RECOMMENDED SPECIFICATIONS AND APPLICATION PROCEDURE
These specifications are of a general nature. Application pro cedures and material approval are the responsibility of the design engineer.
JEW CAREYTEMP 1500 PIPE INSULATION Pipe insulation shall be applied over a clean, dry surface. Sectional insulation under 12' in diameter shall be installed with joints closely butted and secured by neatly pasting down canvas laps furnished with the covering.
Insulation on pipes over 12' in diameter and all outdoor insu lation shall be wired in place on 9' centers with 16 gauge soft an nealed iron wire. Where double layer insulation is applied, joints shall be staggered and each layer must be secured with wire.
Elbows shall be insulated with Premolded Elbows wired in place and covered with a pasted-on 4-oz. canvas jacket. Fittings, flanges and valves shall be insulated with covers fabricated from NEW CAREYTEMP 1500 Pipe Insulation or built-up with MW-One Cement.
Indoor piping under 12' diameter supplied with a factoryapplied jacket requires no additional finish under normal con ditions. Indoor piping over 12" diameter shall be finished with a 6-oz. canvas jacket neatly pasted in place.
Outdoor piping shall be finished with a 45-lb. organic or asbestos felt jacket with both longitudinal and horizontal joints lapped a minimum of 2'. The jacket shall be secured with 16 gauge copperweld wire on 9' centers or X ' wide galvanized bands on 12' centers. Other types of jacketing such as alumi num, sheet metal, plastic coating, etc. may be installed as recommended by the manufacturer.
All indoor fittings, flanges and valves shall be pointed to a smooth surface and finished with a canvas jacket neatly pasted in place. Outdoor fittings, flanges and valves shall be finished with a M ' (H' dry) coat of Thermotex-B Emulsion reinforced with 1' wire mesh.
NEW CAREYTEMP 1500 BLOCK INSULATION VND SEGMENTS Surfaces over 24' diameter up to and including 60' diameter shall be insulated with NEW CAREYTEMP 1500 curved
segments Becurely fastened with 16 gauge black annealed wire or If ' i .020 galvanized steel strapping and seals on 12' to 18' centers. All joints in the segments shall be staggered. All voids and joints shall be pointed-up with Careytemp or MW-One Cement. Then apply wire mesh over the insulated
surface. Finally, apply a X' to X ' coat of Careytemp or
MW-One Cement over the wire mesh. If Careytemp Cement is used, it shall be applied in two coats with the Becond layer troweled smooth. Indoor work shall have a final 6 or 8-oz. canvas jacket neatly pasted in place over the insulated sur faces. Outdoor application shall be weatherproofed by applying a X ' (H' dry) thickness of Thermotex-B Emulsion reinforced with 1' wire mesh.
Surfaces over 60' diameter Bhall be insulated with Careytemp flat block Becurely fastened with 16 gauge black annealed wire
or X ' x .020 galvanized bands and seals on 12' to 18' centers
using staggered joint construction. Point all voids and joints with Careytemp or MW-One Cement. Then apply wire mesh
over the insulated surface. Over the mesh, apply a %' to X '
coat of Careytemp or MW-One Cement. If Careytemp Cement is used, cement shall be applied in two coats, the final coat to be troweled to a smooth finish. Indoor work shall have a final 6 or 8-oz. canvas jacket neatly pasted in place over the insulated surface. Outdoor application Bhall be weatherproofed by ap
plying a X ' (M* dry) thickness of Thermotex-B Emulsion
reinforced with 1' wire mesh.
It is recommended for large vessels, such as towers, tanks, stills, etc., that angle iron supports be installed on 12-ft. centers. On large vessels, vertical angle iron members should be installed to hold a 30-ft. maximum length of the securing wire or band. Horizontal vessels over 6 feet in diameter should have two steel angles welded to the vessel shell approximately 30 degrees below the horizontal center line. The depth of these supports should be held to X ' less than the insulation thickness.
C'
PMiLff* CJ\MYr
TiOiM
Cincinnati, Ohio 45215
DISTRICT OFFICES AND WAREHOUSES:
ATLANTA 2033 Tucker fndustriaf Rd. Tucker, GeorQia 30084 404--939-1505
BOSTON 763-D Concord Aventie Cambridge. Mass. 02138 617-876-7700
CHICAGO 1125 McCabe Avenue Elk Grove Village. III. 60007 312-437-6410
CINCINNATI 1307 Atkinson Square Cincinnati, Ohio 45246 513--821-3000
CLEVELAND 5850 Hummel Rd. Cleveland, Ohio 44142 216-267-8060
DETROIT 14420 Livemois Avenue Detroit, Michigan 48238 313-868-2600
NEW YORK Smith St. & Victory Bridge Perth Amboy, N. J. 08862 201-826-6881
HOUSTON 1400 North Post Oak Road Houston, Texas 77055 713-686-3761
INDIANAPOLIS 1111 S. Franklin Road Indianapolis, Indiana 4623d 317-356-6393
LOS ANGELES 13711 Freeway Drive Santa Fe Springs, Calif. 90670 213-921-3545 213-773-8511 714-523-3130
514 Raritan Center Edison, New Jersey 08817 201--494-0530
PHILADELPHIA 24th and Sedgley Ave. Philadelphia, Pa. 19132 215-229-6430
PROVIDENCE 40 Patton Road East Providence, R.l. 02916 401--434-0250
ST. LOUIS 10847 Midwest Industrial Blvd. St. Louis, Missouri 63132 314--423-5500
MEMPHIS 1510 Orenda Road Memphis, Tennessee 38107 901-526-6861
WASHINGTON. D.C. 10710 Hanna Street Beltsville, Maryland 20705 301--474-8822 Balt. 301-792-0182 (toll free)
WARRANTY--We warrant our materials to be of good Quality and will replace ma terial proved detective. This warranty is in lieu of sll others eioress or Implied and may not be extended by representatives, written sales information or drawings. While we recommend uses for our material based on tests believed reliable, we in no way guarantee particular methods of use or application or ptrformance under apecial conditions.
Descriptions tnd specifications contained herein were In effect ft the time this pub lication was approted for printing. We reserve the right to discontinue products at any time or change specifications and/or designs without notice and without in curring obligation.
Form 6902R-631069RP Litho in U.S.A. v
C 000938
LAM022453
J
OWENS CORNING
Fiberglas
December. 1971
Glaslag Type l-S Pipe Insulation
For Power & Process, high temperature piping system 850F
uses
Glaslag pipe insulation is particularly suitable for use on long run piping in process and power plant systems where hioh temperatures do not exceed 850F.
Tesistanc^^ToHequireaoraesifei?^^^^""^
benefits
Economical application Glaslag is applied quickly and easily particularly in the larger sizes as the insulation and jacketing are applied in one'operation. Three foot lengths also result in more lineal feet per man hour.
Easy fabrication Only a knife and metal shears are needed for fabrication and fitting around valves, flanges, hangers, etc.
description
Glaslag Type l-S pipe insulation is a flexible wrap around type insulation fabricated from special Intermediate Service Board lags adhered to metal jacketing.
Will not cause stress corrosion cracking Glaslag is suitable for use on austenitic stainless steel piping as the base material (l-S Board) is extremely low in leachable chlorides and contains sufficient sodium plus silicate to meet MIL-l-24244 Amendment 3.
Dimensionally stable Glaslag will not shrink or rot and will withstand thermal shock.
LAM022454 C 000339
performance characteristics
Compressive Strength, 5 % deformation
PSF 65
After hot pipe 700F for 96 hours @595 deformation
17
Corrosion resistance does not cause or accelerate corrosion of steel, aluminum. or stainless steel.
Dimensional stability Stable -- will not grow or shrink
Specification compliance Meets MIL-l-24244 Amendment 3, Insulation materials, thermal, with Special Corrosion and Chloride requirements, type 13B
100 200 300 400 SOO 600 700 Mean Temperature F
Recommended thickness
Selection of insulation thicknesses for any specific application should take into consideration at least the following criteria. 1. Cost of insulation applied. 2. Cost of heat energy. 3. Cost of capital. 4. Cost of depreciation -- plant and insulation. 5. Capital investment in heat production equipment. 6. Temperature differential. 7. Size of the pipe or surface. 8. Conductivity of insulation.
Sizes
pipe sizes -- Glaslag Type l-S Pipe Insulation is available to fit nominal pipe sizes from 4" to 40" in diameter.
thickness -- Glaslag Type l-S Pipe Insulation is available in single layer thicknesses from 1" to 4 " depending upon pipe size.
Form
Glaslag Type l-S is available only in 3 foot lengths cut to length so that it will wrap around and enclose the pipe O.D. with insulation. It has a 2" circumferential overlap and a 2" longitudinal overlap.
Jackets
The insulation is furnished adhered to metal jacketing.
metal types-- .016 smooth, corrugated, and embossed aluminum. These weatherproof jackets provide resistance to mechanical damage and present a neat finished appearance to power and process pipe lines. The jackets are oversized to provide a circumferential and longitudinal lap. For the purpose of sealing against weather conditions.
c 000340 LAM022455