Document Dvw9Y3X1b6Ro8jKbkgDddv5DM
INSTRUMENT FUNCTION OUTLINE
'
DEPakjlMENT 24b
TITLE REBOILER:FURNACE COIL FLOW
'' '
LOOP NUMBER- 3 0 7-5
SHEET
l' .
OF .
4
WRITTEN BY y. Brawley DATE 5/2 5/7-2 REV ..BY;- '
CLASSIFICATION FI-307-5 DATE__________________ ^REV. NO .
1.0 NEED FOR LOOP
.
.-
'
. This loop is needed to shut down the furnace in case of low flow in . . the circulating line. Low flow would not give the proper heat
transfer .needed for vaporization in the column and would cause' ' pluggage in the furnace circulating line-due to overheating.
1.1 ' DESCRIPTION OF. LOOP
.
'
'
ill Function
The function of this loop is to indicate the flow rate of crude
through the furnace coil and shut down the furnace burners in case
of a minimum flow.
.
.
1.1.2 'Accuracy Required
.
.
+ 2%
.
'
'
-
. '
1.1.3 Accomplishment of Function
'
' '
.
The circulating flow rate of crude through the furnace'coil is
measured by an orifice plate. The flow rate shows on the indicator.
At the low flow set point, the contact-in the indicator will open
and energize a relay. The relay will shut down the furnace burners'
and bring in an alarm.
INSTRUMENT FUNCTION OUTLINE
TITLE REBOILER FURNACE COIL FLOW.
SHEET 2 '
OP
4 .______
DEPARTMENT '
246
' LOOP NUMBER
307-5
CLASSIFICATION FI-307-5
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A. Indicator & Switch
A, Barton Flow Indicator Model 277
Location: North- side offurnace,
1st level.
.
.. Range: 0-105 (0-10.00 GPM)
.
' Span:
0-5 0" H2O.
Set Point: 25" H?0 ' (420 GPM or ' (4.20 on scale)
Action: Contact to open on low
flow. '
.*
Liquid: SpGr. 1.3
Range: 0-105 = 0-50" W.C.
Contacts - Open on low flow..
IPMO - 257
C. Relay
- '
. Allen Bradley 70ON
.
B. Orifice (FE-3 07-5)'
Location': 7 feet above the
indicator.
Size; 520 Plate
L Relay (#10 CR)
Location: Inside furnace field
cabinet. . .
.
.
PCB-ARCH-EXT0373564
INSTRUMENT FUNCTION OUTLINE
TITLE REBOILER FURNACE COIL FLOW .
SHEET________ 3
OF ________4
' '
Written by_Date________ _Rev. by
DEPARTMENT
246
LOOP NUMBER 3 07-5
CLASSIFICATION FI-307-5
Date
Rev. Number
To Pot
PCB-ARCH-EXT0373565
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT
246
TITLE REBOILER FURNACE. COIL FLOW
LOOP NUMBER- .3 07-5
SHEET
4.
OF
4
CLASSIFICATION FI-307-5
WRITTEN BY_DATEREV. BY___________ DATE .REV .NO.
3.0 . OPERATION OF LOOP
.
.
'
.
3.1 NORMAL OPERATION
..
.
3.1.1 Start-Up Instructions
-
-
Crude must be circulating through the furnace coil.
'
3.1.2 Shut-Down Instructions
The column must be on total reflux 0 all the burner off.,
.
.
3.1.3 Normal Operating Instructions
_
The indicator' will read 1,000 GPM.
'
.
3.1.4 Routine Checks Required
...
Check the indicator at least 2 times a shift.
.
.3.2 INTERLOCKS AND ALARMS
. '
'
'
At low flow set .point (42 0 GPM) the furnace will shutdown and an -
alarm will sound in the control room, the telalarm window "furnace
' . shutdown" will light. Also, an alarm will sound in the furnace .
field cabinet.
.
.
,
3 3 ABNO-RMAL OP E RAT I ON
'
'
3.3.1 Air Failure
..
' " '
Air failure will not affect this loop but the furnace will shut
down due to other interlocks-.
3.3.2 Power Failure
.
:. ' .
' '
A power failure will shut this loop down.
3.3.3 Also see Drawings 2417, E5, 15, and IFO's FIC-307-1 and
3-307-1.
PCB-ARCH-EXT0373566
INSTRUMENT -FUNCTION OU.TL1NE
DEPARTMENT
TITLE RESIDUE TANK LEVEL
LOOP NUMBER- 312-3
SHEET
1.
OF
5
WRITTEN BY V . Brawley DATE 5/18/72 REV.BY_________
CLASSIFICATION. LIA-312-3 DATEREV.NO .
1.0 NEED. FOR LOQP
.
'
Residue 'from 1-312 is fed to the existing No. 2 still for distillation.
Surge tank level must be known prior to pumping residue from the
still pot after a column run.
.
1.1 DESCRIPTION OF`LOOP
1.1.1 .Function
The function of this loop is to provide an indication of the residue
tank level at both the control panel and in the field. Also to give
an alarm on high or low level and to shutdown the column pot ,circu
lating pump on high level.
.
1.1.2 System Performance Required
+ 2%
.
1.1.3 .Accomplishment of Function
The level in the tank is sensed,by a displacer type level transmitter which sends a 3-15 psig air signal to a 0-100% indicator on the control panel as well as a field, mounted 0-100% indicator. This signal also sends an air.signal to two pressure switches in the field panel. One switch is for low alarm-and the other operates a relay which shuts down pump 1-306 and gives an alarm on high level.
NOTE.: . ..
On MCS-1016 operation, the level transmitter is calibrated .
to read 100% with the tank 100% full. Due to the difference-
in gravity on "mono" operation, it will read 75% with the
tank full. Therefore, during "mono" operation, it will be
necessary to use a factor of 1.33 X's indicator reading to
obtain- correct level %.
