Document Ev549wLjx3vzmdbMDMjO0do4L
c .n
v* (k - yy
Extension to
RIVERSIDE STATION of
The United Power Mfg. Co.
ByC. A. BUTLER,
This addition consists of a 28,571-kva condensing turbine-generator supplied
United Light & Power Engineering & Construction Co.
with steam at 825 lb, 825 F, from a single
steam-generating unit fired with pulver
ized coal and having a continuous slag ging furnace. The turbine design per mits steam extraction to the existing 400lb station header. The article reviews the preliminary engineering studies involved and traces the progress in design of steam
generators is now 82,142 leva which, together wlthrthat of an older steam station and several small hydro electric plants, serves Davenport, la., Rock Island and Moline, 111., and the surrounding territory.
History
generating equipment since the initial
Riverside Station is a comparatively new power plant,
installation was made in 1925.
it having been placed in service in 1925. The original
installation consisted of four 1044-hp Heine boilers and
one 25,000-kva turbine-generator. These boilers were
of the cross-drum box-header type, designed for a maxi
HE rapid progress which has been made in the de mum drum pressure of 440 lb per sq in., with combina
Tsign of steam-generating equipment in a compara tion convection and radiant superheaters arranged to tively few years is shown by the development of raise the steam temperature to 700 F. A high-pressure the Riverside Station of the United Power Manufactuerconomizer and a steel-plate induced-draft fan were in
ing Company. This station is located on the west bant stalled in connection with each boiler. The fuel-burning
of the Mississippi River about eight miles north of equipment consisted of four 10-retort, 33-tuy^re under
Davenport, Iowa. Its combined capacity of main feed stokers. There were four forced-draft fans, con-
Fia. 1--Exterior view of Riverside Station
RS-000232 1/17/02 NUECES
**
EDITORIAL
Coal Research
With advancement in power plant practice the effi ciency of coal utilization has steadily improved, as mea
provided in 1935 by the formation of Bituminous Coal Research, Inc., under whose sponsorship projects are now being carried out by several universities and by Battelle Memorial Institute. Much of this research extends be
p il
s
sured on an input-output basis. Further improvement yond the laboratory into the field of coal utilization where
upon the performance of the most up-to-date installa surveys are being made and tests conducted in actual in
tions must be progressively less as the limitations inher stallations. The question of coal segregation has been
ent in the steam cycle are approached. This is demon attacked, sizing has been studied and for the first time
strated by the statistics issued by the Federal Power the reactions and behavior of coal on an underfeed
Commission covering the generation of electricity for stoker have been ascertained under service conditions.
public consumption. From 1920 through 1937 the The program is far-reaching and much still remains to be
pounds of coal per kilowatt-hour steadily decreased from accomplished.
3 in 1920 to 1.43 in 1937, but during the last five years During the eighteen-year period, from 1920 through
the reduction has been only from 1.47 to 1.43. This, of 1937, despite a three-fold increase in electric output, the
course, is an average for nearly 3800 plants, the most consumption of coal by the plants previously mentioned
efficient of which are far under this figure. Much re has remained practically the same. This has been due
mains to be accomplished, however, in raising the effi partly to improved efficiency and partly to the inroads
ciency of the poorer plants, particularly among indus of competitive fuels, particularly gas. In meeting this
trials, to the level of the leaders in their class.
challenge the coal industry through the promotion of re
With further improvements in thermal performance search in utilization is rendering a service to the power
limited, there is still opportunity for increasing the com plant field as well as to itself.
mercial or dollar efficiency through the selection of the correct coal for the particular conditions, thereby sim
R8-000233 1/17/02
plifying operating problems by reduced maintenance and outage. Credit for achieving the marked reduction in
Steam Washing
NUECES
coal consumption per kilowatt-hour belongs to the de
The extensive use of higher boiler pressures has been
signers and operators of power plants and their equip accompanied by the necessity of providing clean steam in
ment, but as an aid to further progress specific informa order to avoid troublesome turbine deposits--a condition
tion on the behavior of different coals under various con seldom obtaining with pressures under three hundred
ditions of burning is needed and would be welcomed not pounds. This has led to the wide use of steam washers
only by the designer of equipment but also the user as a by means of which the steam is washed by the relatively
guide to the selection of the most suitable equipment.
