CHAPTER 10
1956 Guide
of the permeance, and correspondingly, the over-all vapor resistance of an assembly (like a wall) of materials in series is the sum of the resistances of its component parts. The over-all permeance of the assembly may be found from the permeances of the individual components3-4 in a manner paralleling that used in calculating the over-all coefficient of thermal con ductivity from the individual conductances:
l Afi T T Mt
(7)
This simple theory for vapor flow, as in the case of the corresponding
PLASTER MINERAL WOOL SHEATHING ON LATH BETWEEN STUOS PAPER a SIDING
X
Fig. 2. Temperatures and Vapor Pressures under Vapor Flow Conditions in the Insulated Frame Wall of Example 1.
simple heat-flow theory, assumes conditions of unidirectional, steadystate flow. Useful calculations can be made for an assembly or sub assembly for which the inflow and outflow of vapor are equal (a condition at which no condensation occurs) if a permeance applicable to actual conditions can be assigned to each component part. Over-all permeances, vapor pressures and vapor flow can be calculated, and in conjunction with thermal calculations, relative humidities can be determined, and the imminence of condensation predicted. (See Example 1, and Fig. 2. See also Chapter 13, Cooling Load, for use of vapor-flow calculations.)
Example 1: A wood frame wall is exposed to inside conditions 70 F. and 50 per{'fi^i relative humidity (0.37 in. Hg vapor pressure) and outside conditions 0 F. and percent relative humidity (0.03 in. Hg vapor pressure). The wall consists of paint" plaster on gypsum lath on the inside over 2 x 4 in. studs, mineral wool fill between
Moisture in Building Construction 211
sctounddse,n1siant.iown.ood exterior sheathing, paper, and pine lap siding. Check for possible
To simplify the example, consider the paint, plaster and lath as a single element having a permeance M = 1.0 perms and a thermal conductance C = 2.4, and the exterior sheathing, paper, siding and paint as another single element for which Af = 2.0 perms and C = 0.50. From Table 1 the value for the permeability of mineral wool fill may be found as it = 116 perm-inches. The thermal conductivity for mineral wool, k = 0.27.
Solution: In this particular wall, insulated, and with moderate warm-side relative humidities, condensation is unlikely to occur until thesheathingisreached. To check directly for condensation on the warm side of the exterior sheathing (designated as plane X -- X in Fig. 2 for convenient reference) proceed as follows:
Calculate according to the method of Chapter 9 the temperature at plane X -- X. This is found to be 9 F. The saturation vapor pressure at this temperature is 0.06 in. Hg. If condensation is imminent or occurring at X -- X, the vaporpressure there will be 0.06 in. Hg. Calculate the permeance for the portion of the wall from the
warm side to X -- X, and the vapor flow rate to Permeance of wall to X -- X = ------ ~jjg25 = Perma-
L0 + 7KT
Vapor presssure drop to X -- X = 0.37 ~ 0.06 -- 0.31 in. Hg.-
Vapor flow to X
0.97 X 0.31 - 0.30 grains per (sq ft) (hr).
as fCoallolcwulsa:te the vapor flow rate from X -- X to outside
Permeance of wall from X --* X to outside = 2.0 perms. Vapor pressure drop from X -- X to outside = 0.06 -- 0.03
Vapor flow rate to outside = 2.0 X 0.03 -- 0.0-6 g0r.a0i3nsinp.eHrg(.sq ft) (hr).
It is apparent that continuity of vapor flow is not possible, since at the highest fvloawpotropprelasnseurXe a--t XX --thaXnpfreormmiitttetdo boyuttshideet.emCpoenrdaetunrsea,ttiohneries iisndinicdaicteadteadtaagrareteatoefr 0.30 -- 0.06 = 0.24 grains per (sq ft) (hr).
Whether this condensation rate will be serious must still be decided, since it might readily be absorbed by the sheathing during the condensation period without excessive wetting. When the temperature at X -- X is below freezing, as in this ease, the condensation will be in the form of frost which may accumulate until re leased over a short period upon a rise in outside temperature.
Condensation will be reduced or avoided if the permeance of the warm side of the wall can be reduced so that the flow to X -- X is limited to 0.06 grains per (sq ft)
(hr). Permeance required for this is q 37^^0 06 *
Perm or ^ess* ^ more re
sistant paint film on the plaster, reducing the paint-plaster-lath permeance to 0.19 perms would accomplish this.
When the critical plane for condensation is unknown, or for a more informative, graphical representation of the situation throughput the wall, temperatures and vapor pressures may be calculated and plotted as in Fig. 2. The vapor pressures throughout the wall, for continuity of flow, are calculated in a manner similar to the temperatures; the external vapor pressures are given, and the vapor pressure drops across each element are taken in proportion to resistance to vapor flow.
,, The curve for saturation vapor pressures at the various temperatures throughout the wall is also shown in Fig. 2 and is seen to fall below the curve for vapor pressures ^th continuity of flow, .toward the outer portions of the wall. This indicates that a*th the given temperatures and vapor pressures, continuity of flow is not possible and that condensation will occur. Condensation on the sheathing is indicated as a cnnite possibility, and the new vapor pressure curve can be constructed for this
hdition, as shown. This new curve does not rise above the saturation-vapo