412 CHAPTER 17 1950 Guide Solution. ' According to Table 6, a store would use 0.624 lb of steam per degree-day . per 1000 cu ft heated space. From Table 1, Philadelphia has 4739 degree-days per normal year. Inserting in Equation 4: F = 0.624 X 250 X 4739 = 739,284 lb of steam. Degree-Day as an Operating Unit The degree-day is also widely used as a means of comparing the efficiency of the fuel consumption of one period with another for the same building. Since the fuel consumption is proportional to the weather (degree-days), and since the periods to be compared may not have the same weather con ditions, the comparison can be made only after the fuel consumptions have been computed on a comparable weather basis, that is, upon the actual number of degree-days occurring for a given month and year in the city under consideration. Since fuel consumption is proportional to the number of degree-days, plant operators frequently compute each month the fuel burned per degree-day by the heating plant. The resulting unit figure, by eliminating the outside'temperature variable,-indicates-whether the operatingefficiency ofthe plant isabove or below the previous month or year. The figures in Table 7 illustrate a typical example of a method of using the degree-day for making heating comparisons for one building for two consecutive heating seasons! The heat quantity figures inserted are pounds of steam, but a similar comparison could be made using pounds of coal, gallons of oil, or cubic feet of gas. For such a comparison, a two-year record is.often used, as shown-in Table 7. The year under consideration may then be compared, month by month, with the previous year. Column 3, Consumption for Heating, would be used if the same fuel is used for heating and process steam. Some reason able figure must be assumed for the. process requirement and should be deducted from the amount shown in column 2. This would leave in column Table 7. . Heat Consumption Record fob Comparison Col. l Col. 2 , Col. 3 Total Consumption Consumption For Heating Col, 4 Avg Mean Temp. Col. 5 De6g5DFays Base Col 6, Lb/Deg Day Col. 7 Lb/Deg. Day/ - > M Cu Ft 337.500 834,200 Nov..!_____ 1,446,600 Dec....____ 2,176,400 12 Jan- r __ 2,332,200 Feb--_____ 2,131,100 Mar..:_____ 2,021,900 CO. Apr.______ 1,241,500 g May__ __ . 672,500 . g June--------- 258,600 July.--------- 188,400 X Aug---------- 180,100 Total.__ 13,821,000 Sept______ Oct_____ _ 2' Nov.______ el Dec............ C* Jan----------- Feb.... !___ Mar. 330,200 887,100 1,525,200 2,045,500 1,933,400 1,990,200 1,984,100 170,500 667!200 1,279,600 2,009,400 2,165,200 1,964,100 1,854,900 1,074,500 505,500 ...9.1.,6..0.0 -------- _____ 146,200 703,100 1,341,200 1,861,500 1,749,400 1,806,200 1,800,100 65 53 44 25 !22 . 28 31 43 55 146 339 641 1,233 .1,297 1,106 1,032 647 .303. ...50 1,170 1,966 l!990 1,630 . 1,670 1,775 1,799 1,660 .1,670 . 1,830 0.575 0.970' 0.982 0.804 ' 0.822 0.888 0.885 0.818 . 0,822 0.905 __L.. ` 61 52 39 28 30 30 31 167 410 812 1,120 1,044 1,111 1,021 __ 875 1,718 1,653 1,660 1,670. 1,624 ' 1,760 0.431 0.845 0.815 0.817 0.825 0.800 0.868 ' If, forexample.tlie heat consumption in Uaixb, 1943,13 compared with thru in March. 1944.it will befound that in the latter the steam consumption is 1799 -- 1760 = 39 lb lees which is a.decrease of 3.3 per cent. Estimating Fuel Consumption for Space Heating 413 Table 8. Building Load Factors and Demands of Some Detroit Buildings Building CussmcinoN Load Factos 0.318 0.316 0.287 0.263 0.255 0.238 0.223 0.203 0.158 0.138 0.126 . Lb or Dehand pee (Hour) (8q Ft or Equivalent In stalled Radiator Surface) 0.184 0.207 0.217 0.209 0.225 0.182 0.248 0.158 0.152 0.145 0.151 3 only the fuel chargeable to heating. The degree-day values in column 5 are obtainable from the local Weather-Bureau. Figures in column 6 areobtained by dividing corresponding values in column 3 by the degree-days in column 5. The heating index in column 6 is, then, a figure of heat con sumption, corrected for outdoor temperature, and should be relatively con stant month by month. Column 7 in Table 7 may be used if the heat consumption is to be compared on a building volume basis with average values shown in Table 6. MAXIMUM DEMANDS AND LOAD FACTORS In one form of district heating rates, a portion of the charge is based upon the maximum demand of the building, The maximum demand may be measured in several different ways. It may be taken as the instantane ous peak or as the rate of use during any specified interval. One method is to take the average of the three highest hours during the winter. These figures are available for a number of buildings in Detroit, as shown in Table 85. These maximum demands were measured by an attachment on the con densation meter and therefore represent the amounts of condensation passed through the meter in the highest hours, rather than the true rate at which steam is supplied.- There might be slight differences in these two quantities due to time lag and to storage of condensate in the system, but wherever this has been investigated it has been found to be negligible. The load factor of a building is the ratio of the average load to the maximum load and is an index of the utilization. Thus, in Table 8, the theaters, operating for short hours, have a load factor of 0.126 as compared with the figure of 0.318 for clubs and lodges. SEASONAL EFFICIENCY The task of predicting fuel consumption within reasonably accurate limits is a simple one where sufficient experience data are available for the fuel in question. Such data can be analyzed to the point where average unit factors can be determined and expressed in such terms as, for example, cubic feet of gas actually burned per (square foot of calculated steam radia tor surface) (degree-day). The unit U can be inserted directly in Equation 4 without reference to efficiency. Such experience factors are available for gas (see Table 2) and for district steam (Table 6), but not for coal or oil.