QF.
45 - 575T
2 11.55
350 Nona to Boiling 1206'F. 620 - 630 265 0.00031
45 -- 635"F.
-15 8.35
355 374 - 392 705 644 -- 745 240 0.00039
Alkylated Aromatic
60Q*F.
20 - 575T
-40 7.4
355 410 670 635 - 734 340 0.00047
Therminol 55 and 66 have outstanding heat transfer properties, so heating and cooling performance will not be sacrificed in a change from Therminol FR-1. The specific heat and thermal conductivity of Therminol 55 and 66 are shown, along with other physical properties, in Tables 2, 8 and 4, and in Figures 1,2 and 3. The lower pour points of Therminol 55 and 66 will provide easier cold startup of the system.
HONS 074647
ID
TMipanWra
F c
50 10
in a
150 60 200 93 250 121 300 149 350 177 no 204 450 232 500 260 550 2M 600 310 690 343 no 371
TAILS t
THERMINOL* m-1 VARIATION OF FROKRTIEt WITH TEMPERATUHE
DunHy
11.60 11.48 11.22 10.99 10.76
10.53 10.30 10.07 9.83
9.(0 9.37 9.14
9.9! 0.60
tCl/m*
1399.6 1372.7 1343.7 1316.7 1289.1 1261.3
1233.5 1206.8 1178.0 1150.2 1122.5 1094.7 1000.9 1039.3
9|mM HMt
TUmhhI Oiwdmttvtty
BTU/lb Ki/Ka TU/fl Kat/m r c tar T hr
0.272
0.202 0.291 0.3047 0.3151 0.3255 0.3359 0.3464
0.3568 0.W72 0.3776 0.3600 0.3915 0.4009
0.272
0.202 0.291 0.3047 0.3151
0.3255 0.3359 0.3404 0.3568 0.3672
0.3776 0.3000
0.3985 0.4089
0.06098 0.06060 0.06021 0.05976 0.05927
0.05075 0.05819 0.05760 0.05697 0.05630
0.05560 0.05407
0.05400 0.05329
0.0907
0.0902 0.0896 0.0009 0.0882 0.0174
0.0866 0.0857 0.0848 o.o8a
0.0827 0.0117
0.0006 0.0703
VltwcHy
CP
308 23.2 6.6 3.4 2.3 1.4
1.0 0.8 0.6 0.5 0.4 0.4 0.3 0.3
Cl
220 16.9 4.9 2.6 1.8
1.1 0.0 0.7 0.5 0.4 0.4 0.3 0.3 0.3
Vipar
Kl/PP*
_--
----
---- ---- ----
---- 10 0.0136 27 0.0X7 65 0.0104 143 0.1945 291 0.3956 550 0.7480 18.8m* 1.3218 31.9m* 2.2429
11U1
t *0
0 50 10 100 38 150 88 200 93 250 121 300 149 350 177 400 204 450 232 500 260 550 298 600 316 650 343 700 371
TAKE I
THERMINOL* N VARIATION OF FROFERTIEI WITH TEMPERATURE
DmM>
ft/*
8.67 LSI 134 0.14
7.91 7.77 7.59 7.39 7.17 7.04 6.75 6.62 6.42 6.24
6.09
Kl/m1
1040 1020 1000 975 950 930 910 885 060 040 010 793 770
750 730
SpnM Hwt
Thannl Omtaiithlfr
TU/lt KmI/K| BTU/ft KM/m V c hr *T tar *c
0.320 0.350 0.310 0.405
0.430 0.455
0.480 0.505
0.530 0.555 o.5n 0.605 0.630 0.655
0.680
0.320 0.350 0.380 0.405 0.430 0.455 0.400 0.505 0.530 0.555 0.500 0.605 0.630 0.655 0.680
0.0720 0.0711 0.0703 0.0695 0.0687 0.0678
0.0670 0.0662 0.0653 0.0645 0.0637
0.0628 0.0620 0.0613 0.0605
0.1072 0.1060 0.1046 o.ioa
0.1022 0.1000
0.0997 0.0915 0.0972 0.0959 0.0948
0.09a 0.0923 0.0912
0.0900
Co
62000 255 28.0 9.75 4.18 2.42 1.55 1.06 0.77 0.58 0.45 0.36 0.34 0.27 0.20
Cl
50000 250 28.0 10.0 4.40 2.60 1.70 1.20
0.90 0.69 0.55 0.46 0.44 0.36 0.28
V|m 8mw*
mniHv
--
-- -- -- 0.1 -- 2.0 -- 20.0 50.0 100.0 200.0 350.0 760.0 ion
HO/**1
--
-- --
-- -- -- 0.003 -- 0.027 0.061 o.ia 0.272 0.476 1.034 1J60
HONS 074648
I $
c<&
I
TvnpKIim
T c
0 -IS 100 10 ao 93 300 149 400 204 500 200 (00 316
TABLE 4