,
PCB-ARCH-EXT0373567
INSTRUMENT FUNCTION OUTLINE
TITLE RESIDUE TANK LEVEL
SHEET
2
OF
5
,
DEPARTMENT
2 46
LOOP NUMBER
312-3
CLASSIFICATION LIA-312-3
2.0-
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A. - Transmitter
A. Transmitter
.
'
' Location: On top of the residue .tank, east end.
Fisher Gov. 2500T Displacer 125" Long x 3/4" Extension-8.5
Air Supply: 20 PSIG
.
Scale:
0-100' Linear
' Output:.. . 3-15 PSIG
Calibration:
'
0 Grams = 3 PSIG 1060 Grams = 15 PSIG
B. Indicator .
.. .
Torque Tube K-Monel 1
Location:. On panel board in
control room.
.
B.
. Scale:
0-10 Linear
. ..
Input:
3-15 PSIG
.
C. , Mercoid Switches (2- High and Low Levels).
Location: Inside furnace field
cabinet. .
.
C.
IMPO -127
.'
Fisher Porter Ind. Controller
Model 51-1310
Input
3-15 psi
.
Output 3-15 psi
Action Reverse
IMPO - 126
.
Switches
Set Point: High: 14 PSIG Set. Point: Low: 4 PSIG '
' Mercoid Mod. AP 153-R 36
PCB-ARCH-EXT0373568
V>
Ac 2. 2
t-3
cr r. b 2 O ci-5 2
tr
PCB-ARCH-EXT0373569
i. i i\u. ..ajiNl X r ui'jL x i. vJ W ouilj.. ..
TITLE RESIDUE TANK LEVETj
SHEET 4 WRITTEN BY
OF
5
DATE
3.0 OPERATION OF LOOP
REV.BY .
t . is X-> L
i
i'l i.
--
`
LOOP NUMBER' 312-3 '
CLASSIFICATION LIA--312-3
DATE ,
REV.NO.
3.1 NORMAL OPERATION
3.1.1 Start-Up Instructions
-
.
No special instructions, k
' .'
3.1.2 Shut-Down Instructions
' .
Do not allow the high-level interlock to shut down the circulating .
pump on the column pot.
.
3-1.3 Normal Operating instructions
.
It is necess.ary to watch only the level indicator to be sure it
appears to be working.
.
.
-3.1.4 Routine Checks Required
Watch the level indicator as often as necessary to keep-from pumping
too much into the tank and from pumping the tank empty.. .Some liquid
should be left in the tank for circulation, usually around 10%
(1.0- on the indicator scale) . . . ' ' .
.
.
PCB-ARCH-EXT0373570
TITLE RESIDUE TANK T.F.VET._________ ____
`
LOOP NUMBER- 312-3__________
SHEET
5.
OF
WRITTEN BY__________
5
.
CLASSIFICATION LIA-312-3___
DATEJCEV. BY__________
DATE
REV. NO .
3.0 OPERATION
. .
'
'
3.1- NORMAL OPERATION
.
.
Typical level indicator loop.
.
3.2 INTERLOCKS
,
.
.3.3 ABNORMAL OPERATIONS
.
3-3.1 Air Failure
-
Air failure' to this loop will cause loss of indication and .an alarm
indicating low level.
'
3.3.2 Power Failure
'
Power failure to the loop will cause the annunciator to be.inoperative
and. pump 1-3 06 will shut down.
...
PCB-ARCH-EXT0373571
INSTRUMENT FUNCTION OUTLINE
-
D E P A i U' ME N T
24 6 ,
TITLE FUEL OIL. STORAGE .TANK LEVEL '
'
LOOP NUMBER- 316-1
SHEET
1.
OF
5
.
WRITTEN BY -V.' Brawley DATE 5/8/7 2. REV BY
CLASSIFICATION LI 316-1
DATE
REV. NO'.
1.0 NEED FOR LOOP
.
'
A level gauge- is needed for proper oil inventory control. Fuel.oil
. is needed as back-up fuel for the- reboiler operation.
1.1 DESCRIPTION OF LOOP
' '
1.1.1 Function
'
'
The function of this loop is to provide an indication of the level
.
of oil in-the fuel oil storage tank and to actuate an alarm upon
high or low level.
;
1.1.2 System' Performance - Required
'
+2%
"
.
1.1.3. . Accomplishment of Function,.
'
- The level in the fuel oil tank is sensed by a diaphragm type level
transmitter which sends a 3--15 psig proportional signal to a 0-100%
. indicator mounted near the tank. This signal is also sent to
two pressure switches mounted in the' field panel which-' actuate an
alarm on high or low level.
.
"
PCB-ARCH-EXT0373572
INSTRUMENT FUNCTION OUTLINE HUB FUEL OIL. STORAGE TANK. LEVEL
SHEET
2
OF
____
DEPARTMENT . LOOP NUMBER
246 316-1.
CLASSIFICATION LI-316-1
2.0
' . COMPONENT AND CALIBRATION- DATA
OPERATING DATA A. Transmitter
MECHANICAL DATA' A. Transmitter
Location: Bottom of the storage tank, east side.
Scale: 0-100 Linear Span: 0-205" Ho0 Air Supply: 20- PSIG Output: 3-15 PSIF
.. Foxboro 13FA
.
Range: 0-205" HO
Output: 3-15 PSIG
IPMOi 001
B. Alarms
B. Mercoid Switches (2- High & Low Levels).
'Location: Inside the furnace field cabinet.
