INSTRUMENT FUNCTION OUTLINE ' DEPakjlMENT 24b TITLE REBOILER:FURNACE COIL FLOW '' ' LOOP NUMBER- 3 0 7-5 SHEET l' . OF . 4 WRITTEN BY y. Brawley DATE 5/2 5/7-2 REV ..BY;- ' CLASSIFICATION FI-307-5 DATE__________________ ^REV. NO . 1.0 NEED FOR LOOP . .- ' . This loop is needed to shut down the furnace in case of low flow in . . the circulating line. Low flow would not give the proper heat transfer .needed for vaporization in the column and would cause' ' pluggage in the furnace circulating line-due to overheating. 1.1 ' DESCRIPTION OF. LOOP . ' ' ill Function The function of this loop is to indicate the flow rate of crude through the furnace coil and shut down the furnace burners in case of a minimum flow. . . 1.1.2 'Accuracy Required . . + 2% . ' ' - . ' 1.1.3 Accomplishment of Function ' ' ' . The circulating flow rate of crude through the furnace'coil is measured by an orifice plate. The flow rate shows on the indicator. At the low flow set point, the contact-in the indicator will open and energize a relay. The relay will shut down the furnace burners' and bring in an alarm. INSTRUMENT FUNCTION OUTLINE TITLE REBOILER FURNACE COIL FLOW. SHEET 2 ' OP 4 .______ DEPARTMENT ' 246 ' LOOP NUMBER 307-5 CLASSIFICATION FI-307-5 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A. Indicator & Switch A, Barton Flow Indicator Model 277 Location: North- side offurnace, 1st level. . .. Range: 0-105 (0-10.00 GPM) . ' Span: 0-5 0" H2O. Set Point: 25" H?0 ' (420 GPM or ' (4.20 on scale) Action: Contact to open on low flow. ' .* Liquid: SpGr. 1.3 Range: 0-105 = 0-50" W.C. Contacts - Open on low flow.. IPMO - 257 C. Relay - ' . Allen Bradley 70ON . B. Orifice (FE-3 07-5)' Location': 7 feet above the indicator. Size; 520 Plate L Relay (#10 CR) Location: Inside furnace field cabinet. . . . . PCB-ARCH-EXT0373564 INSTRUMENT FUNCTION OUTLINE TITLE REBOILER FURNACE COIL FLOW . SHEET________ 3 OF ________4 ' ' Written by_Date________ _Rev. by DEPARTMENT 246 LOOP NUMBER 3 07-5 CLASSIFICATION FI-307-5 Date Rev. Number To Pot PCB-ARCH-EXT0373565 INSTRUMENT FUNCTION OUTLINE DEPARTMENT 246 TITLE REBOILER FURNACE. COIL FLOW LOOP NUMBER- .3 07-5 SHEET 4. OF 4 CLASSIFICATION FI-307-5 WRITTEN BY_DATEREV. BY___________ DATE .REV .NO. 3.0 . OPERATION OF LOOP . . ' . 3.1 NORMAL OPERATION .. . 3.1.1 Start-Up Instructions - - Crude must be circulating through the furnace coil. ' 3.1.2 Shut-Down Instructions The column must be on total reflux 0 all the burner off., . . 3.1.3 Normal Operating Instructions _ The indicator' will read 1,000 GPM. ' . 3.1.4 Routine Checks Required ... Check the indicator at least 2 times a shift. . .3.2 INTERLOCKS AND ALARMS . ' ' ' At low flow set .point (42 0 GPM) the furnace will shutdown and an - alarm will sound in the control room, the telalarm window "furnace ' . shutdown" will light. Also, an alarm will sound in the furnace . field cabinet. . . , 3 3 ABNO-RMAL OP E RAT I ON ' ' 3.3.1 Air Failure .. ' " ' Air failure will not affect this loop but the furnace will shut down due to other interlocks-. 3.3.2 Power Failure . :. ' . ' ' A power failure will shut this loop down. 3.3.3 Also see Drawings 2417, E5, 15, and IFO's FIC-307-1 and 3-307-1. PCB-ARCH-EXT0373566 INSTRUMENT -FUNCTION OU.TL1NE DEPARTMENT TITLE RESIDUE TANK LEVEL LOOP NUMBER- 312-3 SHEET 1. OF 5 WRITTEN BY V . Brawley DATE 5/18/72 REV.BY_________ CLASSIFICATION. LIA-312-3 DATEREV.NO . 1.0 NEED. FOR LOQP . ' Residue 'from 1-312 is fed to the existing No. 2 still for distillation. Surge tank level must be known prior to pumping residue from the still pot after a column run. . 1.1 DESCRIPTION OF`LOOP 1.1.1 .Function The function of this loop is to provide an indication of the residue tank level at both the control panel and in the field. Also to give an alarm on high or low level and to shutdown the column pot ,circu lating pump on high level. . 