Heating Systems steam
ENGINEERING Illinois Engineering Company
2059 SOUTH R-A C I N E AVENUE CHICAGO 8, ILLINOIS
DIVISION OF AMERICAN AIR FILTER COMPANY, INC.
HEATING SPECIALTIES . CONTROL SYSTEMS . POWER SPECIALTIES
HEATING SPECIALTIES
Float and Thermostatic Traps Series G
For Low Pressure Service Compact, simple, accessible, durable,
dirt-proof. Positive valve action. Wire drawing impossible. Low discharge temperatures. Efficient air venting. Trap not damaged by freezing.
Recommended Applications For draining Low Pressure Heating Systems, Ventilating Units, Unit Heaters, Pre-Heaters, Re-Heaters, and other Fan System Heat Surface, Process Heaters, Hot Water Generators, Drips
of Mains and Risers. Series G operating ranges from 25 inches vacuum to 15 lbs pressure.
Illinois Radiator Supply Valves Quick Opening, Spring Loaded, Pack less. For any two-pipe steam, vapor or vacuum heating system. Extremely smooth and easy to operate with a cool, break-proof plastic handle for finger tip control.
Illinois Thermostatic Trap Series G For Vacuum and Vapor Heating Sys tems--For Working Pressure Up to 15 Pounds Positive acting and responsive to the slightest temperature changes, it dis charges condensate quickly and freely without loss of live steam.
ILLINOIS THERMOSTATIC TRAPS FOR HIGH PRESSURES--Series HG-- Maximum working pressure 150 pounds.
Used where neat appearance and com pactness are desirable,; as for trapping sterilizers or water stills in hospitals; steam jacketed kettles, coffee urns, warming tables and for process work.
These traps are also furnished for
medium pressures.
Series HG Trap
OTHER HEATING PRODUCTS
Air Vent Traps Boiler Return Traps Control Valves Convectors Hot Water Specialties
Strainers Exhaust Heads Suction Strainers Separators--Oil and Steam Pressure Regulating Valves
450
Ittinois Engineering Company
Heating Systems steam
CONTROL SYSTEMS
ILLINOIS HEATING SYSTEMS, with or without control, are offered in five types and cover the complete range of vacuum and vapor heating requirements. ILLINOIS SELECTOTHERM CONTROL SYSTEM--A high vacuum steam heating system with single dial control that provides comfort, economy and convenience. For buildings of any size where boilers are mechanically fired and used for low pressure steam heating only.
CONTINUOUS FLOW CONTROL SYS VACUUM SYSTEMS -A two-pipe
TEMS--Type A--For zoned installa steam circulating system in which a
tions or where steam is used for other standard vacuum pump is used. For any
than heating and domestic hot water type of building, industrial plants, or for
service, or where steam is supplied by groups of buildings heated from a central Central Station Service. Furnished for plant.
pneumatic or manual operation.
VAPOR SYSTEMS--A two-pipe system
CYCLING FLOW CONTROL SYS circulating steam at low positive pres
TEMS--Type R--For automatic or sures without pump or mechanical
manual control of steam flow and pres vacuum producer. Recommended for
sures in vacuum systems and one-pipe Residence, Small Apartment, and simi
or two-pipe gravity installations.
lar service.
POWER SPECIALTIES
STEAM TRAPS--A special feature is
the impact operated valve with snap ac
tion. The valve is either open or shut. It
cannot remain in an intermediate posi
tion. Wire drawing, scoring or cutting of
valve and valve seat are positively
eliminated. The valve cannot chatter on
the seat under any operating condition.
Sizes from in. to 2 in. Pressures from 5
psi to 250 psi and heavy duty to 600 psi.
OTHER PRODUCTS
ILLINOIS MOTORIZED VALVES (on and off)--Type R5--For automatic con
Type R Voire
trol,of steam temperatures and pressures
to prevent overheating and conserve
steam. May be operated by any auto
matic contact device or by manual
switches.
ILLINOIS ASU HEAT EXCHANGERS-- For heating water with steam. Complete range of sizes and capacities.
ILLINOIS CONDENSATION PUMPS-- The complete line includes both hori zontal and vertical. Single and Duplex Units. Illinois Type "ECR" Pump. Capacities, 2,000 to 65,000 sq ft EDR. Discharge pressures to 50 psi. Bronze fitted throughout. Dependable mechani cal seal eliminates leakage around shaft. Heavy duty float control with seamless copper float. Float switch ad justable for various levels. No sub-base required. Cast iron receiver.
451