Mercoid AP-153-R36
High: 14 PSIG
Low:
4 PSIG-
IMPO: 250
Set Point: High-14 PSIG Set Point: Low - 4 PSIG
PCB-ARCH-EXT0373573
' '" T T T . n n m o t t o w n .i
S cn
/
JMO KW
>-3 w
3 i-3
Wz
to , K
U)
O
cn
:-3
O
D
O M
^3 td
>3 >
i--i
M !M< it-*
< KW
n n
t f.Trrc
O tr1
l-1 O U> O > cn >x>
-3 cn
MM Z
c H
O> w
H
o z M
u> I--1
CT)
HI
z LIO
o
PCB-ARCH-EXT0373574
, t INS i. Kur ir.Nl r unuj-iUN OU'iLj.i'i..
um < .. iimi i. r ;i o
TITLE FUEL OIL' STORAGE TANK LEVEL ' ' '
SHEET
4 .
WRITTEN BY
OF
5
. DATE
3.0 OPERATION OF LOOP
.
REV.BY
LOOP NUMBER; 316-1
CLASSIFICATION LI-316-1
DATE
REV.NO.
3.1
normal Operation
'3-1-1 Start-Up Instructions
.
.
None
'
3-1-2 .Shut-Down Instructions
. None
'
3.1.3 Normal Operating Instructions .
' ,
Level indicator should be between 10 and 90%.
3.1.4 Routine Checks Required
.
.
Check 'level indicator at least one time a shift.
PCB-ARCH-EXT0373575
. INSTRUMENT i- UNCTION 0UTLju^L
-- 1-- " ~
TITLE FUEL OIL STORAGE TANK LEVEL ' '
SHEET
5 .
OF
5
. ..
WRITTEN BY ____________ _DATE__REV BY
DLPRRiTiEN.I
2-io
__
-jKo- l
LOOP NUMBER 3&-l
CLASSIFICATIONLI-316-1
' ,
DATEREV. NO . _
,3.0 3.1
3.2
OPERATION NORMAL OPERATION Typical level loop. INTERLOCKS
' '
.
. '
' .
'
,' "
.
'
3.3.
None . .
'.
'
.
,
ABNORMAL OPERATIONS
;
3.3.1 Air Failure
.
Air failure to the loop will cause loss- of indication and low level alarm.
3.3.2. Power .Failure
.
. ,
Power failure will cause alarm tp he inoperative.
.
-
PCB-ARCH-EXT0373576
TITLE LIME.SLURRY TANK LEVEL________
SHEET ' 1
' OF' ,
5
WRITTEN. BY v Brawley DATE~5/l7/7 2 ~ REV. BY
LOOP NUMBER 320-1_________
CLASSIFICATION LI-3,20-1
DATE______
REV . NO .
1.0 -NEED FOR LOOP
, The level indicator on the lime slurry tank is needed to assure the
.
necessary amount of slurry is continuously being used from the tank
' and to prevent overflowing the tank.
.
1.1 DESCRIPTION OF LOOP
.
.'
'.
.
1.1.1 Function
'
The function of this loop is to measure and indicate the level of
slurry in the lime slurry tank. ' .
1.1.2 System Performance Required + 2%
'
.
1.1.3, Accomplishment of Function
,
A displacer type level transmitter senses the level and sends a
3-15 PSIG signal to a receiver gauge, mounted near the vessel, which
reads a 0-100% level. Also a level gauge, is mounted.in the control
room. .
.
'.
'
PCB-ARCH-EXT0373577
INSTRUMENT' FUNCTION OUTLINE
' TITLE LIME SLURRY TANK LEVEL
SHEET
2
OF ____ 5
DEPARTMENT LOOP NUMBER CLASSIFICATION
246 320-1 . LI-320-1
2.0
COMPONENT AND CALIBRATION DATA
' '
OPERATING DATA
Ay Transmitter
.
MECHANICAL DATA
A. Transmitter
" \Location: On top of the lime, slurry tank, 2nd floor.
Air Supply: 20 .PSIG.
B. &C. Gauges , (0-100%)
Fisher Level-Trol
.
Model 2500 T-249 BP
Calibration: 0 grams = 3 PSIG
.
1510 grams = 15 PSIG
Location: 1 on top of the tank, `the other on the panel board -in control- room.
Displacer Extension
60" x 1-1/4" 304 S.S 17 inches
.
I.PMO 127
PCB-ARCH-EXT0373578
TITLE LIME SLURRY TANK LEVEL
SHEET
3
WRITTEN BY'
' OF
S
'DATE
' REV.BY
LOOP NUMBER 320-1
CLASSIFICATION LI-320-1
DATE
REV.NO.
I NSTf? NS LT 320-1 OUTPUT 3-15 PSIG
'
0.
LT
320-1
l*tc
OVI 2417
1 14
P!LL OF MATERIAL
f O HO
2417.9-
C
-- *!<* toO Cu *>
0020
FISHER MOD 2S00T- 2496P
T s FTmL
aa n
f r t f"7?
:
.
*PIC
. ^ O HO
. DSCINT>H
* jjtvsaSEESKEigi^ vtov' cn~i7'Jt-irr.-.T nvn
LOOP
INSTRUMENT
20 1 I 3
- 1
SCHEMATIC
'
DIAGRAil
.
rynCT o. LEVEL INO.OF ITEM 320
[
Cl'* NO
no trfnfNce
.
| 24 17
15 D
Kn ivwto to i
PCB-ARCH-EXT0373579
TITLE LIME SLURRY TANK LEVEL
LOOP NUMBER- 320-1
SHEET' ' 4 WRITTEN BY
OF
5
. DATE
REV.BY
CLASSIFICATION LI-320-1'
DATE
REV.NO.
3.0 OPERATION OF LOOP
..
. . ':
..
.
3.1 NORMAL OPERATION
'
.
'
3.1.l'- Start-Up -Instructions .
.
..
None
"
.
.
.
3.1.2 'Shut-Down Instructions
,
. `
' None
.
'
\
.
3.1.3 Normal Operating Instructions
.
'
. .
. Level normally is between 50 and 8 0%.
