Safety* Devices for Steam and Hot Water Boilers and Liquid Level Controls
General offices: Wrigley Building, Chicago, 111.
"Doing one
a *thing well
PRODUCTS:
Boiler Water Feeders; Feeder-Cut off Combinations;.Low. Water Fuel Cut-offs; Pump Controls, Low Water Alarms; Humidifier. Water Level Controls; Safety Relief Valves for hot water heating boilers and storage tanks; Liquid Level Con trols for a wide range of services.
Boiler Water Feeders--McDonnell boiler feeders protect steam boilers from low water by automatically supplying water to the boiler when and as needed. See illustrations and service data opposite.
Feeder Cut-off Combinations--For automatically fired boilers the No. 2 Low Water Cut-off Switch is added to form a feeder-cut-off combination, like the No. 47-2, No. 51-2, etc. In such a combination the feeder takes care of the normal water requirements. In case of an emergency, such as excessive priming and foaming or failure of the pump, the low water cut-off switch stops the burner until emergency is passed. Electrical ratings of No. 2 Cut-off Switch: A.C.--% hp, 110-220 V.; D.C.-- 10 amp, 125 V.
Low Water Fuel Cut-offs--If the feeder-cut-off combination is not desired, the No. 67 alone can be installed to de pendably stop the burner when low water threatens. Has two switches--one oper ates alarm or controls No. 101 Electric Feeder, other acts as low water cut-off. Rating (each switch): A.C.--% hp, 115-230 V; D.C.--) hp, 115 V.
No. 51-8 Feeder-Cut off Combination. For automaticallyfired boil ers above 5000 sq ft-- maximum steam pres sure 55 lbs. No. 51 (without switch) for hand fired boilers. For pressures from 55 to 75 lbs use the No. 53 (Hand Firing) No. 6 3-8 (Automatic Firing).
"Built-in" Low Water Fuel Cut-offs-- chosen as standard equipment on modern jacketed boilers. Self cleaning to insure depend able operation. Should be speci fied with the boiler.
No. 47-8 Feeder Cut-off Combina tion. For auto maticallyfired boil--
ers up to 5000 sqft capacity--maxi
mum steam Pres sure 86 lbs. No. 47
is for hand fired
boi ler s -- sa m e service range, with
out switch. For process boilers up
to 5000 sq ft, with pressures up to 55
lbs use No. 147
(Hand Firing) or No. 147-8 (Auto
matic Firing).
No. 67 Low Water Fuel Cut-off. For
automatically fired boilers of any size; maximum slearrup.ressure 85 lbs.
For high pressure jobs the No. 150 will serve not only as a low water fuel cut-off but also as a pump control and low water alarm--for pressures as high as 150 lbs. Electrical ratings, Cut-off and Pump Con trol: A.C.--1 hp, 110-220 V; D.C.-- H hp, 115-230 V. Alarm: A.C. or D.C.-- 1 amp, 110 V. Specify 150-M for manual reset low water cut-off.
' No. 101 Electric Water Feeder
for use with No. 67 or Built-
in cut-offs--converts into Feeder-Cut-off Combinations.
Advanced Features--A notable ad vance in No. 47 and 67 is the deep sedi ment chamber, with large capacity, straight-through (A.S.M.E. Standard) blow-off valve. Other features of feeders and cut-offs include: Quick-Hook-Up; Cool feed valve; finer stainless steel valves; large area built-in strainers; double switch construction of the No. 67; electric boiler water feeders; self-cleaning built-ins.
1038
No. 150 Combina tion Pump Control, Low Water Fuel
Cut-offand Alarm, for steam pressures up to 150 lbs. Has two switches:, one
controls pump-- other stops burher
and completes alarm circuit when water level falls to
danger zone.
McDonnell & Miller
Heating Systems Boiler Feeders
McDonnell Snap Action Safety Relief Valves
McDonnell Safety Relief Valves are the maximum gross Btu output.
first to be rated in Btu capacity--in ability to dissipate heat at their set relief pressure. Their "snap action" design was inspired
The series includes Nos. 29 and 129 for hot water heating boilers and the Nos. 229, 329 and 429 for domestic hot water heaters
by exhaustive research which proved that the only proper solution to the problem of preventing explosions and losses of hot water boilers, domestic hot water heaters, and hot water tanks was.to be found in a valve that would have sufficient discharge capacity at relief pressure to prevent further pressure rise when the boiler or
and tanks. The snap action mechanism (Pat. No. 2,248,807) provides, for the first time, a precision-built means of opening the valve wide at set pressure. Revolu tionary features are hardened stainless steel cone instead of composition disc; long lived bellows diaphragm; remarkable ease of testing; complete protection of working
domestic water heater is operated at parts; many other refinements.
No. 29 and No. 129 Safety Relief Valves for Hot Water Heating Boilers
--are rated in Btu capacity so that they can be
matched to the gross Btu output of the boilers on
which they are used:
No. 29 for heating boilers with gross heat output up to 156.000 per hour.
No. 129 for heating boilers with gross heat output up to 350.000 per hour.
Q II 6^
Set relief pressure of both No. 29 and 129 is 29 lbs.
When used in accordance with their ratings they will
No. 89-189
prevent pressures over 29 lbs under all conditions-- even such an emergency as a bottled up system with
all temperature-limiting devices inoperative and heat input at maxi
mum. This is "safety the McDonnell Way."
No. 229-329-429 Safety Relief Valves for Domestic Hot Water Heaters and Tanks
Engineering fundamentals, confirmed by practical
tests prove that there is just one simple rule to
observe in protecting domestic hot water heaters and
tanks: Keep the pressure below the maximum
allowed by the manufacturer of the tank or heater
and there will be no failures or explosions.
To accomplish this, a relief valve must have
No. 889 589-489
capacity to dissipate the maximum heat to which the tank can be subjected. This means that it must be Btu-rated, just as for a hot water boiler, so that it can
be matched to the service condition. Nos. 229,329 and 429 are so rated:
No. 229 is for water supply pressure up to 50 lbs; handles approximate Btu output of 316,720. Inlet tapping 1 in.; outlet tapping % in.
No. 329 is for supply pressure up to 75 lbs; handles Btu output of 380,896.
Inlet tapping 1 in.; outlet tapping % in. No. 429 is for supply pressures up to 100 lbs; handles Btu output of 432,590.
Inlet tapping 1 in.; outlet tapping % in.
Never forget the pressure control--not temperature control--is the fundamental safety measure. You can have pressure and break age without excess temperature, but you can't have an explosion at any temperature, unless you have excess pressure. No. 229, 329 and 429 are the first valves to be built and rated in such a way that they will prevent excess pressure under all conditions--assuming, of course, that their Btu rating is properly observed.
Installation No. 89-189
=1
ren
HOT WATER HEATER
1O1
On Direct Fired Heaters
n
STORAGE TAMC
On Storage Tank
McDonnell No. 217 Humidifier Water Control
--automatically maintains proper water
Compute wUh float chamber, 1 Ujj>ng ,and saddle valve.
Same as1817
omitting tubing and saddle valve.
levels in evaporation pans of warm air furnaces. New snap action eliminates tendency of former controls to become stopped up by foreign matter or to stick
anc* become inoperative. This valve, has
only two positions--tight closed and wide open. When water falls in. in pan .it snaps wide open feeding a full stream that
flushes orifice. Closes leak-tight against any water pressure up to 150 lbs.
1039