pure feedwater and the solids entrained in the steam are
With some six thousand mines in the United States reduced to a minimum.
producing coals of various characteristics and sizes, and Many tests have been made on the purity of steam thus
hardly any two power plants identical in design and op washed and have shown remarkably low solids content,
eration, the great multiplicity and combination of factors ranging from 0.5 to 1 ppm when operating with very high
involved becomes apparent.
boiler-water concentrations. From this it should not be
The chemistry of coal has long been studied and data inferred, however, that high boiler-water concentrations
are available covering the analyses and other properties are always permissible, as this depends upon several fac
of coals from practically all seams. Also, some operating tors including pressure, analysis of the boiler water, the
companies have accumulated helpful information on the steam liberation per cubic foot of drum and the type of
performance of certain coals by trials in individual plants. boiler. Therefore, each case requires individual con
But, despite this, there has been a dearth of information sideration.
on just what goes on during the process of burning these Several methods have been evolved for testing the
various coals.
purity of steam. Among these are evaporation of
There is a growing appreciation of the desirability of the sample and testing by electrical conductivity. In the
giving more attention to coal selection, predicated upon a former method considerable time is required and much
knowledge of its behavior in storage, in handling and in care is necessary in order to avoid contamination,
the furnace, its caking and clinkering characteristics and whereas with the latter the presence of dissolved gases
the mechanism of combustion. This has been brought must be guarded against or corrections made for them.
about partly by developments in power station design While it is possible to determine the purity of steam down
and changes in operating practice and partly by the new to 0.5 ppm, or perhaps less, those experienced in making
marketing situation resulting from application of the such measurements usually advise checking by two or
National Bituminous Coal Act.
three methods when the indicated purity islessthan 1 ppm.
Constructive work in fundamental coal research has
In the final analysis, however, the object is to reduce
been conducted for some time at Carnegie Institute of the steam purity to such a figure as will avoid trouble in
Technology and the U. S. Bureau of Mines, but an added operation. This should be the ultimate criterion of perimpetus to the solution of coal utilization Droblems was jarmnnrp
nected to a common air duct serving all the boilers. Air as originally made, three boilers were required to carry
cooled refractory settings were employed.
the original turbine at full load continuously.
It was found that the maximum continuous output of each boiler as originally installed was 90,000 lb per hr
1936-1937 Addition
and that operation at higher ratings, even for short
Increased load on the system made it necessary to
periods, resulted in excessive furnace and stoker main generate an appreciable amount of power at the Moline
tenance.
steam plant, located farther down the river on the east
In 1929 a second turbine-generator of 28,571 kva bank. Compared with Riverside, the economy of the
capacity was installed. No additional boilers were Moline plant is poor and maintenance costs are high.
put in at that time because the system load did not make The increase in load also indicated early need of increased
it necessary to carry full load on both generating units capacity on the system. Modernization of the Moline
simultaneously. About the same time one'of the boilers plant by installing a superposed unit was considered.
was equipped with a water-cooled furnace. This change But investigations showed that it was more desirable to
increased the availability of this boiler, as was expected, concentrate operations at the more modem Riverside
and greatly reduced furnace maintenance. The re Station and maintain the Moline plant for power-factor
maining three boilers were equipped with water-cooled correction and standby service only.
furnaces in 1930 and 1931.