3.1.'4 . Routine Chocks Required-
Each shift the level is to be checked frequently to be sure the proper
amount of lime slurry is being fed into the crude.
'
.
PCB-ARCH-EXT0373580
TITLE LIME SLURRY TANK LEVEL
' ,
LOOP NUMBER-
320-1
SHEET 5 . WRITTEN BY_
OF
5
DATEREV. BY
3.0 OPERATION .
CLASSIFICATION LI-320-1
_______ DATE ;
REV. NO .
'
:
3.1. NORMAL OPERATION '
'
.
..
Typical level .indicator loop '
3.2 INTERLOCKS
.
.
.
. .
'
. '
None .
3.3 ABNORMAL OPERATIONS
. . 3.1.1 Air Failure
.
.
.
'
'
'
. . Upon air failure there will be no indication of level.
'
PCB-ARCH-EXT0373581
INSTRUMENT FUNCTION OUTLINE
DLr aH'IMENT.
`i O
TITLE ..TEMPERED WATER . .CQNT.EQLLEH.
LOOP NUMBER- 3 25-3
SHEET
1
OF -
5
1
.
CLASSIFICATION TIC-325-3
WRITTEN BY V. Brawley DArfE~5/19/72 REV-.BY_______ ________ DATE__ REV.NO.
1.0 NEED FOR. LOOP :
.
' '
' This loop is needed to provide the necessary temperature for. proper condensation of vapors in the column condenser.
1.1 DESCRIPTION OF LOOP
.
.
i-i-i Function
.
.
The function.of this loop is to maintain a constant temperature of
the cooling water to the column condensor and to actuate an alarm
on high temperature @70C.
.
1.1.2 System Performance Required
.
The temperature should be maintained + 5C. of set point (65C.).
1-1-3 Accomplishment of Function-
The temperature in the water line is sensed by a temperature
indicating controller using a capillary bulb sensing element. The
controller,compares this temperature with a set point and sends a
3-51 psig air signal to a control valve to compensate for variations
.from the set point. As hot water leaves via the control Valve, cold
city make-up-water enters the system in equal volume.
PCB-ARCH-EXT0373582
' INSTRUMENT FUNCTION OUTLINE
IITI TEMPERED WATER CONTROLLER
SHEET
2.
OF
5
DEPARTMENT LOOP NUMBER CLASSIFICATION
24 6 325-3 TIC-325-3
2.0
COMPONENT AND CALIBRATION DATA
operating DATA
MECHANICAL DATA
A. Controller
.
A; Controller
Location: Ground level at north side of the column.
Air Supply: .Output:
Scale:
20 PSIG 3-15 PSIG 0-100 Linear
" SetPoint:
1016 - 65C.
.
'
.
'
MONO 8 00 C.
-
. Alarm is on the controller.
.
'
Taylor 44D RM
Range: 0-100C.' .
.
. Output: 3 - 15 PSIG
Alarm S.W. - N.C. opens at 90C.
IPMO 087
.
'
B. "
B. Thermocouple
/
. Location: In the circulating pump discharge line about 6 feet above the controller.
L Valve (ACV)
Location: By flash tank, S.W. of
water break tank. About 12 feet
from ground level.
.
. Action: Air to close.
.
C. , Valve
.
.
Fisher Gov..657A
Body: 1-1/2" Iron Body
.
Trim: 416 S.S. 17-4P-1-7/8"
Linear Cage
IPMO-12 6
PCB-ARCH-EXT0373583
PANEL
FIELD
LINE N CWI-F2C2-2
TEMPERED WATER CIRC, PUMP y UJSTR.N5 TV3Z5-3
ACTIONj: AIR TO CLO^E-
: o = -w :ATiO.'nI : PLATFORM
col so/ north oio-:-
i
.
-A
FROM EXISTING CITT WATER
A
B
MI-TEMP ALARM (-- SEE DWG.24IJE2I
S OUT IN 1
ias>_4s_TTT
CO f-3
td M H 2
H td h3 CO
H3 td -1-3 i-3 td 2
td td t-3td . .
S3
t-5
td C 3T
td 2
H
OJ
td td td
O.
G 2
O
tM3
OTd
t3
td
o 2
O
OC
o 2
i_p
tMd
Ol td
TO (302J
o
2 td
;--I
COLUMN
2
CONDENSER
l-J
td
LINE N2 . I-32S-I-F2C2-6'
TJtZT] P 6. *<3. AM AO. OJAis 2417 24 1 7- S-
T ICA .3 2 5-3
1
TV 3 2 5- 3
1
43 oooa 30 COTO
tOi. Cr CATS3AS.
TAYLOI! W0H.V4 I DM ll? 3S2- It'd
FI Shi W
t.5/-A.Tf MPV
CONTf.OL V/.l-Vf
0**4 . r**A:
_ ______ ' ______ _I___
-VA
INSTR N TICA325-3
SCALE: O-IOO^C LIN. output: 3-is psig
FROM (32 5) TEMPEREDWATER CIRC. PUWP
ACTION: f/.EAS INC. OUTPUT DEC.
sw. action': me as i'nc. sw. opens (hi alarm)
SET PT. 90`C
lo:atiokUT"/tTl &if/.,uortm sips cai.zoi
O td c
r" L_-w.
cx~juio cc-paht
" td o td >o
ctxi.Ai tscuitssc KPWU!asT. st. iocs. sa*i
CO CO
Td
>
M 2H
2 G2
M s td
r -- O (
=
O ti> 2
> td i-3
t-3 td
M
IMc no. TKA S / r11 -so_._l_h_a_h_c__u_a_g_a_s_____
o 2
CjJ
ro
-'.`.'-T. -_J 0 _1_Tj_m___ JjL5
NJ
*0
T3 Ln CP>
2*117
10 A
Hi O L*J
LO iV>
Ln
OJ
TITLE TEMPERED WATER CONTROLLER
. .
