Document EqNnDmYQjEmOMdYkYbxZJVy6g

HEATINC VENTILATING AIR CONDITIONING GUIDE 1942 Had the tank been set 10 ft higher, the head available for friction, while still giving the same pressure at the top fixtures, would have been 0.43 lb X 10 ft or 4.3 lb greater and this, with the 1 lb drop used previously, would give a total allowable drop of 1 lb + 4.3 lb = 5-3 lb which, divided by the 600 ft equivalent run gives a drop per 100 ft of 5.3 X 100 600 0.9 lb. With this drop, the sizes according to the chart (Fig. 2) are 6 in., 5 in., and 4 in., respectively. If the run is reduced to 200 ft instead of 600 ft, the allowable drop will Table 6. Typical Calculation of Pipe Sizes on Down-Feed Rises with Flush Valve Water-Closets and Urinals (Riser No. 2. Fig. 4) Floor op Bldg. let 2nd 3rd 4th 5th 6th 7th 8th Fixtures on Floor 1 W. C. 21 Wu.. a 1 Lav. 4 W. C. 2 U. 3 Lav. 4 W. C. 2 U. 3 Lav. 6 W. C. 4 Lav. ' 6 W. C. 4 Lav. 6 W. C. 4 Lav. 6 W. C. 4 Lav. ' Gpm PER Fixture 45 45 30 3 45 30 3 45 30 3 45 3 45 3 45 3 45 3 Maximum Gpm ON Floor Maximum Gpm on Riser Usage (per cent) Probable Flow in Riser Gpm Allowable Drop Lb per 100 Ft 45 45 100 45 30 00 30 3 123 168 58 98 30 180 60 9 249 417 31 130 30 180 60 9 249 666 24 160 30 270 12 282 948 19 180 30 270 12 282 1230 270 12 282 1512 16 196 - 30 14 211 30 270 12 282 1794 12 215 2 Pipe Size In. IK IK 2 2 2 2K 2M 4 L 5.3 lb X 100 200 2.7 lb per 100 ft. This gives 5 in., 4 in., and 3 in., respectively, for the flows of 400, 200, and 100 gpm. From Example 4 it is evident that, while the down-feed system possesses certain economies in size for the riser portion, it is quite likely to involve large distribution main sizes, especially when the tank is not elevated to a considerable degree. Example 6. Fig. 4 shows a typical down-feed layout with three risers extending eight stories and with the fixtures noted on each floor. This will be solved assuming that the level of the water in the house tank is 30 ft above the fixtures on the top floor, that the 824 CHAPTER 46. WATER SUPPLY PIPING AND WATER HEATING length of run from the tank to the farthest fixture is 200 ft, equivalent length of fittings 100 ft, and the pressure required at the fixture is 7 lb. The 30-ft head is equal to a static pressure of 0.43 X 30 or 12.9 lb per square inch and to maintain a pressure of 7 lb at the highest fixtures the drop allowable in pressure is 12.9 -- 7.0 lb or 5.9 lb. As the total equivalent run is 300 ft, this is a drop per 100 ft of 1.97 lb, or practically 2 lb. Therefore, all risers and mains from the top floor back to the tank must be sized on the basis of a drop of 2 lb per 100 ft. Tables 5,6, 7 and 8 show the schedule for Risers Nos. 1, 2 and 3 with the maximum flow taken from Table 1, the percentage of use at the peak taken from Fig. 1, and the probable flow at the peak worked Table 7. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals (Riser No. S. Fig. 4) Floor op Bldg. 1st 2nd 3rd 4th 5th 6th 7th 8th Fixtures on Floor 1 S. S. 3 W. C. 1 Lav. 2 Lav. 3 W. C. 1 Lav. 1 S. S. 1 s. s. 1 s. s. 1 s. s. 1 s. s. Gpm PER Fixture 4 45 3 3 45 3 4 4 4 4 4 Maximum Gpm on Floor Maximum Gpm ON Riser Usage (per cent) Probable Flow in Riser Gpm Allowable Drop Lb per 100 Ft 4 4 100 4 30 135 3 138 142 63 89 30 6 148 61 90 30 135 3 4 142 290 4 294 4 298 4 302 4 306 41 119 41 120 40 120 40 121 40 122 30 30 30 30 2 Pipe Size In. K IK IK 2 2 2 2 3 Table 8. Size of Distribution Main for Down-Feed Systems (See Fig. 4) Riser No. 1 2 3 Maximum Gpm Riser 1038 1794 306 Maximum Gpm Main 1038 2832 3138 Usage (per cent) 18 9 9 Probable Gpm 187 255 282 Allowable Drop Lb per 100 Ft Size op Main In. 2 \4 24 25 out for each portion of the riser. Riser sizes are taken from Fig. 2, using a drop of 30 lb per 100 ft except on the riser from the top story back to the tank where 2 lb per 100 ft is the allowable limit. Since down-feed risers are nearly always sized for a pressure loss of 30 lb per 100 ft, it is possible to arrange useful sizing data in tabular form. Fig. 5 shows a typical down-feed riser for a 20 story building. Table 9 may be used for sizing such a riser of any height and for any probable flow up to 250 gpm. It should be noted that the two top floors in Fig. 5 are sized for less than 30 lb per 100 ft. Regardless of the height of the riser being sized, the two top floors of it should be sized from values given for the top floors of Fig. 5. 825 | I , I 1