Document DvxbjvZr9yzkX1Z5db7Lb5O4M

60' _________ CHAPTER 18 > --: , 1948 Q.vfo : :--------------- ;-- capacities as large as 600,000 Btu. Steel furnaces have low heat capacities as a result of their relatively low mass and, therefore, deliver heat rapidly on demand. RATING OF FURNACES--TESTING AND RATING CODES Warm air furnaces are generally rated in Btu per hour output at the bonnet (point of heat generation) or at the register (point of heat delivery). Rating Equations for Gravity Warm Air Furnaces9 Until a method of testing and rating gravity warm air furnaces has been developed, the following empirical rating equations are recom mended by the National Warm Air Heating and Air Conditioning Asso ciation. . Gravity warm-air furnaces of conventional design, having ratios (of heating surface to grate area) of 15 to 1 or greater, and having a ratio of casing area to face area not less than 0.4, are rated by the following equations: a. Hand-fired furnaces Converted to Stoker, Gas, or OH Firing. Bonnet Capacity in Btu per hour = 1785 xSx 1.333 (2) b. Hand-fired furnaces, with ratios of heating surface to grate area greater than 16 to 1 and less than 25 to 1. Bonnet Capacity in Btu per hour = 1785 xSx 1.333 (3) c. Hand-fired furnaces with ratios of heating surface to grate area in excess of 25 to 1. Bonnet Capacity in Btu per horn- = 1785 x 25 xGx 1.333 where ' S = heating surface, in square feet. *' G -- actual grate area, in square feet. (4) The Register Delivery Rating is equal to 0.75 x (Bonnet Capacity). The Leader Pipe Rating in square inches, formerly, used as a rating unit, may be found by dividing the Register Delivery Rating by 136. Heating Surface of Furnace. . Prime heating surface is defined as surface above the top of the grate having hot gases or livefuel on one side and circulating air over-the other, and in all cases is measured on the exterior or air side. The.areas of tfie outer casing, the inner liner, and any. radiation shields shall not be con sidered as heating surface. In determining the amount of heating surface, extended surfaces are considered to be prime heating surface subject to the following limitations: a. Extended heating surface may consist of fins, ribs, webs, lugs, or other projections from the prime heating surface. Projections less than % in. thick at the base and extending more than 1 in. from the prime surface are classified as fins. -b. Integral fins are continuously welded to, or cast as a part of, the prime heating surface. Both sides are included as heating surface, subject to the following allowances: Distance from Prime Surface ... 1st inch Ratio of Effective Area toTotal Area__ 0.40 2nd inch 0.30 3rd inch Over 3 in. 0.20 None Heating Boilers and Furnaces 361 c. Non-integral fins are spot welded to, or otherwise held in line contact with the prime heating surface. Both sides are included as heating surface, subject to the fol lowing allowances: Distance from Prime Surface................. 1st inch Ratio of Effective Area to Total Area---- 0.30 2nd inch 0.20 3rd inch Over 3 in. 0.15 None . d. In the case of ribs, webs, or lugs more than H in. thick at the baw: and extending less than 1 in. from the prime surface, the entire surface in contact with circulating air is included as heating surface. e. In the case of ribs, webs, or lugs more than in. thick at the base and extending more than 1 in. from the prime heating surface the areas of both sides of the first inch are included as prime heating surface. The portions projecting beyond 1 in. are treated as integral fins. Grate Area Grate area is defined and treated for purpose of rating as follows: a. The nominal grate area is defined as the total cross-sectional area of the bottom of the firepot. In steel furnaces the nominal grate area is the cross-sectional area inside the firebrick lining. b. The actual grate area, used for calculating the ratios of heating surface to grate area, is the nominal grate area minus certain areas that cannot be considered as part ` the grate itself. The following rules govern these deductions: (1) If a solid, con tinuous ledge extends around the grate and inside the firepot, any area of this ledge extending inside of a circle, the diameter of which is 1 in; less than the diameter of the bottom of the firepot, shall be deducted. (2) If separate, solid projections extend from the firepot towards the grate, the areas of any portions of these projections extending inside of a circle, the diameter of which is 3 in. less than the diameter of the bottom of the firepot, shall be deducted. (3) In the case of grates which are inclined, or are conical, the projected area is the same as the nominal grate area. The latter should, therefore, be used after making any necessary deductions. Ratings for Forced Air Furnaces For solid fuel burning, forced air furnaces having bonnet capacities between 80,000. and 250,000 Btu per hour, no standard method of test has been accepted, although eventually such codes will be1 developed. The National Warm Air Heating and Air Conditioning Association recommends empirical equations similar to Equations 2, 3, and 4 for gravity furnaces, except that ai constant of 2265 is used in place of the 1785. The following testing and rating codes have been generally accepted in the industry: Commercial Standards CS-109-44 for rating solid fuel-burning, forced-air furnaces having bonnet outputs of 80,000 Btu per hour or less. This provides a method of rating small coal-fired forced-air furnaces by test. A Tentative Code for Testing Oil-Fired Furnaces. This code has been adopted by the National Warm Air Heating and Air Conditioning Association for rating oil-fired fur naces by test. The American Gas Association method of rating gas-fired furnaces based upon per formance under tests. This is described in the Approval Requirements for Central Heating Gas Appliances. Commercial Standards US-44 is a method of rating oil-burning floor furnaces by test. Commercial Standard CS 104-43 is a method of rating warm air furnaces equipped with pot-type oil burners by test. Various codes covering the construction and performance of appliances as related to fire hazards have been developed by Underwriter Laboratories, Inc. In addition, there