LOOP NUMBER- 325-3
SHEET
4.
OF
WRITTEN BY_____________
5 DATE_________
REV. BY
CLASSIFICATION TIC-325-3 . ___________ DATEREV. NO .____ _
3.0 OPERATION OF LOOP
,
'
.
'
3.1 NORMAL OPERATION
' 3,1.1 Start-Up Instructions
. .
The tempered water system must be full of water and the water supply
.
pump must be on. This system must be in operation before the reboiler
furnace is put into operation. -
..
3<12 Shut--DownInstructions
.
-
.
The reboiler furnace must be off before shutting this system down.
It is also advisable to close the dead-head valve at the vacuum jet.
3,1,3 Normal Operating Instructions
The circulating pump will be running. The water supply pump will.be
running'and the temperature at set point. The set points' are:
6 50 C. - MONO - 8 0 C.
...
:
3.1.4 Routine Checks Required
.
' Check the multipoint recorder frequently to be sure the temperature
. is under control.
'
'
'
PCB-ARCH-EXT0373585
INS tiu.irNT F ti-jL rrUN OUTLiiu,
TITLE TEMPERED WATER CONTROT,LE R.
SHEET
5
WRITTEN BY
OF'
5
. DATE
REV.BY
jj L> i. ' /1l i iLu t'i J.i1
z; '-1 u
- -
LOOP NUMBER- 325-3
CLASSIFICATION TIC-325-3
DATE
REV.NO.
.3.0 OPERATION '
.
. .
'
3.1- 'NORMAL OPERATION'
'
'
;
Typical local temperature control loop.
3.2, INTERLOCKS
3.3 ABNORMAL. OPERATIONS
3.3.1,
Air Failure
.
.
-.
.
Air failure to the loop will, cause'the control valve to open.
. 3.3.2 , Power Failure
,
. '
'
Loss of power-will cause the alarm to be inoperative.
,
PCB-ARCH-EXT0373586
INSTRUMENT FUNCTION. OUTLINE
. .
DEPARTMENT
246
TITLE LIGHT ENDS RECEIVER LEVEL '
.
LOOP NUMBER; 328
SHEET
1.
OF
WRITTEN BY V. Brawlev
.
1.0 NEED FOR LOOP
. 5 DATE 5/22/72
.
.
N , .* /..
REV .BY VI.
.
-J
""
.
'
.
CLASSIFICATION LIA-328
DATS
1 ^ REV. NO .
. `
' ;.
Reliable level measurement is essential in this receiver.for proper
balance.of light ends received from the column and LE's feed to the
.
chlorinators. . .
. .
'
'
.
1.1 DESCRIPTION OF LOOP
'
.
'
'
1-1 ! Function .
.
The function -of this instrument is to measure and indicate .the level,
of material in the light ends receiver and to provide an alarm on.
high or.low level. ,
.
.
.
l-l-2 System Performance Required
, ..
+ 2% .
'
'
'
.
1.1.3 Accomplishment of Function
A diaphragm type level transmitter senses the liquid level.in the tank
and.sends a proportional 3-15 psig air signal to a 0-100% indicator
mounted near the transmitter. This signal is also sent to two pressure
switches in the field cabinet which are,set to provide an alarm at
.
the panel on high or low level.
.
PCB-ARCH-EXT0373587
INSTRUMENT FUNCTION OUTLINE
TITLE LIGHT ENDS RECEIVER LEVEL
SHEET .
2 ,;
OF
5
DEPARTMENT
246
LOOP NUMBER
328
CLASSIFICATION LIA-328 .
2.0
COMPONENT AND' CALIBRATION DATA
OPERATING DATA A. Transmitter . '
MECHANICAL DATA A. Transmitter
. Location: Ground level, north side
of tank.
...
Foxboro 13 FA Range-; 0-150" W.C.
Air Supply: 20 PSIG
Output: 3-15 PSIG
Span:
150V W.C.
IPMO: 001
Output.:
3-15 PSIG
B. Switches
. -
B. Mercoid Switches (2- One high and One Low Levels)
Location: Inside furnace field cabinet.
Mercoid AP-153-R36
High: 14.5 PSIG Low : 4 PSIG
Set Point-High: 14.5 PSIG
.
Set Point-Low:
4 PSIG
PCB-ARCH-EXT0373588
I PANEL
IN5TR N2 LA32&-I.I SET FT- I4-.S PSIG> ACTION) MEAS. iKJC
5W. OPENJS
FIELD FIELD CABINET
HI-LO LEVEL-
Alarm see
x
DiVCi 24H-E2I
INSTR Ns LA 328-1.C SET FT. 4PSIC-, .... ACTION MEAS . DEC.
SVJ. OPENS
<UA HO.
LtA i 328- 1
LA 326- l.t
i
LA
32feii^ i
|!*fC 2417
32 54.
54
BILL OF MATERIAL
*.o. h6
2417- 9
DlC*TlON
FOXQORO NOD. 13FAI- MK 0043 ' -3-.s `Level teams mittCr pwc, [mFRCOID won* AP- 153-R3b 2417 lit piT>5.ure 5W.ij.Cit
Dwc,
2417-114.
-
LIGHT ENDS RECEIVER.
A
O-IGOLINl.
ij
OUT
S
-z^r--<JAS
ur
SET
20 PSIGi
IN5TR. NQ LI A 32. 8-1
SPA.Nl- I SO ' V C.
OUTPUT 3-IS PSIGi.
*x>ATQCC*PA*r ` . .
t*TRAL FHC-S(RIHC DPARrfhT. ST LOUIS. msSODRl
* ***H'v (oM'iv C OH* CINNai -.** a**--
' m
Cj-h'i -s*
u .>< j"'i t.
