INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich .
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
ISSUED BY
C. J.
FIC-303-1
DATE
PLANT LOOP NO.
Hans
7/19/71
REV. BY
.
DATE
REV
SHEET
OF
1.0 COLUMN DISTILLATE CONTROLLER . . .
.
The the via for
column distillate draw-off rate serves indirectly to control
column reflux ratio. This reflux ratio is automatically reset
this controller from 3:1 to 5:1 for 1016 and from 4:1 to 8:1
"mono".
v
1.1 DESCRIPTION OF LOOP
,
1.1.1 Function
.,
'
.
-
The function of this loop is to control the flow of product to storage and thereby set the reflux ratio.
1.1.2 System Performance Required
'
1.1.3 Accomplishment of Function
...
.
\
"
'
The distillate flow rate is controlled by measuring the rate of flow in the line using an armored tube rotameter transmitter. This transmitter sends a pneumatic signal to the panel mounted indicating controller. The indicating ^controller compares this signal with a set point signal and sends a varying 3-15 psig signal to the control valve which adjusts the valve to compensate for variation of the set point. .
The same rotameter transmitter signal is also sent to an analogue
computing station which squares the signal (to be compatible with
the integration on the panel). This analogue computing station
sends its output to the integrator on the new panel which totalizes
the amount of distillate to storage. Upon a preset number of
counts, a contact in the integrator closes causing a solenoid to
energize and switch an air signal to the set point of the flow
controller. This air signal comes from one of two manual loading
stations which are preset to give a 3:1 and a 5:1 reflux ratio. At
the predetermined count, the solenoid.switches air from the 3:1 signal
to the 5:1 signal.
t
On the "mono" operation these signals will be set for a 4:1 and 8:1
reflux ratio. Settings for these points or any intermediate reflux
ratio may be found with the attached table D-10.
.
PCB-ARCH-EXT0372678
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Organic
plant w. a. Krummrich
SLOG/DEPT
AUTH NO.
.. 811.00
2417
3.0 OPERATION
CEO LOOP NO.
.
ISSUED BY
C. J.
REV. BY
FIC- 303-1
DATE
Nans
7/19/71
DATE
PLANT LOOP NO.
REV
SHEET
OF
3.1 NORMAL
a. At the start of batch the controller set point should be at 0. with the controller in automatic position (for total reflux). Remote-local switch in local position, set the integration total to read 0 counts. Set the predetermining counter to read 3585 counts. (3585 x 2.44 factor = 8750 gallons. Forecut + No. of gallons (> 3:1 ratio). Check setpoint regulator outputs so that reflux ratios will be 3:1 and 5:1 for 1016 operation and 4:1 and 8:1 for "mono" operation.
After column has lined out switch controller local-remote
.
switch to "remote". Setpoint should move up to correct reflux
ratio with red pen immediately following.
If a forecut is takenvit will be necessary to observe the integration reading to know where to switch XCV-303-2 closed and XCV-303-1 open to divert product to the receiver.
When the predetermining counter reaches the number of counts previously set, the reflux ratio will automatically move to the correct reflux ratio for the last half of the distillation step.
3.1.1 Startup Instructions
a. Set controller setpoint on 0 auto + local.
b. Set PCV-303.1 and PCV-303.2 in field cabinet.
c. Set counter to zero
d. Set predetermining register to correct setting.
3.1.2 Shut Down Instructions
.
a. Switch local remote switch to "local" on FIC-303-1 with set joint at 0 to go on total reflux.
3.1.3 Manual Operating Instructions
a. Switch local remote switch to "local" and manual-automatic switch to "manual" to control flow through FV-303-1 to receiver.
3.2 INTERLOCKS
None.
PCB-ARCH-EXT0372680
Monsanto
INSTRUMENT FUNCTION OUTLINE
JlVISION
plant w* G* Krummrich
BLOG/DEPT
AUTH NO.
Oraanic ..
811.. 00
2417
CED LOOP NO.
FIC-303-1
ISSUED BY
C. J. Hans
OATE
PLANT LOOP NO.
7/19/71
REV. BY
DATE
REV
SHEET OF
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
'
Air failure to the loop will cause control valve FV-303-1 to close.
3.3.2 Power Failure
......, ....
.
Power failure will cause reflux ratio set point to go to the ratio used in the first half of batch.
\