36--Exhaust and Ventilation
TABLE 36-E VENTILATION RATES FOR OPEN-SURFACE TANKS
Minimum Ventilation Rate cfm Per Sq Ft Hood Opening
Enclosing Hood
Canopy Hood
Minimum Ventilation Rate cfm Per Sq Ft Tank Area
Lateral Exhaust (Note 1)
W/L
=
Tank Tank
Width Length
RATIO
One Two Three Four Open Open Open Open Side Sides Sides Sides
W/L 0-024
AB
W/L 025-049
AB
W/L 050-10
AB
Plating
Chromium (Chromic Acid Mist)
Arsenic (Arsine) Hydrogen Cyanide Cadmium Anodizing Metal Cleaning (Pickling)
Cold Acid Hot Acid Nitnc and Sulfuric Acid Nitnc and Hydrofluonc Acid Metal Cleaning (Degreasing) See Note 2 Metal Cleaning (Caustic or
Electrolytic) Not Boiling Boiling Bright Dip (Nitnc Acid) Stnpping Concentrated Nitnc Acid Cone Nitnc and Sulfunc
Acid Salt Baths (Molten Salt) Salt Solution (Parkenze,
Bonderize, etc) Not Boiling Boiling Hot Water (if vent desired) Not Boiling Boiling
75 65 75 75 75
65 75 75 75
65 75 75
75
75 50
90 75
50 75
too 125 175 125 175 150 200 175 225 90 100 150 90 130 110 150 130 170 100 125 175 125 175 150 200 175 225 100 125 175 125 175 150 200 175 225 100 125 175 125 175 150 200 175 225
90 100 150 90 130 110 150 130 170 100 125 175 125 175 150 200 175 225 100 125 175 125 175 150 200 175 225 100 125 175 125 175 150 200 175 225
90 100 150 90 130 110 150 130 170 100 125 175 125 175 150 200 175 225 100 125 175 125 175 150 200 175 225
100 125 175 125 175 150 200 175 225
100 125 175 125 175 150 200 175 225 75 75 125 60 90 75 100 90 110
90 100 150 90 130 110 150 130 170 100 125 175 125 175 150 200 175 225
75 75 125 60 90 75 100 90 110 100 125 175 125 175 150 200 175 225
ASHRAE Cuide and Data Book, 1970, Chapter 20 Used by permission
NOTE 1 Column A refers to tank with hood along one side or two parallel sides when one hood is against a wall or a baffle running length of tank and as high as tank is wide also to tanks with exhaust manifold along center line with W/Z becoming tank width in W/L Ratio Column B refers to free standing tank with hood along one side or two parallel sides
NOTE 2 Complete control of the vapors and mist from degreasing operations requires the same ventilation rates as recommended for pickling However, the solvents employed in degreasing operations are relatively volatile, and the solvent loss caused by evaporation increases rapidly as the exhaust rate at the tank increases For this reason, perfect control is usually sacrificed in favor of lower solvent evaporation rates Where solvent loss does not present an important cost or operating problem, the exhaust rates given for pickling should be adhered to, but where solvent loss must be kept at a minimum, an exhaust rate of 50 cfm per sq ft of tank area is commonly employed Where this rate is used, control will be adequate only if the tank is located in an area free of drafts and if the degreasing operations are carried out in accordance with a rigid schedule