Document EqDxXJqGj2rV7pZ1vNz5VzBdN

FROM A. A. RAMBEA'JR ENVIRONMENTAL CONTROL September 26, 1973 TO cc: MR. WAYNE CENTER ENGINEERING Mr. C. L. Green Mr. C. F. Scott Mr. T. Flores Dr. P. R. Atkins - Pittsburgh RE: SPRAYING CABLE TRAYS WITH FLAMEMASTIC FLAME RETARDANT Considerable delay has been encountered in obtaining clarification a3 to whether EPA regulations permit use of Flamemastic for coating cable trays in Refining. The writer originally objected to use of Flamemastic cn the basis of a paragraph in the Federal Register, Vol. 38, Number 66, April 6, 1973, Section 61.22(e): "e. Spraying: There shall be no visible emissions to the outside air from the spray on application of materials containing more than 1 percent asbestos, on a dry weight basis, used to insulate or fire proof equipment and machinery except as provided in paragraph (f) of this section. Spray-on materials used to insulate or fire proof buildings, structures, pipes and conduits shall contain less than 1 percent asbestos on a dry weight basis." It seemed that the last sentence was the pertinent one, "Spray on materials.......... shall contain less than 1 percent asbestos (I Flamemastic contains 7% asbestos and was to be sprayed outdoors on cable trays. However, we now have a copy of a letter from EPA's Region IX, San . Francisco (attached), in which they state that our type of spraying "is included under the provisions...........for equipment and machinery" which requires that no visible emissions be generated. Since Dyna-Therm Corporation has supplied us with a report from an independent analytical laboratory stating there were no visible asbestos fibers found on the sample filter, the writer withdraws his objections to use of Flamemastic for fire retardation at Point Comfort Operations. It is suggested that all personnel in the immediate vicinity be supplied with respiratory protection and that the spraying be monitored to insure that there are no visible emissions. In addition, Mr. T. Flores, extension 277, should be notified when spraying is to occur so he may monitor the atmosphere with personnel > samplers. 4Tf T A \ A. A. RAMBUCUR A PC 005243 I -42C3 (V ti-S' UNITED STATES ENVIRONMENTAL PROTECTION AGENCY REGION IX lOO CALIFORNIA STREET SAN FRANCISCO. CALIFORNIA 94111 ` Mr. Robert Groves, Senior Vice-President The Dyna-Therm Corporation 11120 Sherman Way Sun Valley CA 91352 JUL 2 7 1373 Dear Mr. Groves: This is in response of your request of June 25, 1973 for a determination of the applicability of the National Emission Standards for Hazardous Air Pollu tants (NESHAPS) to the spraying of material containing more than 1% asbestos for the purpose of providing fireproofing of electrical cables. Section 61.22 (e) of the NESHAPS regulation applies to the spraying of asbestos for purposes of insulating and fireproofing. Sprayirtg of electrical cables is included under the provisions of this section for equipment and maSKLnery. Therefore", no visible`emissions to the outside air are allowed from the spray on application of Flameastic 71A. Questions regarding this determination may be directed to Mr. Stanley Zwicker of our Permits Branch (415-556-3450). Sincerely, Richard L. O'Connell Director, Enforcement Division A PC 005244