Document EjG29JwVJBJMxRQn48gV3RjL
726
. CHAPTER 40
- -1946 Guide
TYPES OF SUPPLY AND RETURN OPENINGS
Wall type openings are: perforated plates, vaned outlets, registers, slotted outlets, and ejector nozzles.
Perforated Outlets
Due to the non-adjustability and small vane ratio perforated sheet metal outlets, although inexpensive, have not met with favor as wall type supply, openings. They are useful primarily where directional air control is unnecessary, and for return air openings.
Vaned Outlets
Outlets equipped.with both vertical and horizontal adjustable vanes are particularly suited to sidewall distribution. For proper control over the air flow, the vane ratio should be from 1 to 2. - Outlets with non-adjustable. vanes may be employed but they should only be used where the per- formance is not critical or can be adequately predicted. Vanes should be properly designed to prevent an increase of noise above permissible level.
Registers
Fixed vanes or perforated grilles equipped with a vane damper are termed registers. They are used primarily for residential heating systems, where the outlet distribution is not critical and low cost is of.importance.
Slotted Outlets
Slotted outlets essentially consist of either flat steel plates containing a number of long narrow slots or a single long narrow slot. In order to give a good, conversion from static pressure to-velocity pressure, the sides of the slots are rounded to give a venturi effect. Due to their high aspect ratio, the slotted outlets have a greater induction effect than the compar able vaned'outlets of equal area and consequently the throw is reduced. ' They are primarily useful where an unobtrusive means of distribution is. desired, and where it is desirable to submerge the outlets into the room decoration and to minimize the effect of obstructions in the line of dis- .charge; They are adaptable to narrow rooms of low ceiling. In this case the slots are run full -length of the room.
Since these outlets offer greater induction at a given noise level, they are useful in obtaining proper air motion under certain design limitations. One disadvantage, however, is that air quantity and distribution must be carefully planned as correction after installation is difficult.
Ejector Nozzles
' Ejector Nozzles refer to outlets which operate at high static pressures,'
which are constructed to give a high conversion from static in the duct
to velocity pressure in the outlet,' and which have a high induction
effect due to their high outlet velocity. They are chiefly used for long
throws and industrial process installations, such as drying, freezing,
cooking, etc. Another type of ejector, is sometimes referred to as a lower
nozzle having a 45 to 90 deg elbow, which can be rotated similarly to a
universal joint about an axis perpendicular to the surface to which it is
fastened. These outlets give a considerable degree of adjustability and
are, therefore, desirable for use in confined spaces where spot cooling is
employed. ^
'
Air Distribution
727
Ceiling Outlets
s
In ceiling outlets when the jet is circumferential and covers 360 deg,
greater quantities of room air can be handled than is permissible with
comparable side wall outlets, with a given air motion within the occupied-
space. Temperature differentials may be higher than for ordinary side
wall outlets but may not be so high as for outlets with small widely
placed slots.
;
Plaques
When plaques are used, the air from the supply opening impinges against a plate, which, with proper inlet conditions, permits the air to discharge radially. The stream is discharged horizontally in all directions. In certain applications a properly designed plaque yields satisfactory results.
Ceiling Diffusers
This type of outlet is a round, or, in some cases, rectangular outlet, which incorporates guide vanes into its construction.
The air pattern is determined from the contour and design of the guide vanes. In some units the air streams are projected horizontally, the performance being similar to that of well designed plaques. In others the air stream is projected downward. Others produce air streams at varying angles to the ceiling.
Perforated Ceilings
This method obtains air diffusion by discharging air through perfor ations in the ceiling, the free area being usually less than 15 per cent. The advantages are appearance and the ready application of sound absorbing material to the design. Also, if- designed properly, this system provides a low rate of room air motion and consequently lends itself to applications having high load or high ventilating requirements. The perforations should be kept free of accumulations of dirt, as clogging will cause uneven distribution. Dirt will also smudge the ceiling. Best results .are obtained in systems having efficient cleaning devices.
In using perforated ceilings for air distribution it is advisable to counter act the wall and glass heat losses by local heating means.
Perforated Panels
Perforated panels are used in some installations, their gross area usually being less than 25 per cent of the ceiling area. A downward,jet pattern is obtained without any directional control. The jet velocities are higher than used in.perforated ceilings, in order to produce proper diffusion.
Air volume is controlled by controlling the static pressure in the individual plenum chambers that serve the panels.
OUTLET LOCATIONS
In selecting the location of outlets, consideration must be given to the factors of physical construction, physical appearance, location of heating or cooling loads, and outlet performance.
1. The physical construction of a building, particularly of old buildings, immediately places limitations on the type of distribution system which