THERMINOL* H VARIATION Of PROPERTIES WITH TEMPERATURE
Dimity
ik/id
7.62 7.31 7.00 6.09 6.39 6.07 9.76
Kl/nH
915 079 840 003 766 729 691
IpuHlf Hut
AbaMTMOk4umNa|VuL.fl|Hhf
ITU/Ik Kul/Kj ITU/ft Kul/m "T X kr T hr "C
0.420 0.472
0.522 0.572 0.620
0.670 0.718
0.420 0.472
0.522 0.572 0.620
0.670 0.710
0.0813 0.0704
0.0753 0.0724 0.0692
0.0661 0.0630
0.1210 0.1167
0.1121 0.1077 0.1030 0.0904 0.0938
VImnUt
Co
1472 25.4 4.20 1.69 0.904 0.563 0.415
Cl
1610 30.1 5.0 2.10 1.18 0.80 0.60
Var Prwiwt
mmHf teth*
_
_
0.5 3.0 10 40
100 250
0.001 0.004 0.014 0.054
0.136 0.330
FIQURE l THCMKINOLO FR1 PHYSICAL PROPERTIES
fc
?
I
16
tM
ST
i <XE 10 i
8Uoi
>
6
2 z
8
MCNS 074649
5
c0
FIGURE 2 THERMINOLG M
FIGURE 3
5'
f .SPECIFIC HEAT-- B TU /LB .
SPECIFIC HEAT -- B TU /LB .
074650 HONS
40 35 30 25 20 15 10 5 0
40 35 30 25 20 15 10 5 0
VISCOSITY -- CENTISTOKES
VISCOSITY -- CEMTISTOKES
II
Generally speaking, then, a well designed system currently operating on Therminoi FR-I can be converted to Therminol 55 and 66 with few, if any, basic changes in design -- and without sacrifice to heat transfer efficiency. With the similarity of the heat transfer properties of the three fluids thus established, let us turn to the important differences between Therminol FR-1 and Therminol 55 and 66: namely, fireresistance and oxidation-resistance,
Fire-Rssfstanca
As stated in the Introduction to this bulletin, the Therminol FR fluids were unique in their inherent fire-resistance. No other commonly ueed heat transfer medium could be so classified. Even so, the Therminol FR fluids could be made to bum under certain conditions, as indicated by their AIT of about 1200F.
It is important to realize that Therminol 55 and 66 are less fire-resistant than Therminol FR-1, and to modify the heat transfer system accord ingly; it is equally important to understand that Therminol 55 and 66 are not volatile, highly flammable fluids, but rather combustible as defined by FM and NFPA (NFPA No. 321).
Protecting the System
There are two major fire protection considerations in changing to Therminol 55 or 66 -- system leakage and possible tube ruplur* (in the heater). The former is actually part of the larger subject of good system maintenance, and should be considered regardless of the heat transfer medium employed. A tight, well-maintained system is usually a good, safe systeml Following are some suggestions to prevent leakage when you convert to Therminol 55 or 66.
First, if your system has rotary mechanical seals, you should provide a spray shield and a drip pan with a drain to a collection sump. Canned and seal-less pumps offer excellent protection against leakage.
The best way to prevent piping leakage is to weld all connections. Where you must have access, use raised-face flanges with appropriate gasketing and high-temperature bolting. Control of piping leaks is especially important, since fluid-soaked insulation poses a more serious hazard than the leaking fluid, itself.