>
IK -tr
> " tM-
* IN<^
A'*
M
I L*4I>>' I'Hl -W-*l
A** *** -pj' 're-*** a-m* #. i..-i < ;uhii - i** .< - >a
><
. 4*^ *-
tj
>-.t .*k .t-e'Oi** 13 -* - .
IN
i**
13 K *so INI
(u*< a " Nr-i-
<" J INM *
-N* *)' k-
- |N. > IA-
INSTRUMENT SCHEMATIC DIAGRAM
___ U1A 3 28-1
cc*-_LEyIMpIC ATTCTj^ ALACUyij IT. j/i;
H
c * * . _
__________
2 A 17 -T". "
ao
17....B...
______
"
Lr^i - ^ p A
PCB-ARCH-EXT0373589
INSTRUMENT. FUNCTION OUTLINE
TITLE LIGHT ENDS; RECEIVER LEVEL
.
SHEET . 4 . tfRITTEN BY_,
OF .
5
...... .
.
DATE_________ REV .BY ____ _
3.0, OPERATION OF LOOP
. .
3.. 1. NORMAL OPERATION
. Start-Up Instructions
.
None .
3.1.2. Shut-Down Instructions
'
. None
.
' '3.1.3
NormalOperatingInstructions
.
Unknown - tank not in service as of 5/72.
'
3.1.4 Routine ChecksRequired
'
. ' Unknown
.
DEPARTMENT
246
LOOP NUMBER 328
.
CLASSIFICATION LIA-328
DATE
. REV.NO.
PCB-ARCH-EXT0373590
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT 246
titleuight ENDS RECEIVER LEVEL
LOOP NUMBER 328
SHEET
5
JRITTEN BY
OF
5
DATE
REV. BY .
CLASSIFICATION LIA-328
DATE
REV.NO.
3.0
OPERATION
. .'
-
3.1
NORMAL OPE RATI ON
.
.
'
Typical level loop.
.. '
'
.
3,2- , INTERLOCKS
'
' :
.
' '
None . .
3;3
ABNORMAL OPERATIONS
.
'
.
. . . 3^3.1 Air Failure
-
.
. ' Air failure to the loop will cause loss of indication and the
low level alarm will actuate.
-
3.3.2 Power Failure
.
'
'
Power failure will cause alarms to be inoperative.
PCB-ARCH-EXT0373591
,,
. .i-of-iENI F'uWC'j.'xON QUTijj,..i.
u Lrj . !>/ inn i
` -
TITLE #2- INTERMEDIATE STORAGE LEVEL.
'
' LOOP NUMBER-
3 2 9-1
SHEET
1 .
OF
5
WRITTEN BY y. Brawl.ev DATE T/2 2 /7 2 REV - BY
O..0
NEED FOR LOOP
.
'
CLASSIFICATION LIA-329-1
DATE
REV.NO.
' . .
1>1
The still- pot is both batch charged and "chain" fed with Aroclors in
this tank. Accurate level measurement is essential for this very .
active in-process' tank for- smooth refining operations. .
.
DESCRIPTION. OF--LOOP
. .
.
1.1.1 Function
'
.
The function of this loop is to. measure and indicate the level of ' material -and to alarm on high level.,
' . 1.1.2 System Performance Required
.-
+ 2%
.
1.1.3 Accomplishment of Function' ...
-
'
,
.
A diaphragm type level transmitter senses the liquid level in the tank
and sends a proportional 3-15 psig air signal to a 0-100% indicator
on the panel and also one near the transmitter. This signal is,also
sent to a pressure switch which actuates an alarm on high level.
PCB-ARCH-EXT0373592
INSTRUMENT FUNCTION OUTLINE
TITLE #2 INTERMEDIATE STORAGE .LEVEL
SHEET
2.
OF
5
DEPARTMENT
246
LOOP NUMBER
329-1
CLASSIFICATION -J.,I Ar.3 2-1-1
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A.' Transmitter
A. Transmitter
Location: Bottom of tank, east side.
Air Supply: Output: . Scale: Span: Sp.Gr.: .
20 PSIG 3-15. PSIG 0-100 Linear 485" W.C. 1,25
Foxboro 13FA1
Range: Output:
0-344" W.C. 3-15 PSIG
IPMO - 001 '
B. Pressure Switch
B. Mer'co.id Switch
'Mercoid AP-153-R36
Location: In furnace field cabinet
Set Point: 14.5 PSIG on Rise
Set Point:. 14.5 PSIG (For high level alarm )
PCB-ARCH-EXT0373593
PCB-ARCH-EXT0373594
Xi\JS j. j\uixull' Jl1 1 UNv.-iiU'i QU l'L a
U I..I L 4*1 .L , Util X 240
TITLE \\2 INTERMEDIATE STORAGE LEVEL.
.
SHEET
4 .OF____________ ________ 5________
`WRITTEN BY
_______ , DATEREV.BY
LOOP NUMBER-3 2 9-1
CLASSIFICATION LIA-329-1
DATE
REV.NO.
3.0 OPERATION OF LOOP
.
. .
3.1 NORMAL OPERATION
'
3.1.1 Start-Up Instructions
None
3.1.2 Shut-Down Instructions
It may be necessary to shut down either the column (if the level is
low) or the continuous chlorinators (if the level is high) before
any work can be done to the transmitter. The tank must be completely
empty before the transmitter can be removed.
.
3.1.3 Normal Operating Instructions
..The level will be between 20% and 90%.
3.1.4 Routine Checks Required
.
Check the level frequently so the tank don't go empty (this' would
cause a loss of vacuum on the column and an emission), also so the
tank doesn't run. over.
.
i PCB-ARCH-EXT0373595
INSTRUMENT function outline
DEPARTMENT________ 246
TITLE #2 INTERMEDIATE STORAGE LEVEL
LOOP NUMBER '.329-1
SHEET.