Although the equipment at Riverside could not be
The fuel burned on the underfeed stokers was princi considered obsolete, and the station was operating at a
pally southern Illinois coal. In 1932 a strip mine was heat consumption of approximately 16,500 Btu per kw
opened approximately sixty miles from the power plant. hr generated, it was obviously unwise to add new equip
The coal from this mine could be delivered to the plant ment designed for the steam conditions of 440 lb per sq
at considerably less cost than that then being used, but in. and 740 F, without giving serious consideration to
it ran high in moisture and had a low ash-fusion tem the possibilities of more economical operation obtainable
perature; hence it could not be successfully burned on with equipment designed for higher steam pressure and
the underfeed stokers.
temperature. The use of a high-pressure superposed
In order to take advantage of this supply of low- unit exhausting to the 400-lb header did not prove at
priced fuel, the stoker was removed from one of the tractive for several reasons. First, with 400 lb exhaust boilers, the water-cooled furnace was altered and two pressure, the capacity of a superposed unit using steam
pulverizers were installed. Direct firing and the inter at 1400 lb or less at the throttle would be too small to
mittent slag tap method of removing the ash were em provide the additional system capacity required. Fur
ployed. To provide preheated air for the mills, a small thermore, the blading efficiency of so small a high-pres
Ljungstrom air heater was installed with the gas passage sure turbine would have been comparatively low. It
in parallel with the economizer. This equipment was was thought that there was insufficient operating ex
placed in sendee early in 1933. With the increased fuel perience with pressures in excess of 1400 lb per sq in. to
burning capacity, and the reduction in draft loss through justify consideration of a higher pressure in order to
the economizer, as a result of diverting part of the flue increase the capacity of the superposed unit. Secondly,
gas through the air heater, the steaming capacity of the due to the fact that a portion of the base load of the
boiler was increased to 140,000 lb per hr. This installa system is carried by the hydroelectric plants, the new
tion was so successful that a second boiler was similarly equipment would at times be required to operate at
altered later in the same year.
comparatively light loads. Finally, it would obviously
In 1934 natural gas became available at Riverside. be impractical to make the superposed turbine-generator This was supplied on a typical "dump gas'1 basis, and available for use with steam from the 440-lb boilers.
did not entirely replace coal as fuel. All the boilers were equipped for burning gas. The burners on the two
The New Turbine-Generator
boilers that had been provided with pulverizers were con
Further studies, taking into consideration fuel cost,
verted to combination gas and coal burners, and in the equipment cost, expected character and amount of load,
other boilers gas was burned over the stokers.
and other important factors, led to the selection of a
With both pulverized coal and gas firing, the superheat 3600-rpm condensing turbine-generator designed for
added to the steam in the radiant superheaters was re throttle steam conditions of S25 lb per sq in. and 825 F
duced. Therefore these radiant superheaters were re total temperature. Specifications were drawn up re
built not only to regain the lost superheat, but to raise quiring that the turbine should be designed for these
the final stream temperature to 740 F.
steam conditions, but should be able to carry full load, at
By 1936 the increase in industrial and domestic use of reduced economy, with throttle steam of 400 lb and 740 F.
gas had limited the amount available for use in the power The turbine selected is a 21-stage G-E tandem-com
plant. This fact, together with increased system load, pound machine using impulse blading throughout.
made it necessary to remodel the remaining two boilers Eighteen stages are in the high-pressure cylinder. There
for pulverized coal firing, despite the fact that plans for are two rows of moving blades in the first stage and the
additional boiler and turbine capacity were already other 17 stages in the high-pressure cylinder have one
being made. The changes were similar to those pre row of moving blades each. The low-pressure cylinder
viously made on the other two boilers.
