Document EqdzjV29xyaDmBGvDJXmEjyLN
856
CHAPTER 54
1965 Guide And Data Book
Water System
function as intended. Basic piping principles for steam, sys
tems are discussed in Chapter 8,1964 GuideAnd Data Book.
Rapid condensation of steam, especially during heating-up
periods, is characteristic of steam unit heaters. The return
piping must be planned to' keep the heating coil free of con
densate during periods of maximum beat output, and the
steam piping must be ample to carry a full supply of, steam
to the unit to take the place of that condensed. Adequate
sizes of piping are especially important where & unit heater
fan is operated under on-off control,' because the, condensate
rate fluctuates rapidly.
.> .
Recommended piping connections for unit heaters' are
shown in Figs. 16 to 19.
' /
In steam systems, the branch from the supply main to the
heater should pitch toward the .main and' be. connected to.
its top, to prevent condensate in the main'from draining
through the beater, where it might reduce capacity and
cause noise.
The return piping from steam unit heaters'should provide a
minimum drop of 10 in. below the heater, so that the head
of. water required to overcome resistances of check valves,
traps, and strainers will not cause condensate to remain, in
the heater.
' ''
Dirt pockets at the outlet of unit heaters are essential, and
strainers with ^ in. perforations to prevent rapid plugging
are recommended as an additional means of retaining dirt and
scale which might affect operation of check valves and traps.
Strainers should always be installed in the steam supply lihe,
if the heater is equipped with the steam-distributing' type of
coils or is valve-controlled. '
An adequate air vent is required for low-pressure closed-
gravity systems. The vertical pipe connection to the air
vent should be at least } in. IPS, to permit separation of the
water from the air passing to the vent.
- -
In vacuum systems, if thermostatic instead of float-ond-
thermostatic traps are used, a cooling leg must be provided
ahead of the trap.
In high-pressure systems, it is customary' to vent the air
through a petcock which is left slightly open at all times.
Where posable, it 'is advisable to-install pressure^ reducing
valves to permit operation of the heaters at low pressure.
Traps used must be suitable for the operating pressure en
countered.
When piping is connected to hot water unit heaters, it
should be pitched to permit the escape of air to the high point
in the piping, where it can be vented to the atmosphere. An
air vent at the heater is used to facilitate air removal or to vent the top of the heater. Provision should be made for complete drainage of the system, including nipple and cap drains or drain cocks where units are located below mains.
Maintenance
Regular inspection, based upon a schedule determined by the amount of dirt in the atmosphere, will insure mariming economy in operation and maintenance of Heating capacity!
Heating elements should be cleaned when necessary by brushing or blowing with high-pressure air, or by using a steam spray. Removal of the heating element and washing with a mild alkali solution, followed by thorough rinsing with water, may be necessary in oertain installations.
Dirty fan blades will cause capacity losses and may cause unbalance and vibration, with consequent noise and damage to bearings. Hence, fan blades should be cleaned when neces sary. Vibration or noise may also be caused by improper fan position or loose set screws.
There is considerable difference in the.attention required by the various types of motors used with unit heaters. This is particularly true of lubrication, the instructions for which must be carefully followed for trouble-free operation. Ex cessive lubrication may cause lubricant to reach and damage the motor.. An improper lubricant may cause failure of bearings. Instructions for care of the motor on any unit heater should therefore be obtained from the manufacturer and should be kept at the unit.
Fan bearings and drives must be given the lubrication and other attention specified by the manufacturer. If the unit is direct-connected, the couplings should be inspected pe riodically for wear and alignment. V-belt drives should have all belts replaced with a matched set if one belt shows wear.
Periodical inspections of traps, check and air valves, and the replacement of worn parts are important maintenance items. Strainers should be cleaned regularly.
When filters are incorporated in the unit, they must be cleaned or replaced when dirty.
For prevention of corrosion in .unit heaters, see Chapter 15, Corrosion and Deposits, in this edition and also Bulletin 12, The Care and Maintenance of Steam and Hot Water Unit Heaters, published by the Air Moving and Conditioning As sociation, Inc.
REFERENCES
ASHVE Standard Code far Testing and Rating Steam Unit
Ventilators (ASHVE Transactions, Vol. 38, 1932, p. 25).
* G. L. Laraon, D. W. Nelson, and R. W. Kubasta: ASHVE
Research Report No. 936--Investigation of air outlets in
r.liw room ventilation (ASHVE Transactions, Vol. 38, 1932, p. 463). F. C. Houghten,.Carl Gutberlet, and M. F. lichtenfels:
ASHVE, Research Report No. 1017--Air supply to classrooms
in relation to vent flue openings (ASHVE Transactions, Vol.
41,1935, p. 279). * Standard Code for Testing and Rating Steam Unit Heaters
(Air Moving and Conditioning Association, AMCA Bulletin No.
20, 1950).
,,
4 Standard Code for Testing and Rating Hot Water Unit
Heaters (Adopted jointly by The American Socibtt op Heat
ing and Ventilattxo Engineers and Industrial Unit Heater As
sociation, IUHA Bulletin No. 11, April 1953, 2nd ed). ........