5 ' OF 5
'
CLASSIFICATION LI A-3 2_9-l
WRITTEN BY_.
, DATEREV. BY__DATE
' REV. NO .
3.2 INTERLOCKS . .
.
.
'
.
None
'
.
3.3 ABNORMAL OPERATIONS
.
3.3.1. Air Failure
.
.
Air failure to the loop will cause loss of indication.
.
3.3.2 Power Failure
.
Loss of power will cause alarm to be inoperative.
.
NOTE: 'N2 is used to blanket the tank when making MONO. The zero of
'
level transmitter should be set after N.n blanketing system is in
' operation. N2 enters and is regulated @ 4" W.C. and relieves.at
7" W.C. . Since the low side is not compensated, it will be
- '
necessary to.run the zero elevated @ almost 5" W.C. ,
PCB-ARCH-EXT0373596
INSTRUMENT FUNCTION OUTLINE
,
DEPARTMENT
246
TITLE LIME SLURRY CONTROL VALVE TIMER
LOOP NUMBER;352-1
SHEET . 1 .
OF
WRITTEN BY y, Brawlev
t
'
1.0 NEED FOR LOOP
5 DATE r?/1 B/72~ REV. BY
'*
'
`
.
.. .
CLASSIFICATION KIC-352-1 DATEREV.NO.
Allow lime slurry to bo. mixed on a semi-continuous basis with the crude Aroclors on the way to intermediate'storage. Lime mixing on . this' basis is necessary to neutralize essentially all the HCL dissolved' in the Aroclors prior to charging the Aroclors to the still . pot. This in turn is required, to' minimize the potential of chloride stress corrosion cracking in.the 316.S.S. column.
1.1 : DESCRIPTION OF LOOP
..
- 1.1.1 Function ..
.
,
The function of this loop is to control the flow rate by lime slurry addition to the product going to intermediate storage.
. 1.1.2 ' System Performance Required'
+ 2%
' .
.
'
1.1.3 Accomplishment of Function
'
The flow rate- is'adjusted by two timers mounted on the panel which , control the amount of time a pneumatic, actuated ball valve is open
and how long it" is. closed each cycle. The valve is continuously cycled open and closed after the open-close selector switch is
turned to "open".
PCB-ARCH-EXT0373597
INSTRUMENT FUNCTION OUTLINE
TITLE LIME SLURRY CONTROL VALVE TIMER
SHEET 2__________________ OF
5
DEPARTMENT
246 '
LOOP NUMBER
352-1
CLASSIFICATION KIC-352-1
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
' ' MECHANICAL DATA
A. Flow Valve
Location: On stair landing, north' of #9 chlorinator on 2nd level
B. Solenoid Valve .
Location: On stair landing, north
of #9 chlorinator on 2nd level by
the flow valve.
-
C. Timers (2)
. 1 for seconds open 1 for minutes closed
Location:' On panel board in control room.
A. Flow Valve
'
' Hills McCanna F602CS PCS . 1/4" Chrom. Pit. Ball - Valve Operator = Ramcon
Model R35FS Air to Open
B. Solenoid Valve ASCO 8317A 35 110 V 11 Watts
C. ATC Timer 305D
PCB-ARCH-EXT0373598
instrument function outline
.
TITLE LIME SLURRY CONTROL VALVE TIMER
,
SHEET
3 OF
5
WRITTEN BY
. DATE
REV.BY
DEPARTMENT
246
LOOP number
352-1 . '
CLASSIFICATION KIC-352-1
DATE
REV.NO.
PCB-ARCH-EXT0373599
INSTRUMENT FUNCTION OUTLINE
'
.
DEPARTMENT246 ,,
TITLE LIME SLURRY 'CONTROL VALVE TIMER ..
LOOP NUMBER
- 3 52-1
SHEET
4
WRITTEN BY
I
' '
OF
5
. ________ DATE______
3.0. OPERATION OF LOOP
.
.
'
REV. BY
'
3.1 NORMAL OPERATION'
..
3.1.1 Start-Up Instructions
CLASSIFICATION KIC-352-1
DATE
REV .NO.
'
'
. .
'
.
, Continuous chlori'nators should be running, set the timers and turn
` the selector switch to "open".
.
' -3.1.2 'Shut Down Instructions
Set the selector switch on "closed". 3.1.3 Normal Operating Instructions . .
'
.
'
. The.light.on,the panel board will be- on.. The timers working and the
.level in the. lime slurry tank going down at a steady rate.
' 3,1.4 Routine Checks Required ' .
Check the above at least 4 times a shift to be sure the necessary
percent of slurry is being added.
.
'
PCB-ARCH-EXT0373600
INSTRUMENT FUNCTION.OUTLINE
DEPARTMENT
24 6
TITLE t.TMF. SLURRY CONTROL VAUV
SHEET
5
WRITTEN BY
OF
5
. DATE
.
REV,BY
LOOP NUMBER' 352-1
CLASSIFICATION KIC-352-1.
DATE
REV.NO.
3.0 OPERATION
.
.
' .
.
3.1 NORMAL OPERATION'
.
.
.
.
.The slurry timer is turned on during the time material is going to
intermediate storage from the chlorinators.
.
3.1.1 Start-Up. Instructions
.
.
Set "open" timer for number of seconds valve is to be open (0-6 sec.) . Set "cycle" timer for number of minutes.valve is to be closed (0-6 min.) Turn selector switch to "open" position.
3.2 .INTERLOCKS'
3.3 ' ABNORMAL OPERATIONS
' . '
'
'
3.3.1 Air Failure
: '
'
.
Upon air- failure valve will fail closed.
.
/
- 3,3.2 Power Failure
.
. .
.
Upon power failure valve will fail closed.
PCB-ARCH-EXT0373601
INSTRUMENT function outline
.