is of the double-flow type. There are nine admission
As a result of the changes in these four boilers since valves in the steam chest. The eighth and ninth valves,
they were first installed, they can now carrv both 100- which are used only when the turbine is operating with
lb turbines at maximum emergence capacity, and three 400-lb steam at the throttle, admit steam directly to the
boilers can carry both turbines at normal full load fourth stage. A fulcrum shifting device, actuated by
capacity, namely, 20,000 kw each. In the installation the steam pressure at the throttle, is incorporated in the
RS-000234 1/17/02
NUECE8
governing mechanism. At pressures above 500 lb the a pulverizer out of service for maintenance withou
eighth and ninth valves are prevented from opening, and drastically reducing the capacity of the steam generatin
the full range of the governor is made available for operat unit. Therefore, three pulverizers were finally selecte
ing the first seven valves. At pressures below 500 lb of a capacity such that under ordinary conditions tw
the governor is able to open all of the admission valves. would supply enough steam to carry normal load on th
When the turbine is operating with 825 lb steam pres turbine. With three pulverizers in service ample ca
sure at the throttle, all of the steam passes through the pacity is provided to take care of adverse fuel conditions.
first stage. Inasmuch as the pressure in the first stage By providing more capacity than originally planned i
chamber under the heavier loads rises above 400 lb, the forced- and induced-draft fans, it is possible to
it was found practical to provide for extracting steam utilize most of the capacity of the three pulverizers under
from this turbine into the 400-lb header when the high- normal fuel conditions, and increase that of the steam
pressure steam generating equipment is in service and generating unit to 300,000 lb of steam per hour.
the machine is loaded above 22,000 kw. The design of The boiler installed is a C-E bent-tube three-drum
the turbine permits 166,500 lb of steam per hour to be type designed for a maximum pressure of 900 lb per sq
extracted at 400 lb per sq in., but until a second 900-lb in. Its drums are of welded construction and the heat
pressure boiler is installed, the amount of high-pressure ing surface in the boiler proper is 8020 sq ft. The super
steam available will limit the extraction to 126,500 lb heater, which is located between the first and second
per hr.
banks of tubes, has sufficient surface (6400 sq ft) to raise
Despite its versatility, this turbine has an economy the total steam temperature to 825 F when the output is
under normal operating conditions, which is within one 112,500 lb of steam per hour. At higher outputs the
per cent of that of a turbine not having these features of steam temperature is controlled through bypassing a
large high-pressure steam extraction and the ability to portion of the gas around the superheater and thus main
carry full load with reduced throttle pressure. Further taining the temperature at 825 F.
more, the economy when operating on 400 lb per sq in.
A 9480-sq ft continuous-loop economizer is located
is better than that offered by any turbine manufacturer within the boiler setting in space provided between the
when the machine installed in 1929 was under considera two rows of tubes constituting the last bank. A gas
tion.
bypass located entirely within the setting makes pos
The main generator driven by this turbine produces sible partial bypassing of the economizer. This, serves
13,800-volt, 3-phase, 60-cycle energy. Its capacity is two purposes. At low ratings gas is bypassed so as to
28,571 kva at 70 per cent power factor. Excitation for increase its temperature entering the air heater and thus
the main generator is provided by an exciter on the main prevent its being cooled below the dew-point in the air
shaft of the unit and the excitation for this main exciter heater. This reduces the danger of corrosion and
is, in turn, provided by a pilot exciter which is also plugging in the air heater. Since approximately one-
driven by the main shaft. This eliminates losses in the third of the total draft loss occurs in the economizer, the
generator field rheostat during normal operation.
gas bypass can be used if necessary at extremely high
Since the major portion of the power from Riverside ratings to reduce the draft required at the induced-draft
Station is transmitted by overhead lines, it was neces fan under adverse conditions. The feedwater enters the
sary to provide a source of power supply for the essential economizer at 212 F and is heated to 398 F at maximum
auxiliaries independent of the main generators and the rating. The feedwater regulating valves are located
main bus. The 1500-kw house-service generator driven between the economizer and the boiler drum to prevent
by a non-condensing turbine, which was a part of the steam being generated in the economizer when bringing
original installation, was inadequate to serve the en the boiler up to operating pressure.
larged plant; hence, a 2500-kw house-service generator was incorporated in the new turbine-generator unit. This is located between the main generator and the ex citers. All of the auxiliaries in the station are supplied with power at 440 volts, 3-phase, 60-cycles, and the new house-service generator supplies power of these character istics direct to the house-service bus.
The air preheater is of the Ljungstrom type, with its shaft horizontal. It is placed above the boiler and con tains 14,400 sq ft of heating surface. The air tempera ture is raised to 305 F at 112,500 lb per hr steam output and to 394 F at the maximum steam output of 300,000 lb per hr.
The furnace is completely water cooled. It has a
/Cq /Cq
Steam Generating Equipment
volume of 12,650 cu ft and the effective heat-absorbin surface in the furnace walls is 3825 sq ft. A steel cask;
Since the new turbine could be operated at full load on encloses the entire furnace, boiler, economizer and
steam from the existing boilers, only one 900-lb pressure superheater. The waterwall circulating tubes are lo
boiler was considered. A boiler having sufficient ca cated within the casing behind the furnace tubes, and
pacity to carry full load on the new turbine, without ex are protected from the furnace heat by insulation Ln
traction to the 400-lb header, was first contemplated. addition to the protection afforded by the furnace tubes.
Due to the character of the coal to be burned, pulverizers Fuel is fired tangentially by twelve burners, three in
were the only type of fuel burning equipment considered. each comer of the furnace. One burner in each comer
The steam generating unit offered originally had a is connected to each of the three pulverizers, so that one.
capacity of 225,000 lb of steam per hour, and was fired two or three mills may be used as required without up
by two pulverizers. As the coal at times contains ex setting tha tangential effect. In each burner provision
cessively high moisture, a considerable margin in pul is made fOr burning gas as well as coal. Gas and coni
verizer capacity was necessary to insure full boiler ca may be burned either individually or simultaneously.
pacity under such conditions. Furthermore, with only one This feature is especially valuable because at times =
high-pressure boiler, it was desirable to be able to take limited amount of gas is available, but the amount is no :
22
RS-000236 1/17/02
NUECES
CC. 240.04
RS-000236 1/17/02 NUECES
sufficient to supply the entire fuel requirements of the new boiler.
The tubes in the furnace bottom are covered with cast-iron blocks. Ash is removed in viscous form through an opening fifteen inches wide at the back of the furnace floor, this opening extending entirelv across the furnace. The viscous slag drops into a water filled ashpit, where it is cooled to produce a cinder similar to the ash from a stoker. The ash is removed from the pit periodically by draining the pit and feeding the ash to the suction of an ash pump bv means of hydraulic jets.
During the period when the ash is being removed, the slag dripping from the furnace floor is cooled by water sprays in the upper portion of the pit.
The three pulverizers, each of 15,000 lb per hr capacity, \
are of the Raymond bowl-mill type. Each exhauster is / directly connected to its mill so that both mill and exhauster may be driven by the same 150-hp. 1200-rpm motor. The average heating value of the coal is 10,400 ( Btu per lb. In order to provide the best possible mill '' foundations, simplify coal piping and afford space on the operating floor, the pulverizers were located in the boiler
room basement. Each is served by an independent coal feeder located on the boiler operating floor where it can be easily inspected and adjusted by the fireman.
Boiler Auxiliaries
The new boiler is served by a single induced-draft fan located above the unit. At maximum capacity this fan handles 212,000 cfm of flue gas at 407 F with a draft at the fan inlet of 17.2 in. of water. It is driven by a 900/400-hp, 720/514-rpm 440-volt, 3-phase 60-cycle motor, through a 42-in. variable-speed hydraulic coupling.
load conditions, but driven by a constant-speed or a two-speed motor.
The forced-draft fan, of 104,300 cu ft maximum ca pacity at 11.75 in. of water, is located adjacent to the induced-draft fan and air heater. Ibis equipped with inlet vanes and driven by a 300/125-hp, 1200/900-rpm motor. The blades of this fan are backwardly curved to produce a non-overloading power characteristic.