* G. L. Larson, D. W.- Nelson, and O. C. Cromer: ASHVE
Research Report No. 958--Temperature gradient observations
in a large heated space (ASHVE Transactions, Vol. 39, 1933^
p. 243). G. L. Larson, D. W. Nelson, and John James: ASHVE
research Report No. 1011--Tests of three heating systems m
an industrial type of building (ASHVE Transactions, Vol. 41,
1935, p. 185).
,, r,
* Piping, Trapping and Venting Steam and Hot Water Unit
Heater's (Air Mooing and Conditioning Association, Inc., Bulle
tin No. 15).
CHAPTER 55
RADIATORS, CONVECTORS, BASEBOARD AND FINNED-TUBE UNITS
Definition*, Heat Emission, Radiators, Convectors, Baseboard, Finned-rube, Ratings, Corrections for Nof^Standord Conditions, Enclosed Rodiofon
RADIATORS, convectors, baseboard, and finned-tube
RADIATORS
.units are types' of heat-distributing units commonly used in steam and low temperature water heating systems. Column and large-tube radiators are no longer manufactured,
They supply heat through a combination of radiation and convection, and their function is to maintain the desired air temperature in the space. In general, these types of heatdistributing units should be placed at the points of greatest heat loss of the space, so as to offset or counteract these
but, since many of these units are still in use, Tables 1 and 2 are included to provide principal dimensions and average ratings.
The small-tube type radiators, with a length of only 1} in. per section, occupy less space than the older column and large-
losses. For example, such units are commonly located under windows, along exposed walls, and at door openings
tube units, and are particularly suited to installation in re cesses.
The term radiator is generally confined to sectional cast-
After a study of the demand for various sizes of radiators,
iron radiation of column, large tube, or small tube type. The term convector refers to a heat-distributing unit, that
the Institute of Boiler and Radiator Manufacturers, in' co operation with the Division of Simplified Practice of the
operates with gravity circulated air, has a. heating element with a large amount of secondary surface, and is surrounded
National Bureau of Standards, established the Simplified Practice Recommendation R174-47, Cast Iron Radiators; for
on all sides by an enclosure having an air inlet opening below, and an air outlet opening above, the heating element.
small-tube radiators. Table 3 shows the dimensions and ratings of the units how being manufactured.under R174-47.
The terms baseboard or baseboard radiation refer to heatdistributing units designed for installation along the-bottom
Wall radiators are well adapted to use in factory buildings; storage areas, etc. Tests have shown that the heat emitted
of walls, in place of the conventional baseboard. They may be made of cast-iron, with a substantial portion of the front
from a wall type radiator may be reduced 5 to 15 percent, if tiie radiator is located at the filing with the tubes horizontal.
face directly exposed to the room, or with a finned-tube ele^ meat in a sheet metal enclosure. They operate with gravity-
Such ceiling installations are not recommended because the resulting temperature gradients between.floor and ceiling<are
circulated room air.
excessive and make it difficult to heat the.living zone satis
' The' term finnedfube refers to heat-distributing units fabri cated from metallic tubing with metallic fins bonded to the
factorily. Dimensions and output ratings of wail type radi ators in normal wallfinstallation are given'in Table 4.
tube. They operate with gravity-circulated room air, and may be installed without an enclosure, with an open type grille, a
PIPE COILS'
:
cover, or an enclosure having top, front, or inclined outlets.
Pipe coils were once a popular type of heat-distributing
unit in factory buildings, but they have now .largely been
HEAT EMISSION
These types of heatniistributing units emit beat by a com bination of radia&on to the space and convection to the air
replaced by finned-tube radiation. The heat emission of such pipe coils is shown in Table 5, for purposes of estimating re-; placement requirements,and boiler loads. .
within the space. These heat transfer processes and the factors
CONVECTORS .
which influence them are discussed in detail in Chapter 4. In
-togeneral/those units which' have a large portion of their heated
surface exposed the space, i.e., radiators and easMron
baseboard, emit a larger portion of heat by radiation than do.
units having completely or partially concealed heating, sur
face, Le.,' cfinvectors, finned tube, and finned tube type
baseboard..
.
. Tim' output ratings of these types of heat-distributing units
are expressed in units, of Btu per hour (Btuh), 1000 Btu per
hour (MBh), or in square feet equivalent direct, radiation
(EDR) (e.g., 240 Btuh = 1 eq ft EDR with 1 psig steam)'.
Ratings' in EDR are largely being abandoned by many
manufacturers in the industry. ,.
' Convectors are n-iadp in a wide'variety of depths,
^
lengths, and enclosure or cabinet types. The basic sixes and
types are listed in Simplified Practice Recommendation
238-50; Connectors. The heating elements sue available in
fabricated ferrous and non-ferrous metals. The air enters the
enclosure below the'heating element, is heated in passing
through the element, and' leaves the enclosure through' the'
outlet grille located above the heating element Factory-
assembled units comprised of a heating element and enclosure
are widely used.- These may be free standing, wall hung/ or
recessed (Fig. 1); and may have outlet grilles and arched inlets
or inlet grilles, as desired. "
In cases where cabinets or enclosures are to be used, but!
The genera) rpoii*ibtljt7 tot thi* chapter b
tad 8teua
-
to TC 8.1, Hot Water,
are not furnisliedby the manufacturer; it-is important that the proportions of the cabinets of enclosures and the grilles
857