Organic compounds such as Therminol 56 and 66 exhibit a slow oxidation reaction with the air trapped inside the voids of the in sulating material when system temperatures reach about 500*F. Saturated insulation offers a large fuel surface in the face of poor heat dissipation conditions, and this, along with possible catalysis from the insulating material (magnesia, silicate-bonded asbestos or calcium silicate) can cause a temperature build-up in the mass. This temperature build-up can result in ignition of the fluid when the spsce between the piping and the saturated insulation is exposed to air (i.e., should the insulation be broken for repair, etc.).
This phenomenon is not fully understood, but appears to occur less with closed cell insulation than with the insulating materials mentioned
HGNS 074651
i
above. Closed cell materials, then, are preferred, especially where leakage is a possibility despite all precautions.
The principle problem areas are near instrument connections, valve packing glands, flanges, and where cracks develop in relatively im permeable insulation cement adjacent to oil soaked insulation.
To obviate this problem, eliminate any source of leakage promptly. Replace leaky gaskets, oil soaked insulation, and re-pack valve stems. Cover insulation where leaks might occur with a hydraulic setting, oil-resistant cement. Install valves, where possible, with the stems in a horizontal position bo that leaks will drip away from the insulation. And again, use closed cell insulating materials on suspect piping areas.
Tubs Rupture in Fired Huatsrs
Generally speaking, where Are protection is concerned, it is best to consult your insurance underwriter for guidance and counsel. Likewise, you will want to discuss your fire safety equipment requirements with qualified suppliers of fire protection equipment. Selection and sizing of fire protection equipment is important to safeguard the installation.
A commonly used method of preventing fire in the event of tube rupture in fired heaters is piping steam or COt as a snuffer into the combustion chamber of the heater. Usually a properly-sized line with a remote manual valve for activation is the preferred arrangement. This snuffer system could be automated by the use of an exhaust stsck temperature switch. This switch would then energize a solenoid valve and alarm upon excessive temperature rise, automatically flooding the chamber with a fire extinguishing agent.
In practice the temperature switch is often set about 100F. ossr the normal exhaust temperature to prevent nuisance shutdowns. Where steam snuffer systems are used, it is a good idea to employ a steam trap to avoid slugging the combustion chamber with water when the system activates, or is activated manually.
You can obtain a basic guideline in the selection of COi protection equipment (again, it is best to consult your insurance underwriter) from the National Fire Protection Assn., 60 Batterymarch Street, Boston, Maas. 02110 AC 617-482-8756. NFPA Bulletin No. 12 dated 1968 should be requested. This bulletin should be helpful in determining the amount of COt and the concentration of COt needed to extinguish a fire based on your specific application.
COt cylinders are available from Cardox Division of Chemetron, Chicago, 111. as well as other suppliers. Some standard sizes are 50, 75, 100 and 150 pound cylinders. Prices usually include drawings of the units, fully charged cylinders, flexible piping connectors, spray nozzle, pressure switch, alarm and automatic control, provided COt release signal is supplied by customer device. Piping, wiring, and installa tion labor to be provided by the customer. Recharging of spent cylinders is available at an additional cost from a variety of ''Fire k Safety Equipment Suppliers" listed in the Yellow Pages of your phone book.
RONS 074652
Selection of all equipment and installation recommendations should be obtained from qualified suppliers; however, it is important to insure that sufficient COt is available to prevent re-ignition while the heater is cooling.
The Halon Fire Suppression System is a possible alternative to a CO, arrangement because it can be used in closed spaces with personnel in the area. One supplier of Halon systems is the Cardox Division of Chemetron Corporation, Chicago, 111. 60611.
Again, we strongly recommend that the advice of fire protection companies be solicited in either case to insure proper equipment selection and installation.
If steam is to be used rather than the other alternatives suggested above, please refer to the NFPA Volume I, Section 86A (1970-1971) to obtain the volume of steam required.