Due to the size and comparatively low voltage of the induced-draft fan motor, an auto-transformer has been installed with proper control equipment to reduce auto matically the voltage at the motor terminals on starting, and also when the speed of the motor is changed. This
it pos contrc full-si; smalle
The by tw to th valve In cai produ the f Wher
arrangement limits the maximum inrush of current to
approximately 1500 amp.
Two boiler-feed pumps, each of sufficient capacity to
supply feedwater to the new boiler at maximum output
are installed in the pump bay of the extension. Each is
rated at 700 gpm against 2600 ft total head at 212 F.
Double-suction impellers are employed throughout,
thus insuring good hydraulic balance. Each pump is
driven by a 700-hp 3600-rpm wound-rotor motor. The
principal reason for employing this type of motor was to
reduce the starting current. However, the motor con
trols are designed to permit variable-speed operation of
the pumps, in order to take care of varying load condi
tions most efficiently. The pumps are designed for ap
proximately 100 lb per sq in. greater excess pressure than
required for maximum operation so as to provide for
decreasing total available head due to wear between periods of overhaul. The variable-speed motors permit
40Ct
operation at reduced speed when the pumps are in best
condition, to maintain normal excess of boiler feed
pressure over the drum pressure.
The new boiler is equipped with complete Bailey air-
operated combustion control equipment designed to
maintain the best operating conditions whether the
boiler is being fired with coal, gas or coal and gas in com
bination.
RS-000237
Valves and Piping
1/17/02
NUECES
Carbon-molybdenum tubing, fittings and valve bodies
are used in the high-temperature steam piping, and seat
ing surfaces on all high-temperature valves are faced
Fig. 3--Boiler room instrument panel
with stellite. Where joints were required in the steam
piping, 900-lb Standard flanges with small tongue and
The speeds of the motor were selected so that the low- groove facing were used. All high-pressure valves
speed winding may be used in normal operation when the greater than 2-in. are flanged, and small drain valves
steam output of the boiler is below 226,000 lb per hr.
were machined with socket ends for welding.
The fan blades have abrasion-resistant steel wearing A novel arrangement of two reducing valves and one
pads formed over the inside edge of each blade and tack- desuperheater was used to make the capacity of the high-
welded to the outside edge. Stay rods in the fan wheel pressure boiler available to operate the 400-lb turbines.
are protected by pipe sleeves. _The fan housing, inlet In order to insure maximum flexibility, two reducing
boxes and gas ducts are made oversize to permit lining valves were installed. The valve which opens first has
of these parts with concrete applied by means of a cement a venturi-type desuperheater installed at its outlet.
gun. This concrete is reinforced with bars and wire The other reducing valve, which starts to open only after
mesh securely anchored to the plates of the housing, the first valve is nearly wide open, discharges steam
inlet boxes and ducts. These special features of con beyond the desuperheater outlet. The thermostat
struction should greatly reduce maintenance caused by which controls the water to the desuperheater is installed
erosion from fly ash. The hydraulic coupling was beyond the point where the discharge from the de
selected rather than inlet vanes in order to reduce to a superheater join? the outlet pipe from the second re
minimum the number of parts subject to erosion, and ducing valve. Thus the temperature of the steam to the
because previous experience in other plants has indicated 400-lb header is always automatically controlled, but
that the erosion of parts in a variable-speed fan is ap only one-half of the maximum flow of 300,000 lb of steam
preciably less than in a fan operating under variable per hour passes through the desuperheater. This makes
the: take bad heat pod bv
Ii plac orig a tv rive aisl tur1 boi
I put
1
' it possible to use a smaller desuperheater which will control the steam temperature more accurately than a full-size desuperheater at low steam flows. Besides, the
smaller desuperheater costs less. The reducing valves are air-operated and controlled
by two pilot regulators. One of these pilots is connected to the 400-lb header and normally controls the reducing valves to maintain a pressure of 390 lb in this header. ,, In case of trouble in the 400-lb steam system which would produce an excessive steam demand on the 900-lb header, the first pilot will open wide both reducing valves. When the pressure in the 900-lb header drops to S00 lb
boilers. Therefore the boiler room was extended two bays, using the same column spacing in both directions as was used in the original installation. This provided space for the new boiler and for a future boiler, both on the side of the firing aisle farthest from the river. The space between the firing aisle and the existing turbine room, which would have been used for two more boilers, if the boiler arrangement used in the original installa tion had been continued, was made a part of the turbine room. The new turbine-generator was installed in this space.