1.1.2 System Performance Required + 2% . 1.1.3 .Accomplishment of Function The level in the tank is sensed,by a displacer type level transmitter which sends a 3-15 psig air signal to a 0-100% indicator on the control panel as well as a field, mounted 0-100% indicator. This signal also sends an air.signal to two pressure switches in the field panel. One switch is for low alarm-and the other operates a relay which shuts down pump 1-306 and gives an alarm on high level. NOTE.: . .. On MCS-1016 operation, the level transmitter is calibrated . to read 100% with the tank 100% full. Due to the difference- in gravity on "mono" operation, it will read 75% with the tank full. Therefore, during "mono" operation, it will be necessary to use a factor of 1.33 X's indicator reading to obtain- correct level %. , PCB-ARCH-EXT0373567 INSTRUMENT FUNCTION OUTLINE TITLE RESIDUE TANK LEVEL SHEET 2 OF 5 , DEPARTMENT 2 46 LOOP NUMBER 312-3 CLASSIFICATION LIA-312-3 2.0- COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A. - Transmitter A. Transmitter . ' ' Location: On top of the residue .tank, east end. Fisher Gov. 2500T Displacer 125" Long x 3/4" Extension-8.5 Air Supply: 20 PSIG . Scale: 0-100' Linear ' Output:.. . 3-15 PSIG Calibration: ' 0 Grams = 3 PSIG 1060 Grams = 15 PSIG B. Indicator . .. . Torque Tube K-Monel 1 Location:. On panel board in control room. . B. . Scale: 0-10 Linear . .. Input: 3-15 PSIG . C. , Mercoid Switches (2- High and Low Levels). Location: Inside furnace field cabinet. . . C. IMPO -127 .' Fisher Porter Ind. Controller Model 51-1310 Input 3-15 psi . Output 3-15 psi Action Reverse IMPO - 126 . Switches Set Point: High: 14 PSIG Set. Point: Low: 4 PSIG ' ' Mercoid Mod. AP 153-R 36 PCB-ARCH-EXT0373568 V> Ac 2. 2 t-3 cr r. b 2 O ci-5 2 tr PCB-ARCH-EXT0373569 i. i i\u. ..ajiNl X r ui'jL x i. vJ W ouilj.. .. TITLE RESIDUE TANK LEVETj SHEET 4 WRITTEN BY OF 5 DATE 3.0 OPERATION OF LOOP REV.BY . t . is X-> L i i'l i. -- ` LOOP NUMBER' 312-3 ' CLASSIFICATION LIA--312-3 DATE , REV.NO. 3.1 NORMAL OPERATION 3.1.1 Start-Up Instructions - . No special instructions, k ' .' 3.1.2 Shut-Down Instructions ' . Do not allow the high-level interlock to shut down the circulating . pump on the column pot. . 3-1.3 Normal Operating instructions . It is necess.ary to watch only the level indicator to be sure it appears to be working. . . -3.1.4 Routine Checks Required Watch the level indicator as often as necessary to keep-from pumping too much into the tank and from pumping the tank empty.. .Some liquid should be left in the tank for circulation, usually around 10% (1.0- on the indicator scale) . . . ' ' . . . PCB-ARCH-EXT0373570 TITLE RESIDUE TANK T.F.VET._________ ____ ` LOOP NUMBER- 312-3__________ SHEET 5. OF WRITTEN BY__________ 5 . CLASSIFICATION LIA-312-3___ DATEJCEV. BY__________ DATE REV. NO . 3.0 OPERATION . . ' ' 3.1- NORMAL OPERATION . . Typical level indicator loop. . 3.2 INTERLOCKS , . .3.3 ABNORMAL OPERATIONS . 3-3.1 Air Failure - Air failure' to this loop will cause loss of indication and .an alarm indicating low level. ' 3.3.2 Power Failure ' Power failure to the loop will cause the annunciator to be.inoperative and. pump 1-3 06 will shut down. ... PCB-ARCH-EXT0373571 INSTRUMENT FUNCTION OUTLINE - D E P A i U' ME N T 24 6 , TITLE FUEL OIL. STORAGE .TANK LEVEL ' ' LOOP NUMBER- 316-1 SHEET 1. OF 5 . WRITTEN BY -V.' Brawley DATE 5/8/7 2. REV BY CLASSIFICATION LI 316-1 DATE REV. NO'. 1.0 NEED FOR LOOP . ' A level gauge- is needed for proper oil inventory control. Fuel.oil . is needed as back-up fuel for the- reboiler operation. 1.1 DESCRIPTION OF LOOP ' ' 1.1.1 Function ' ' The function of this loop is to provide an indication of the level . of oil in-the fuel oil storage tank and to actuate an alarm upon high or low level. ; 1.1.2 System' Performance - Required ' +2% " . 1.1.3. . Accomplishment of Function,. ' - The level in the fuel oil tank is sensed by a diaphragm type level transmitter which sends a 3--15 psig proportional signal to a 0-100% . indicator mounted near the tank. This signal is also sent to two pressure switches mounted in the' field panel which-' actuate an alarm on high or low level. . " PCB-ARCH-EXT0373572 INSTRUMENT FUNCTION OUTLINE HUB FUEL OIL. STORAGE TANK. LEVEL SHEET 2 OF ____ DEPARTMENT . LOOP NUMBER 246 316-1. CLASSIFICATION LI-316-1 2.0 ' . COMPONENT AND CALIBRATION- DATA OPERATING DATA A. Transmitter MECHANICAL DATA' A. Transmitter Location: Bottom of the storage tank, east side. Scale: 0-100 Linear Span: 0-205" Ho0 Air Supply: 20- PSIG Output: 3-15 PSIF .. Foxboro 13FA . Range: 0-205" HO Output: 3-15 PSIG IPMOi 001 B. Alarms B. Mercoid Switches (2- High & Low Levels). 'Location: Inside the furnace field cabinet. Mercoid AP-153-R36 High: 14 PSIG Low: 4 PSIG- IMPO: 250 Set Point: High-14 PSIG Set Point: Low - 4 PSIG PCB-ARCH-EXT0373573 ' '" T T T . n n m o t t o w n .i S cn / JMO KW >-3 w 3 i-3 Wz to , K U) O cn :-3 O D O M ^3 td >3 > i--i M !M< it-* < KW n n t f.Trrc O tr1 l-1 O U> O > cn >x> -3 cn MM Z c H O> w H o z M u> I--1 CT) HI z LIO o PCB-ARCH-EXT0373574 , t INS i. Kur ir.Nl r unuj-iUN OU'iLj.i'i.. um < .. iimi i. r ;i o TITLE FUEL OIL' STORAGE TANK LEVEL ' ' ' SHEET 4 . WRITTEN BY OF 5 . DATE 3.0 OPERATION OF LOOP . REV.BY LOOP NUMBER; 316-1 CLASSIFICATION LI-316-1 DATE REV.NO. 3.1 normal Operation '3-1-1 Start-Up Instructions . . None ' 3-1-2 .Shut-Down Instructions . None ' 3.1.3 Normal Operating Instructions . ' , Level indicator should be between 10 and 90%. 3.1.4 Routine Checks Required . . Check 'level indicator at least one time a shift. PCB-ARCH-EXT0373575 . INSTRUMENT i- UNCTION 0UTLju^L -- 1-- " ~ TITLE FUEL OIL STORAGE TANK LEVEL ' ' SHEET 5 . OF 5 . .. WRITTEN BY ____________ _DATE__REV BY DLPRRiTiEN.I 2-io __ -jKo- l LOOP NUMBER 3&-l CLASSIFICATIONLI-316-1 ' , DATEREV. NO . _ ,3.0 3.1 3.2 OPERATION NORMAL OPERATION Typical level loop. INTERLOCKS ' ' . . ' ' . ' ,' " . ' 3.3. None . . '. ' . , ABNORMAL OPERATIONS ; 3.3.1 Air Failure . Air failure to the loop will cause loss- of indication and low level alarm. 3.3.2. Power .Failure . . , Power failure will cause alarm tp he inoperative. . - PCB-ARCH-EXT0373576 TITLE LIME.SLURRY TANK LEVEL________ SHEET ' 1 ' OF' , 5 WRITTEN. BY v Brawley DATE~5/l7/7 2 ~ REV. BY LOOP NUMBER 320-1_________ CLASSIFICATION LI-3,20-1 DATE______ REV . NO . 1.0 -NEED FOR LOOP , The level indicator on the lime slurry tank is needed to assure the . necessary amount of slurry is continuously being used from the tank ' and to prevent overflowing the tank. . 1.1 DESCRIPTION OF LOOP . .' '. . 1.1.1 Function ' The function of this loop is to measure and indicate the level of slurry in the lime slurry tank. ' . 1.1.2 System Performance Required + 2% ' . 1.1.3, Accomplishment of Function , A displacer type level transmitter senses the level and sends a 3-15 PSIG signal to a receiver gauge, mounted near the vessel, which reads a 0-100% level. Also a level gauge, is mounted.in the control room. . . '. ' PCB-ARCH-EXT0373577 INSTRUMENT' FUNCTION OUTLINE ' TITLE LIME SLURRY TANK LEVEL SHEET 2 OF ____ 5 DEPARTMENT LOOP NUMBER CLASSIFICATION 246 320-1 . LI-320-1 2.0 COMPONENT AND CALIBRATION DATA ' ' OPERATING DATA Ay Transmitter . MECHANICAL DATA A. Transmitter " \Location: On top of the lime, slurry tank, 2nd floor. Air Supply: 20 .PSIG. B. &C. Gauges , (0-100%) Fisher Level-Trol . Model 2500 T-249 BP Calibration: 0 grams = 3 PSIG . 1510 grams = 15 PSIG Location: 1 on top of the tank, `the other on the panel board -in control- room. Displacer Extension 60" x 1-1/4" 304 S.S 17 inches . I.PMO 127 PCB-ARCH-EXT0373578 TITLE LIME SLURRY TANK LEVEL SHEET 3 WRITTEN BY' ' OF S 'DATE ' REV.BY LOOP NUMBER 320-1 CLASSIFICATION LI-320-1 DATE REV.NO. I NSTf? NS LT 320-1 OUTPUT 3-15 PSIG ' 0. LT 320-1 l*tc OVI 2417 1 14 P!LL OF MATERIAL f O HO 2417.9- C -- *!<* toO Cu *> 0020 FISHER MOD 2S00T- 2496P T s FTmL aa n f r t f"7? : . *PIC . ^ O HO . DSCINT>H * jjtvsaSEESKEigi^ vtov' cn~i7'Jt-irr.-.T nvn LOOP INSTRUMENT 20 1 I 3 - 1 SCHEMATIC ' DIAGRAil . rynCT o. LEVEL INO.OF ITEM 320 [ Cl'* NO no trfnfNce . | 24 17 15 D Kn ivwto to i PCB-ARCH-EXT0373579 TITLE LIME SLURRY TANK LEVEL LOOP NUMBER- 320-1 SHEET' ' 4 WRITTEN BY OF 5 . DATE REV.BY CLASSIFICATION LI-320-1' DATE REV.NO. 3.0 OPERATION OF LOOP .. . . ': .. . 3.1 NORMAL OPERATION ' . ' 3.1.l'- Start-Up -Instructions . . .. None " . . . 3.1.2 'Shut-Down Instructions , . ` ' None . ' \ . 3.1.3 Normal Operating Instructions . ' . . . Level normally is between 50 and 8 0%. 3.1.'4 . Routine Chocks Required- Each shift the level is to be checked frequently to be sure the proper amount of lime slurry is being fed into the crude. ' . PCB-ARCH-EXT0373580 TITLE LIME SLURRY TANK LEVEL ' , LOOP NUMBER- 320-1 SHEET 5 . WRITTEN BY_ OF 5 DATEREV. BY 3.0 OPERATION . CLASSIFICATION LI-320-1 _______ DATE ; REV. NO . ' : 3.1. NORMAL OPERATION ' ' . .. Typical level .indicator loop ' 3.2 INTERLOCKS . . . . . ' . ' None . 3.3 ABNORMAL OPERATIONS . . 3.1.1 Air Failure . . . ' ' ' . . Upon air failure there will be no indication of level. ' PCB-ARCH-EXT0373581 INSTRUMENT FUNCTION OUTLINE DLr aH'IMENT. `i O TITLE ..TEMPERED WATER . .CQNT.EQLLEH. LOOP NUMBER- 3 25-3 SHEET 1 OF - 5 1 . CLASSIFICATION TIC-325-3 WRITTEN BY V. Brawley DArfE~5/19/72 REV-.BY_______ ________ DATE__ REV.NO. 1.0 NEED FOR. LOOP : . ' ' ' This loop is needed to provide the necessary temperature for. proper condensation of vapors in the column condenser. 1.1 DESCRIPTION OF LOOP . . i-i-i Function . . The function.of this loop is to maintain a constant temperature of the cooling water to the column condensor and to actuate an alarm on high temperature @70C. . 1.1.2 System Performance Required . The temperature should be maintained + 5C. of set point (65C.). 1-1-3 Accomplishment of Function- The temperature in the water line is sensed by a temperature indicating controller using a capillary bulb sensing element. The controller,compares this temperature with a set point and sends a 3-51 psig air signal to a control valve to compensate for variations .from the set point. As hot water leaves via the control Valve, cold city make-up-water enters the system in equal volume. PCB-ARCH-EXT0373582 ' INSTRUMENT FUNCTION OUTLINE IITI TEMPERED WATER CONTROLLER SHEET 2. OF 5 DEPARTMENT LOOP NUMBER CLASSIFICATION 24 6 325-3 TIC-325-3 2.0 COMPONENT AND CALIBRATION DATA operating DATA MECHANICAL DATA A. Controller . A; Controller Location: Ground level at north side of the column. Air Supply: .Output: Scale: 20 PSIG 3-15 PSIG 0-100 Linear " SetPoint: 1016 - 65C. . ' . ' MONO 8 00 C. - . Alarm is on the controller. . ' Taylor 44D RM Range: 0-100C.' . . . Output: 3 - 15 PSIG Alarm S.W. - N.C. opens at 90C. IPMO 087 . ' B. " B. Thermocouple / . Location: In the circulating pump discharge line about 6 feet above the controller. L Valve (ACV) Location: By flash tank, S.W. of water break tank. About 12 feet from ground level. . . Action: Air to close. . C. , Valve . . Fisher Gov..657A Body: 1-1/2" Iron Body . Trim: 416 S.S. 17-4P-1-7/8" Linear Cage IPMO-12 6 PCB-ARCH-EXT0373583 PANEL FIELD LINE N CWI-F2C2-2 TEMPERED WATER CIRC, PUMP y UJSTR.N5 TV3Z5-3 ACTIONj: AIR TO CLO^E- : o = -w :ATiO.'nI : PLATFORM col so/ north oio-:- i . -A FROM EXISTING CITT WATER A B MI-TEMP ALARM (-- SEE DWG.24IJE2I S OUT IN 1 ias>_4s_TTT CO f-3 td M H 2 H td h3 CO H3 td -1-3 i-3 td 2 td td t-3td . . S3 t-5 td C 3T td 2 H OJ td td td O. G 2 O tM3 OTd t3 td o 2 O OC o 2 i_p tMd Ol td TO (302J o 2 td ;--I COLUMN 2 CONDENSER l-J td LINE N2 . I-32S-I-F2C2-6' TJtZT] P 6. *<3. AM AO. OJAis 2417 24 1 7- S- T ICA .3 2 5-3 1 TV 3 2 5- 3 1 43 oooa 30 COTO tOi. Cr CATS3AS. TAYLOI! W0H.V4 I DM ll? 3S2- It'd FI Shi W t.5/-A.Tf MPV CONTf.OL V/.l-Vf 0**4 . r**A: _ ______ ' ______ _I___ -VA INSTR N TICA325-3 SCALE: O-IOO^C LIN. output: 3-is psig FROM (32 5) TEMPEREDWATER CIRC. PUWP ACTION: f/.EAS INC. OUTPUT DEC. sw. action': me as i'nc. sw. opens (hi alarm) SET PT. 90`C lo:atiokUT"/tTl &if/.,uortm sips cai.zoi O td c r" L_-w. cx~juio cc-paht " td o td >o ctxi.Ai tscuitssc KPWU!asT. st. iocs. sa*i CO CO Td > M 2H 2 G2 M s td r -- O ( = O ti> 2 > td i-3 t-3 td M IMc no. TKA S / r11 -so_._l_h_a_h_c__u_a_g_a_s_____ o 2 CjJ ro -'.`.'-T. -_J 0 _1_Tj_m___ JjL5 NJ *0 T3 Ln CP> 2*117 10 A Hi O L*J LO iV> Ln OJ TITLE TEMPERED WATER CONTROLLER . . LOOP NUMBER- 325-3 SHEET 4. OF WRITTEN BY_____________ 5 DATE_________ REV. BY CLASSIFICATION TIC-325-3 . ___________ DATEREV. NO .____ _ 3.0 OPERATION OF LOOP , ' . ' 3.1 NORMAL OPERATION ' 3,1.1 Start-Up Instructions . . The tempered water system must be full of water and the water supply . pump must be on. This system must be in operation before the reboiler furnace is put into operation. - .. 3<12 Shut--DownInstructions . - . The reboiler furnace must be off before shutting this system down. It is also advisable to close the dead-head valve at the vacuum jet. 3,1,3 Normal Operating Instructions The circulating pump will be running. The water supply pump will.be running'and the temperature at set point. The set points' are: 6 50 C. - MONO - 8 0 C. ... : 3.1.4 Routine Checks Required . ' Check the multipoint recorder frequently to be sure the temperature . is under control. ' ' ' PCB-ARCH-EXT0373585 INS tiu.irNT F ti-jL rrUN OUTLiiu, TITLE TEMPERED WATER CONTROT,LE R. SHEET 5 WRITTEN BY OF' 5 . DATE REV.BY jj L> i. ' /1l i iLu t'i J.i1 z; '-1 u - - LOOP NUMBER- 325-3 CLASSIFICATION TIC-325-3 DATE REV.NO. .3.0 OPERATION ' . . . ' 3.1- 'NORMAL OPERATION' ' ' ; Typical local temperature control loop. 3.2, INTERLOCKS 3.3 ABNORMAL. OPERATIONS 3.3.1, Air Failure . . -. . Air failure to the loop will, cause'the control valve to open. . 3.3.2 , Power Failure , . ' ' Loss of power-will cause the alarm to be inoperative. , PCB-ARCH-EXT0373586 INSTRUMENT FUNCTION. OUTLINE . . DEPARTMENT 246 TITLE LIGHT ENDS RECEIVER LEVEL ' . LOOP NUMBER; 328 SHEET 1. OF WRITTEN BY V. Brawlev . 1.0 NEED FOR LOOP . 5 DATE 5/22/72 . . N , .* /.. REV .BY VI. . -J "" . ' . CLASSIFICATION LIA-328 DATS 1 ^ REV. NO . . ` ' ;. Reliable level measurement is essential in this receiver.for proper balance.of light ends received from the column and LE's feed to the . chlorinators. . . . . ' ' . 1.1 DESCRIPTION OF LOOP ' . ' ' 1-1 ! Function . . The function -of this instrument is to measure and indicate .the level, of material in the light ends receiver and to provide an alarm on. high or.low level. , . . . l-l-2 System Performance Required , .. + 2% . ' ' ' . 1.1.3 Accomplishment of Function A diaphragm type level transmitter senses the liquid level.in the tank and.sends a proportional 3-15 psig air signal to a 0-100% indicator mounted near the transmitter. This signal is also sent to two pressure switches in the field cabinet which are,set to provide an alarm at . the panel on high or low level. . PCB-ARCH-EXT0373587 INSTRUMENT FUNCTION OUTLINE TITLE LIGHT ENDS RECEIVER LEVEL SHEET . 2 ,; OF 5 DEPARTMENT 246 LOOP NUMBER 328 CLASSIFICATION LIA-328 . 2.0 COMPONENT AND' CALIBRATION DATA OPERATING DATA A. Transmitter . ' MECHANICAL DATA A. Transmitter . Location: Ground level, north side of tank. ... Foxboro 13 FA Range-; 0-150" W.C. Air Supply: 20 PSIG Output: 3-15 PSIG Span: 150V W.C. IPMO: 001 Output.: 3-15 PSIG B. Switches . - B. Mercoid Switches (2- One high and One Low Levels) Location: Inside furnace field cabinet. Mercoid AP-153-R36 High: 14.5 PSIG Low : 4 PSIG Set Point-High: 14.5 PSIG . Set Point-Low: 4 PSIG PCB-ARCH-EXT0373588 I PANEL IN5TR N2 LA32&-I.I SET FT- I4-.S PSIG> ACTION) MEAS. iKJC 5W. OPENJS FIELD FIELD CABINET HI-LO LEVEL- Alarm see x DiVCi 24H-E2I INSTR Ns LA 328-1.C SET FT. 4PSIC-, .... ACTION MEAS . DEC. SVJ. OPENS <UA HO. LtA i 328- 1 LA 326- l.t i LA 32feii^ i |!*fC 2417 32 54. 54 BILL OF MATERIAL *.o. h6 2417- 9 DlC*TlON FOXQORO NOD. 13FAI- MK 0043 ' -3-.s `Level teams mittCr pwc, [mFRCOID won* AP- 153-R3b 2417 lit piT>5.ure 5W.ij.Cit Dwc, 2417-114. - LIGHT ENDS RECEIVER. A O-IGOLINl. ij OUT S -z^r--<JAS ur SET 20 PSIGi IN5TR. NQ LI A 32. 8-1 SPA.Nl- I SO ' V C. OUTPUT 3-IS PSIGi. *x>ATQCC*PA*r ` . . t*TRAL FHC-S(RIHC DPARrfhT. ST LOUIS. msSODRl * ***H'v (oM'iv C OH* CINNai -.** a**-- ' m Cj-h'i -s* u .>< j"'i t. > IK -tr > " tM- * IN<^ A'* M I L*4I>>' I'Hl -W-*l A** *** -pj' 're-*** a-m* #. i..-i < ;uhii - i** .< - >a >< . 4*^ *- tj >-.t .*k .t-e'Oi** 13 -* - . IN i** 13 K *so INI (u*< a " Nr-i- <" J INM * -N* *)' k- - |N. > IA- INSTRUMENT SCHEMATIC DIAGRAM ___ U1A 3 28-1 cc*-_LEyIMpIC ATTCTj^ ALACUyij IT. j/i; H c * * . _ __________ 2 A 17 -T". " ao 17....B... ______ " Lr^i - ^ p A PCB-ARCH-EXT0373589 INSTRUMENT. FUNCTION OUTLINE TITLE LIGHT ENDS; RECEIVER LEVEL . SHEET . 4 . tfRITTEN BY_, OF . 5 ...... . . DATE_________ REV .BY ____ _ 3.0, OPERATION OF LOOP . . 3.. 1. NORMAL OPERATION . Start-Up Instructions . None . 3.1.2. Shut-Down Instructions ' . None . ' '3.1.3 NormalOperatingInstructions . Unknown - tank not in service as of 5/72. ' 3.1.4 Routine ChecksRequired ' . ' Unknown . DEPARTMENT 246 LOOP NUMBER 328 . CLASSIFICATION LIA-328 DATE . REV.NO. PCB-ARCH-EXT0373590 INSTRUMENT FUNCTION OUTLINE DEPARTMENT 246 titleuight ENDS RECEIVER LEVEL LOOP NUMBER 328 SHEET 5 JRITTEN BY OF 5 DATE REV. BY . CLASSIFICATION LIA-328 DATE REV.NO. 3.0 OPERATION . .' - 3.1 NORMAL OPE RATI ON . . ' Typical level loop. .. ' ' . 3,2- , INTERLOCKS ' ' : . ' ' None . . 3;3 ABNORMAL OPERATIONS . ' . . . . 3^3.1 Air Failure - . . ' Air failure to the loop will cause loss of indication and the low level alarm will actuate. - 3.3.2 Power Failure . ' ' Power failure will cause alarms to be inoperative. PCB-ARCH-EXT0373591 ,, . .i-of-iENI F'uWC'j.'xON QUTijj,..i. u Lrj . !>/ inn i ` - TITLE #2- INTERMEDIATE STORAGE LEVEL. ' ' LOOP NUMBER- 3 2 9-1 SHEET 1 . OF 5 WRITTEN BY y. Brawl.ev DATE T/2 2 /7 2 REV - BY O..0 NEED FOR LOOP . ' CLASSIFICATION LIA-329-1 DATE REV.NO. ' . . 1>1 The still- pot is both batch charged and "chain" fed with Aroclors in this tank. Accurate level measurement is essential for this very . active in-process' tank for- smooth refining operations. . . DESCRIPTION. OF--LOOP . . . 1.1.1 Function ' . The function of this loop is to. measure and indicate the level of ' material -and to alarm on high level., ' . 1.1.2 System Performance Required .- + 2% . 1.1.3 Accomplishment of Function' ... - ' , . A diaphragm type level transmitter senses the liquid level in the tank and sends a proportional 3-15 psig air signal to a 0-100% indicator on the panel and also one near the transmitter. This signal is,also sent to a pressure switch which actuates an alarm on high level. PCB-ARCH-EXT0373592 INSTRUMENT FUNCTION OUTLINE TITLE #2 INTERMEDIATE STORAGE .LEVEL SHEET 2. OF 5 DEPARTMENT 246 LOOP NUMBER 329-1 CLASSIFICATION -J.,I Ar.3 2-1-1 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A.' Transmitter A. Transmitter Location: Bottom of tank, east side. Air Supply: Output: . Scale: Span: Sp.Gr.: . 20 PSIG 3-15. PSIG 0-100 Linear 485" W.C. 1,25 Foxboro 13FA1 Range: Output: 0-344" W.C. 3-15 PSIG IPMO - 001 ' B. Pressure Switch B. Mer'co.id Switch 'Mercoid AP-153-R36 Location: In furnace field cabinet Set Point: 14.5 PSIG on Rise Set Point:. 14.5 PSIG (For high level alarm ) PCB-ARCH-EXT0373593 PCB-ARCH-EXT0373594 Xi\JS j. j\uixull' Jl1 1 UNv.-iiU'i QU l'L a U I..I L 4*1 .L , Util X 240 TITLE \\2 INTERMEDIATE STORAGE LEVEL. . SHEET 4 .OF____________ ________ 5________ `WRITTEN BY _______ , DATEREV.BY LOOP NUMBER-3 2 9-1 CLASSIFICATION LIA-329-1 DATE REV.NO. 3.0 OPERATION OF LOOP . . . 3.1 NORMAL OPERATION ' 3.1.1 Start-Up Instructions None 3.1.2 Shut-Down Instructions It may be necessary to shut down either the column (if the level is low) or the continuous chlorinators (if the level is high) before any work can be done to the transmitter. The tank must be completely empty before the transmitter can be removed. . 3.1.3 Normal Operating Instructions ..The level will be between 20% and 90%. 3.1.4 Routine Checks Required . Check the level frequently so the tank don't go empty (this' would cause a loss of vacuum on the column and an emission), also so the tank doesn't run. over. . i PCB-ARCH-EXT0373595 INSTRUMENT function outline DEPARTMENT________ 246 TITLE #2 INTERMEDIATE STORAGE LEVEL LOOP NUMBER '.329-1 SHEET. 5 ' OF 5 ' CLASSIFICATION LI A-3 2_9-l WRITTEN BY_. , DATEREV. BY__DATE ' REV. NO . 3.2 INTERLOCKS . . . . ' . None ' . 3.3 ABNORMAL OPERATIONS . 3.3.1. Air Failure . . Air failure to the loop will cause loss of indication. . 3.3.2 Power Failure . Loss of power will cause alarm to be inoperative. . NOTE: 'N2 is used to blanket the tank when making MONO. The zero of ' level transmitter should be set after N.n blanketing system is in ' operation. N2 enters and is regulated @ 4" W.C. and relieves.at 7" W.C. . Since the low side is not compensated, it will be - ' necessary to.run the zero elevated @ almost 5" W.C. , PCB-ARCH-EXT0373596 INSTRUMENT FUNCTION OUTLINE , DEPARTMENT 246 TITLE LIME SLURRY CONTROL VALVE TIMER LOOP NUMBER;352-1 SHEET . 1 . OF WRITTEN BY y, Brawlev t ' 1.0 NEED FOR LOOP 5 DATE r?/1 B/72~ REV. BY '* ' ` . .. . CLASSIFICATION KIC-352-1 DATEREV.NO. Allow lime slurry to bo. mixed on a semi-continuous basis with the crude Aroclors on the way to intermediate'storage. Lime mixing on . this' basis is necessary to neutralize essentially all the HCL dissolved' in the Aroclors prior to charging the Aroclors to the still . pot. This in turn is required, to' minimize the potential of chloride stress corrosion cracking in.the 316.S.S. column. 1.1 : DESCRIPTION OF LOOP .. - 1.1.1 Function .. . , The function of this loop is to control the flow rate by lime slurry addition to the product going to intermediate storage. . 1.1.2 ' System Performance Required' + 2% ' . . ' 1.1.3 Accomplishment of Function ' The flow rate- is'adjusted by two timers mounted on the panel which , control the amount of time a pneumatic, actuated ball valve is open and how long it" is. closed each cycle. The valve is continuously cycled open and closed after the open-close selector switch is turned to "open". PCB-ARCH-EXT0373597 INSTRUMENT FUNCTION OUTLINE TITLE LIME SLURRY CONTROL VALVE TIMER SHEET 2__________________ OF 5 DEPARTMENT 246 ' LOOP NUMBER 352-1 CLASSIFICATION KIC-352-1 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA ' ' MECHANICAL DATA A. Flow Valve Location: On stair landing, north' of #9 chlorinator on 2nd level B. Solenoid Valve . Location: On stair landing, north of #9 chlorinator on 2nd level by the flow valve. - C. Timers (2) . 1 for seconds open 1 for minutes closed Location:' On panel board in control room. A. Flow Valve ' ' Hills McCanna F602CS PCS . 1/4" Chrom. Pit. Ball - Valve Operator = Ramcon Model R35FS Air to Open B. Solenoid Valve ASCO 8317A 35 110 V 11 Watts C. ATC Timer 305D PCB-ARCH-EXT0373598 instrument function outline . TITLE LIME SLURRY CONTROL VALVE TIMER , SHEET 3 OF 5 WRITTEN BY . DATE REV.BY DEPARTMENT 246 LOOP number 352-1 . ' CLASSIFICATION KIC-352-1 DATE REV.NO. PCB-ARCH-EXT0373599 INSTRUMENT FUNCTION OUTLINE ' . DEPARTMENT246 ,, TITLE LIME SLURRY 'CONTROL VALVE TIMER .. LOOP NUMBER - 3 52-1 SHEET 4 WRITTEN BY I ' ' OF 5 . ________ DATE______ 3.0. OPERATION OF LOOP . . ' REV. BY ' 3.1 NORMAL OPERATION' .. 3.1.1 Start-Up Instructions CLASSIFICATION KIC-352-1 DATE REV .NO. ' ' . . ' . , Continuous chlori'nators should be running, set the timers and turn ` the selector switch to "open". . ' -3.1.2 'Shut Down Instructions Set the selector switch on "closed". 3.1.3 Normal Operating Instructions . . ' . ' . The.light.on,the panel board will be- on.. The timers working and the .level in the. lime slurry tank going down at a steady rate. ' 3,1.4 Routine Checks Required ' . Check the above at least 4 times a shift to be sure the necessary percent of slurry is being added. . ' PCB-ARCH-EXT0373600 INSTRUMENT FUNCTION.OUTLINE DEPARTMENT 24 6 TITLE t.TMF. SLURRY CONTROL VAUV SHEET 5 WRITTEN BY OF 5 . DATE . REV,BY LOOP NUMBER' 352-1 CLASSIFICATION KIC-352-1. DATE REV.NO. 3.0 OPERATION . . ' . . 3.1 NORMAL OPERATION' . . . . .The slurry timer is turned on during the time material is going to intermediate storage from the chlorinators. . 3.1.1 Start-Up. Instructions . . Set "open" timer for number of seconds valve is to be open (0-6 sec.) . Set "cycle" timer for number of minutes.valve is to be closed (0-6 min.) Turn selector switch to "open" position. 3.2 .INTERLOCKS' 3.3 ' ABNORMAL OPERATIONS ' . ' ' ' 3.3.1 Air Failure : ' ' . Upon air- failure valve will fail closed. . / - 3,3.2 Power Failure . . . . Upon power failure valve will fail closed. PCB-ARCH-EXT0373601 INSTRUMENT function outline . TITLE #2 & #3 ABSORBERS FLOW CONTROLLER ' SHEET 1 OF4 WRITTEN BY V. Brawlev DATE s/23/72 BY DEPARTMENT246 LOOP NUMBER' 541-1 CLASSIFICATION FICA-541-1 DATE REV.NO. 1.0 NEED FOR LOOP . . 1.1 This loop is needed to insure proper flow,of aroclor to. the absorbers. DESCRIPTION OF LOOP .. 1.1.1 Function of Loop . ' ' ' . The function of this loop is to control the flow of material into the absorbers and to sound an alarm if flow is too low. . 1.1.2 . System Performance Required . ' . The flow rate should be maintained'+ 1/2 GPM of set point. Accomplishment of Function' . " The flow rate is sensed by a differential.pressure transmitter across an orifice plate in the line. The.transmitter sends a . 3-15 psig air signal, to a flow indicating controller. The controller compares this signal to a set point and sends a 3-15 psig air signal to a control valve to compensate for.variation from set point. The transmitter also sends an air signal to a pressure switch which activates an alarm on low flow. . . . . / PCB-ARCH-EXT0373602 INSTRUMENT FUNCTION OUTLINE TITLE #2 & #3 ABSORBERS FLOW CONTROLLER SHEET ___ 2 ' . OF_ .4 DEPARTMENT . LOOP NUMBER CLASSIFICATION 2 46_________ 541-1 , FICA-541-1 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA ' MECHANICAL DATA ' A. FT-541-I Differential Press. Trans Location: Ground'level, NE of .Tank 530.- , Supply: 20 psig Output: 3-15 psig ' Flow: 0-15 gpra Span: 0-100" W.C. B. FIC-32 Flow Indicating Controller Location: Panel A. Foxboro Integral Orifice Diff. Bress Trans. W/Piped & Mt'd. Air Set W/Gauge . " -Model #: 13A-HS2 Range: 0-200 to 0-850" W.C., Calibrated Range: 0-400" W.C. Body: 316 S.S, . Process Conn: 1/2" NPT . - Orifice: .350" Bore .316 S.S. . Accuracy: 1/2% ' ' . Serial #: 1947915 ' Input: . Output: Action Supply: 3-15 psig 3-15 psig Inc. Input Dec. Output 20-psig 2. FV-32 Control. Valve-' Location: 14' level, NE of Tank 530 . , . . Input: 3-15 psig Action: Air to Open Fails Close -. IPMO: 001 . B. Fisher & Porter Flow Ind. Controlle Model #: 51-1351 ABEC ' . - ' Range: 3-15 psig sq. rt.- . Scale: 0-100 sq. rt. Prop. Band: 2-500% ' Reset Rate: .02 to 5 min. ' . Accuracy: 1/2% . .IMO: .' ' IPMO: 165 - C. Fisher Gov. Control Valve #667-BF D. ' FSA-32 Pressure -Switch Location; Panel Input: . 3-15 psig Set Point: 33% . FCT: Lo. Flow Alarm-at 3.3 GPm . ^ SPOT Contact/115 V. , 10A Actuator Size 30 Travel 3/4" ' 1" 15 0# Fig. 316- S.S. Body - