Document EvXjmnrkMkLRQQen6K3wj3R8N
SHELL' OIL COMPANY MFG & TECH - ENG REF & CHEM PLTS
April 1985
SINEERING GUIDE FIREPROOFING
17 EG-2 Page 4 of 5
3. MISCELLANEOUS ITEMS
3.1 VESSEL HEADS
When required, internally insulated bottom heads on vertical vessels or columns shall be fireproofed if the head is exposed to a potential fire area.
3.2 BUILDINGS
Structural steel columns in brick walls shall be fireproofed with one four-inch course of brick. Columns shall be sandblasted and primed with inorganic zinc in accordance with 19 GS-11 and 12, prior to bricking in.
3.3 INSTRUMENT RACEWAYS
Instrument conduits and cable trays for pneumatic and electrical instru mentation in hydrocarbon process areas shall be encased in one inch thick insulating board as shown on appended Drawing No. S-17-2-2 in those areas indicated on routing plan. These areas typically include regions with higher fire risks, such as over hydrocarbon pumps, hot piping manifolds, ect.
4. FIREPROOFING MATERIALS AND APPLICATION
4.1 REINFORCED CONCRETE FIREPROOFING
4.1.1
Concrete materials shall be designed and proportioned so that the concrete shall have a minimum compressive strength of 3,000 pounds per square inch at 28 days.
4.1.2
Cement shall be Portland cement, ASTM C150, Type 1.
4.1.3
Aggregate shall be pea gravel, ASTM C33, having a maximum size of 3/8 inch.
4.1.4 4.1.5
Reinforcing mesh shall be 2 inch x 2 inch x 14 gauge welded steel fabric.
Lacing wire shall be 18 gauge wire.
LAM 018205
4.1.6
Method of placement shall be formed-in-place or trowled; i.e., pneumatic method shall not be used. Mixing, placement, curing, and testing shall conform to applicable parts of American Concrete Institute Standard 318.
4.1.7
When poured placement is used, slump shall not be less than 3 inches or more than 6 inches.
MTE 17 EG-2-0005.0.0
DPMC-11875
ENGINEERING GUIDES ID GENERAL SPECIFICATIONS^"" SHELL OIL COMPANY
FIREPROOFING DETAILS
^ ZA nro AND TECH - ENG
INSTRUMENT CABLE TRAYS AND CONDUIT
" REF AND CHEfl PLTS
DRAWING: S-17-2-2
'////S//'//////"/'////? /~S S72 CONOUIT PROTECTION
JOHNS-MANVILLE MARINITE - 36TYPE 8" l" THICK ON TOP, BOTTOM ANO SIDES. S.S. STRAP ANO WOOO SCREWS(24"CENTERS)
&& J-BOLTS OR KORN CLAMPS W/SS. NUTS ANO BOLTS (24* CENTERS)
SLEEPER 2" WIOE MAOE OF f MARINITE (24"CENTERS)
BOLT THRU SLEEPERS
CABLE ANO TUBING PROTECTION
JOHNS-MANVILLE MARINITE - 36 TYPE V' l" THICK ON TOP, BOTTOM ANO SIDES
S.S. STRAP ANO WOOO SCREWS (24"CENTERS)
S.S. NUTS ANO BOLTS OR S.S. ORIVE RIVETS (24" CENTERS)
SLEEPER 2" WIOE MAOE OF l" MARINITE (24"CENTERS)
NOTES
LAM 018206
1. MITER MARINITE EDGES AT ALL ELLS ANO TEES IN RACK.
2. PAINT ALL EXPOSED MARINITE SURFACES WITH TWO COATS EPON ESTER GRAY
DPMC-11876