The suspended parabolic coal bunker construction
the second pilot, which is connected to the 900-lb header, takes control of the main valves and operates them as back-pressure valves to maintain the pressure in that header at S00 lb, but still pass to the 400-lb header that portion of the high-pressure boiler capacity not required by the high-pressure turbine.
Building
In the original installation the tour boilers were placed two on each side of a common tiring aisle. The original turbine and the second turbine were installed in a turbine room located between the boiler room and the river. The turbine shafts are all parallel to the tiring aisle; hence, after the second turbine was installed the turbine room was approximately 72 ft l inger than the boiler room.
Despite its greater capacity, it was lAuud possible to put the new steam generating unit in a space the same size and shape as that occupied bv : of
employed in the original installation was duplicated, using the same cross-sectional dimensions and the coal conveyor over the original bunker was extended to serve the new bunker. The height of the building extension over the boiler and bunker was made the same as in the original part of the building, and the section over the new turbine was made considerably lower.
This method of extending the building for the new equipment not only reduced building costs, due to the decreased space required, but further reduced this cost because the construction was far enough from the river to eliminate the necessity of a cofferdam.
In order to install the turbine and its auxiliaries in the space provided, the condenser was located with its tubes parallel to the turbine shaft. A single-pass condenser with 17,300 sq ft of surface, made up of 7/,-in. diameter tubes 20 ft long was selected, as a long narrow condenser was best suited to this arrangement. The condenser was
- than its final position before the turbine foundation was unit share to some extent the advantages of a superposed
built. The reinforced-concrete foundation was then turbine in increasing the economy of the older turbines.
built around the condenser. After the turbine was 3. The new unit may be operated alone when the
erected the condenser was raised to its final location and load is light. This would not be possible in a superposed
attached to the turbine exhaust nozzle by welding. The installation and makes this unit much more economical
entire weight of the condenser is supported by the tur under light load conditions than a superposed plant.
bine exhaust nozzle.
4. The new unit may be operated with steam from
Two horizontal circulating pumps serving the second the old boilers, thus making it unnecessary to install
turbine were removed and replaced by two vertical pro more than one high-pressure boiler to insure maximum
peller type pumps which were built into the existing 42- availability of the new turbine. This makes better
in. suction pipes that had served the pumps removed. use of existing investment in lower pressure boiler equip
The capacity of the pumps removed was approximately ment than is usually possible with superposition.
26.000 gpm each. The new pumps have a capacity of 5. The arrangement of turbine governing mechanism,
55.000 gpm each and can supply sufficient water for the piping and steam-pressure reducing and desuperheating
condenser of the new unit as well as for the condenser equipment makes the capacity of the high-pressure
which the horizontal pumps had served. Therefore boiler instantly available to supply steam to the 400-lb
the expense of installing additional suction pipes was header in case of trouble with the high-pressure turbine,
avoided, and no additional space was required for cir and also makes it possible to maintain the new turbine
culating pumps for the new unit.
in operation, without loss of load, with steam from the
The resulting decrease in building volume required 400-lb boilers in case of trouble with the high-pressure
per pound of steam generated per hour, and per unit of steam generator.
installed capacity is shown in the accompanying table. The equipment described was placed in operation
This tabulation does not include the switchhouse, screen late in 1937. Operation to date has shown that the
house or the space, unoccupied at present, which has expected increase in plant economy due to this equip
been provided for a future boiler. Although there has ment has been fully realized.
been a substantial reduction in space occupied by tur
bine-generators and turbine auxiliary equipment per unit of capacity, a considerable proportion of the reduc
Program for A.S.M.E. St. Louis Meeting
tion in total plant volume per kva of capacity has been due to the reduction in building space required per pound of steam generated.