TITLE #2 & #3 ABSORBERS FLOW CONTROLLER '
SHEET
1 OF4
WRITTEN BY V. Brawlev DATE s/23/72
BY
DEPARTMENT246
LOOP NUMBER' 541-1
CLASSIFICATION FICA-541-1
DATE
REV.NO.
1.0 NEED FOR LOOP
.
.
1.1
This loop is needed to insure proper flow,of aroclor to. the absorbers. DESCRIPTION OF LOOP
.. 1.1.1 Function of Loop
. '
'
' .
The function of this loop is to control the flow of material into the absorbers and to sound an alarm if flow is too low.
. 1.1.2 . System Performance Required
.
'
.
The flow rate should be maintained'+ 1/2 GPM of set point.
Accomplishment of Function'
.
"
The flow rate is sensed by a differential.pressure transmitter
across an orifice plate in the line. The.transmitter sends a
. 3-15 psig air signal, to a flow indicating controller. The controller
compares this signal to a set point and sends a 3-15 psig air signal
to a control valve to compensate for.variation from set point. The
transmitter also sends an air signal to a pressure switch which
activates an alarm on low flow.
. .
.
.
/
PCB-ARCH-EXT0373602
INSTRUMENT FUNCTION OUTLINE
TITLE #2 & #3 ABSORBERS FLOW CONTROLLER
SHEET ___ 2 '
. OF_
.4
DEPARTMENT . LOOP NUMBER
CLASSIFICATION
2 46_________ 541-1 , FICA-541-1
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
'
MECHANICAL DATA '
A. FT-541-I Differential Press. Trans
Location: Ground'level, NE of
.Tank 530.-
,
Supply: 20 psig
Output: 3-15 psig
'
Flow:
0-15 gpra
Span:
0-100" W.C.
B. FIC-32 Flow Indicating Controller
Location: Panel
A. Foxboro Integral Orifice Diff.
Bress Trans. W/Piped & Mt'd.
Air Set W/Gauge .
"
-Model #: 13A-HS2
Range: 0-200 to 0-850" W.C.,
Calibrated Range: 0-400" W.C.
Body: 316 S.S,
. Process Conn: 1/2" NPT
.
- Orifice: .350" Bore
.316 S.S. .
Accuracy: 1/2%
'
' . Serial #: 1947915 '
Input: . Output:
Action
Supply:
3-15 psig 3-15 psig Inc. Input Dec. Output 20-psig
2. FV-32 Control. Valve-'
Location: 14' level, NE of Tank
530
. ,
. .
Input: 3-15 psig
Action: Air to Open
Fails Close
-.
IPMO: 001
.
B. Fisher & Porter Flow Ind. Controlle
Model #: 51-1351 ABEC
' .
- ' Range:
3-15 psig sq. rt.-
.
Scale:
0-100 sq. rt.
Prop. Band: 2-500%
'
Reset Rate: .02 to 5 min. '
. Accuracy: 1/2%
. .IMO:
.' '
IPMO: 165
-
C. Fisher Gov. Control Valve #667-BF
D. ' FSA-32 Pressure -Switch
Location; Panel
Input:
. 3-15 psig
Set Point: 33%
.
FCT: Lo. Flow Alarm-at 3.3 GPm .
^ SPOT Contact/115 V. , 10A
Actuator Size 30 Travel 3/4"
' 1" 15 0# Fig. 316- S.S. Body -
Packing Set 1U2546-0101
. 3/4" 316 S.S. Trim,-Micro-Flute
Valve Plug 2J7335-3507
.
: Valve Ring 1R1262-3507
Teflon Packing, Skirt-Top Guiding
Spare Valve S.C. 07-75671
IMO: 45
IPMO: 126
.
. Serial #.: 4435034 ' . '
.. - .
D. Barksdale Pressure Switch #DIT-H18^
Range: 0-18 psig .
Bronze Diaphragm: 1/4" IPS
Conduit Conn: 1/2" NPS
Setting Trips at 4.08# on drop
t
Stores Code; 44-73246
PCB-ARCH-EXT0373603
f
PCB-ARCH-EXT0373604
INSTRUMENT FUNCTION OUTLINE
X
" `
-
~ -......................
.....r - - n '
- 1"
TITLE #2 & #3 ABSORBERS FLOW CONTROLLER
DEPARTMENT
246'
-----------"------------------- *................ .................
LOOP NUMBER'
541-1
SHEET. 1TEN BY
OF DATE
REV. BY
CLASSIFICATION FICA-541-1 DATEREV. NO .
3.0 OPERATION OF LOOP
3.1 NORMAL OPERATION
.
. '
3.1.1: Start-Up Instructions
,
.
The column should be running, on 1016 , and ready to cut forward
from total reflux.
'
.
.
. 3.1.2 Shut-Down Instructions
'
.
The column must, be on total relfux, or down.
.
3.1.3 Normal Operating Instructions
The controller set point will be about 95 (14 gpm) during the 1st part of a run. ''After the reflux ratio changes the set point will be about 65 (9 gpm) on the controller. The flow is acutally split to send an equal amount of product through the two absorbers and flow is balanced sending a equal amount of flow through the two rotometers.
. 3.1.4 Route Checks Required
3.2 3.3
Check the level in the receiver frequently to hold it at 20%. Check
:the rotometers at least 2 times a shift to keep the flow equalized
''through the absorbers.
INTERLOCKS AND ALARMS
'. '
.
If the flow drops to about 3 gpm, the alarm will sound on the , annun ciator and the-window marked "low flow #2 & 3 absorber".
ABNORMAL OPERATION
.
. .
3.3.1 Air Failure
....
If the air fails, the valve will close and the alarm will sound.
3.3*2 Power Failure
.
If. the power fails, the alarm w i 1 l~'->n o.t^'S chin r?. i
3.3.3 Other
None
PCB-ARCH-EXT0373605