Oxidation-Resistance
With a Therminol 56 or 66 system, some provision should be made to prevent oxidation caused by air contact at fluid temperatures exceeding 200F. This was not the case with Therminol FR fluids, but must be observed for Therminol 55 and Therminol 66. Oxidation can result in sludge formation, eventually leading to carbonaceous deposits on heat transfer surfaces and at mechanical seal faces.
Oxidation of fluid can develop by air contact in an open, vented expan sion tank. Therefore, we recommended that the expansion tank be blanketed with an inert gas (such as nitrogen) as shown in Figure 4. If this is not possible, air contact can be minimised by a cold seal arrange ment as shown in Figure 5. An inert gas pressure of one to two psi is adequate, as Therminol 55 and 66 do not require pressurization to maintain liquid phase.
FIGURE 4 SUQGESTED INERT QAS ARRANGEMENT
FOR EXPANSION TANK
INERT GAS 1--2 PSI --
XL
RUPTURE DISC (OPTIONAL) S RELIEF valve
t rr
QAPPROX. Vi --
FULL LINE SIZE
-a LLC
J
"O*
PUMP
HONS 074653
$) C'
FIGURE 5 SUGGESTED COLD SEAL TRAP ARRANGEMENT
fOR EXPANSION TANK
You can design the cold seal arrangement quite simply by piping the expansion tank vent to a second tank where the vent line projects subsurface and can be flooded with additional Therminol 56 or 66 to minimize air contact in the expansion tank vapor space. In converting from Therminol FR to Therminol 56 or 66, it is important to remember that many Therminol FR systems were designed with a hot bleed line into the expansion tank to eliminate moisture accumula tion. Moisture accumulation in the presence of hydrogen chloride gas released during the decomposition of the FR fluids could contribute to acidity problems. This is not the case with Therminol 55 or 66; there fore, this bleed, line should not be used during normal operation of a Therminol 56 or 66 system. This line should be valued off during opera tion but it could be retained as a convenient means of venting the system during initial startup after conversion. Further protection against a hot expansion tank occurrence would be the removal of any expansion tank insulation and feeder line insulation. Carbonaceous deposits can also occur at the pump seal face due to leakage at high temperatures. The use of a seal flush system or a double mechanical seal is helpful in preventing excessive seal wear. Converting to Therminol 55 and 66 With fire-protection and oxidation-resistance procedures well in mind, let us turn to the matter of preparing the Therminol FR system for Therminol 56 or 66. Accumulation of debris over the years in the system could cause serious problems, especially to mechanical seals, rotary joints, etc. All heat transfer systems should be cleaned from time to time as a part of normal preventive maintenance. Since a fltiid change is neces
MONS 074654 10
o
sary at this time, it would seem practical to use the downtime to thoroughly clean the system prior to startup on a fresh charge of fluid.
We strongly advise you not to simply drain and change, but to take this opportunity to clean your system. Many potential problems will be prevented by so doing.
Another reason for cleaning your system at this time is to assure com* plete removal of the Therminol FR fluid. A system cleanout is the only sure way to do so. How to go about the cleanout is a matter of choice, but here are some alternatives for your consideration:
A. Fluid Flush Cleaning This method is probably the fastest and most effective where heating surfaces are not heavily fouled. It also offers the advantage of not having to introduce foreign chemicals into the system.
With this method, the system is drained of Therminol FR, re-filled with Therminol 55 or 66, operated for a reasonable period of time, drained once again, and finally, recharged with fresh Therminol 55 or 66.
Both the drained Therminol FR and the Therminol 55 or 66 used to flush the system may then be returned to Monsanto for disposal.
B. Solvent Cleaning This method is satisfactory for cleaning a slightly soiled system, but chlorinated solvents must be avoided. Typical solvents used are benzene, and xylol (caution should be used with low flash point solvents). Do not use trichlorobenzene or perchloroethylene. (CAUTION: ALL SOLVENTS SHOULD BE COMPLETELY REMOVED FROM THE SYSTEM PRIOR TO OPERATING AT HIGH TEMPERATURES). Normally this is accomplished by drying the residual with warm air or by operating the refilled Therminol system at a temperature slightly above the boiling point of the solvent until the residual is vented from the system. Some caution should be used in drying the system to prevent flashing of the solvent with resultant discharge of Therminol from the system. Both the drained Therminol FR and the flushing solvent may then be returned to Monsanto for disposal.