The summer meeting of the American Society of Me chanical Engineers will be held in St. Louis, June 19 to 23, inclusive. Informal conferences and committee meet
ings will occupy Sunday and on Monday morning the
COMPARISON OP BUILDING SPACE PER UNIT OF STEAM AND ELECTRIC GENERATING CAPACITV
Plant Immedi-
ately Preced 1930-1937
Original ing 1936-1937 Addition
Installation Addition
Only
Steam generating ca
pacity, lb per hr
3G0.000
560.000
300.000
Space occupied by
steam generators
and tbeir auxilia
ries, cu ft
908,000
90S,000
269,000
Space occupied by
steam generators
and their auxilia
ries in cu ft per lb
of steam per hr
2.52
1.62
0.89
Capacity of main
and auxiliarv gen
erators (kva)
26.875
55,446
31,696
Space occupied by
turbine-generators
and tbeir auxilia
ries, cu ft
632,000
1,187,000
239,000
Space occupied by
turbine-generators
aud their auxilia
ries in cu ft psr kva
23.6
21.4
7.5
Total volume of
mtuu power bouse
(exclusive of space
provided for future
equipment), cu ft 1,540,000
2,095.000
50S.000
Total volume of
main power house in cu ft per kva
57.4
37. S
10 0
Plant Includ ing 1936-1937
Addition 860,000
1.177,000
1.37 87,142
1,4 26,000
16* 4
2,603.000 29.9
first of two Fuels Sessions will be held. Papers at this session include: "A Down-Draft Conversion Burner for Domestic Furnaces," by J. R. Fellows; "Coal Carboniza tion and Its Relation to the Smoke Problem," by M. D. Curran; and "Smoke-Density Measurements," by H. E. Bumgardner.
On Tuesday morning there will be a Boiler Feedwater Session at which the following papers will be presented: `Carbonaceous Zeolites--An Advance in Boiler-Feed water Conditioning," by Howard L. Tiger; "BoilerWater Treatment--New Methods for Preventing Em brittlement," by F. G. Straub and T. A. Bradbury; "Boiler Operation as It Affects Prime Movers," by S. E. Tray; and "The Behavior of Sodium Sulphite in HighPressure Boilers," by R. M. Hitchens and J. W. Purssell.
A combined Hydraulic and Power Session is scheduled for Tuesday afternoon at which will be presented two papers, one on "Trends in Design of Large High-Pressure Boiler Units" by John Van Brunt, and the other "Operat ing Methods and Problems of a Combined Hydro- and Steam-Electric System" by H. Harrington and E. B.
Conclusions
Strowger. On Wednesday morning the second Fuels Session will
The latest addition to Riverside Station shows that be held at which the following papers will be presented:
superposition is not the only way of increasing the econ "Fuels for Industrial Heating Furnaces," by Matthew H.
omy of an existing steam-electric- generating station. Mawhinney; "Power-Plant Requirements of a Dis
The important features may be summarized as follows: tillery," by H. L. Walton; "Experiences and Difficulties
1. The new boiler and turbine-generator operating in Processing Coal," by L. C. McCabe.
at 825 lb per sq in. S25 F steam conditions produce power A session on Welding and Flame-Cutting will comprise
at the lowest total cost considering fuel cost, load fac papers on "Oxy-Acetylene Surface Hardening," by A. K.
tor and investment charges in this particular case.
Seernann; "Welding Applied to Plant Maintenance and
2. Steam may be extracted from the new turbine to Repairs," by H. R. Wass; and ".Arc-Welding Costs," bv
the older 400-lb steam header, thus making the new H. W. P. Smith.
RS-000239
1/17/02 NUECES