Document EvGkVj2OMr52JoryQZqqmaOvj

Monsanto |)IVISION Organic INSTRUMENT FUNCTION OUTLINE plant W. G. Krummrich . BLDG/DEPT AUTH NO. 811.00 2417 CED LOOP NO. ISSUED BY C. J. FIC-303-1 DATE PLANT LOOP NO. Hans 7/19/71 REV. BY . DATE REV SHEET OF 1.0 COLUMN DISTILLATE CONTROLLER . . . . The the via for column distillate draw-off rate serves indirectly to control column reflux ratio. This reflux ratio is automatically reset this controller from 3:1 to 5:1 for 1016 and from 4:1 to 8:1 "mono". v 1.1 DESCRIPTION OF LOOP , 1.1.1 Function ., ' . - The function of this loop is to control the flow of product to storage and thereby set the reflux ratio. 1.1.2 System Performance Required ' 1.1.3 Accomplishment of Function ... . \ " ' The distillate flow rate is controlled by measuring the rate of flow in the line using an armored tube rotameter transmitter. This transmitter sends a pneumatic signal to the panel mounted indicating controller. The indicating ^controller compares this signal with a set point signal and sends a varying 3-15 psig signal to the control valve which adjusts the valve to compensate for variation of the set point. . The same rotameter transmitter signal is also sent to an analogue computing station which squares the signal (to be compatible with the integration on the panel). This analogue computing station sends its output to the integrator on the new panel which totalizes the amount of distillate to storage. Upon a preset number of counts, a contact in the integrator closes causing a solenoid to energize and switch an air signal to the set point of the flow controller. This air signal comes from one of two manual loading stations which are preset to give a 3:1 and a 5:1 reflux ratio. At the predetermined count, the solenoid.switches air from the 3:1 signal to the 5:1 signal. t On the "mono" operation these signals will be set for a 4:1 and 8:1 reflux ratio. Settings for these points or any intermediate reflux ratio may be found with the attached table D-10. . PCB-ARCH-EXT0372678 Monsanto INSTRUMENT FUNCTION OUTLINE DIVISION Organic plant w. a. Krummrich SLOG/DEPT AUTH NO. .. 811.00 2417 3.0 OPERATION CEO LOOP NO. . ISSUED BY C. J. REV. BY FIC- 303-1 DATE Nans 7/19/71 DATE PLANT LOOP NO. REV SHEET OF 3.1 NORMAL a. At the start of batch the controller set point should be at 0. with the controller in automatic position (for total reflux). Remote-local switch in local position, set the integration total to read 0 counts. Set the predetermining counter to read 3585 counts. (3585 x 2.44 factor = 8750 gallons. Forecut + No. of gallons (> 3:1 ratio). Check setpoint regulator outputs so that reflux ratios will be 3:1 and 5:1 for 1016 operation and 4:1 and 8:1 for "mono" operation. After column has lined out switch controller local-remote . switch to "remote". Setpoint should move up to correct reflux ratio with red pen immediately following. If a forecut is takenvit will be necessary to observe the integration reading to know where to switch XCV-303-2 closed and XCV-303-1 open to divert product to the receiver. When the predetermining counter reaches the number of counts previously set, the reflux ratio will automatically move to the correct reflux ratio for the last half of the distillation step. 3.1.1 Startup Instructions a. Set controller setpoint on 0 auto + local. b. Set PCV-303.1 and PCV-303.2 in field cabinet. c. Set counter to zero d. Set predetermining register to correct setting. 3.1.2 Shut Down Instructions . a. Switch local remote switch to "local" on FIC-303-1 with set joint at 0 to go on total reflux. 3.1.3 Manual Operating Instructions a. Switch local remote switch to "local" and manual-automatic switch to "manual" to control flow through FV-303-1 to receiver. 3.2 INTERLOCKS None. PCB-ARCH-EXT0372680 Monsanto INSTRUMENT FUNCTION OUTLINE JlVISION plant w* G* Krummrich BLOG/DEPT AUTH NO. Oraanic .. 811.. 00 2417 CED LOOP NO. FIC-303-1 ISSUED BY C. J. Hans OATE PLANT LOOP NO. 7/19/71 REV. BY DATE REV SHEET OF 3.3 ABNORMAL OPERATIONS 3.3.1 Air Failure ' Air failure to the loop will cause control valve FV-303-1 to close. 3.3.2 Power Failure ......, .... . Power failure will cause reflux ratio set point to go to the ratio used in the first half of batch. \ ES 141 PCB-ARCH-EXT0372681