Ftaid Disposal
Monsanto offers an incineration service for the disposal of PCB heat
transfer fluids and the flushing fluids mentioned above. For details of
this service and how to return fluids to Monsanto for disposal, please
write:
Monsanto Company
P.O. Box 14617
St. Louis, Missouri 63178
... or call (314) 694-2514 and ask for a Monsanto Heat Transfer
Specialist.
*
HCNS 07465S
11
Handling: Ganaral Information
Heat transfer fluids are intended only for indirect heating purposes. Under no circumstances should any Therminol heat transfer fluid be allowed to come in contact with or in any way contaminate food, animal feed, food products, food packaging materials, food handling equipment, pharmaceuticals or any food-related items.
Thsrminol SB and Therminol M: Safety of Handling According to the definitions of the U.S. Federal Hazardous Substances Labeling Act, Therminol 55 and 66 are not toxic substances since the oral and dermal lethal doses in animals are greater than 5 grama per kilogram Hi body weight. Additional animal studies indicate that they do not have significant skin or eye irritation potential. It is suggested however, that good industrial practice relating to the avoidance of repeated and prolonged skin contact to any industrial chemical, heat transfer fluids, or petroleum product be followed.
Therminol 55 and 66 have such low vapor pressures at ambient temper ature that inhalation of vapors during transfer of fluid from shipping containers to a heat transfer system presents no hazard. Vapors emitted by either fluid at elevated temperatures may be irritating ss would be the case with excessively heated petroleum oils. In heat transfer installations, the fluids are used in a dosed, unpreasurized system free from leaks and with the expansion tank vent trapped so as to condense any vapors and thus prevent their escape to the work environment. Consequently, there should be little or no opportunity for workers to experience any contact or exposure. While it is believed that Therminol 56 and 66 pose no serious problems with respect to the environment, as a concerned supplier to industry, Monsanto urges the user to maintain a tight system, to correct leakage promptly, and to exercise care in the handling and disposal of this and all other such products. A tight maintenance program not only protects the environment, but keeps employes comfortable, the working area dean, and the system running smoothly.
MOMS Q7A656
12 2-32510172 8 Ulba i U S A
r ittA
i
CUSTOMER SERVICE CENTERS
AKRON. OHIO 44313 260 Springaida Dm* Morttroa* Dmvmiopmmnt Park Tat. (216) 696-4111
ATLANTA. GEORGIA 30339 320 fntarstata North Parkway Suit* 600 Tat. (404) 432-7111
BOSTON. MASSACHUSETTS 02149 Cvaratt Station Tat. (617) 367-6010
CHICAGO. ILLINOIS 3159 Oat Pfainaa Ava. Da* Pfainaa. ittinoit 60018 TaL (312) 296-6699
CINCINNATI. OHIO 4S206 1501 Madfaon Road TaL (M3) 761-6707
DETROIT; MICHIGAN
COO Northland Towara Waat Southfbfd. Michigan 49076 Tat. (313) 367-0910
HOUSTON. TEXAS 77027 1301 Root Oak Towar 6061 Waathaknar Road TaL (713j) 621-9660
LOS ANGELES. CALIFORNIA 90022 6670 . PhtHh St. TaL (213) 723-2492
NEW YORK. NEW YORK 10036 1114 Avamta at tha America* Tat. (212) 764-6000
ST. LOUIS. MISSOURI 63166 SOON. UndharghBNd. Tat. (314) 694-1000
SAN FRANCISCO BAY AREA 2710 Lafayette Santa Clara. California 96062 TaL (406) 243-0414
SEATTLE. WASHINGTON 9B121 2112 Third Avenue Tnt. (206) 622-4203
WILMINGTON. DELAWARE 19810 Suita 204. Bancroft BMg. 3411 Siivartida Road TaL (302) 479-4600
Monunta Industrial Chemicals Ca. A Unit ot Monsanto Company 800 N. Lindbergh Blvd., St. Louis, Mo. $3166
12/71
#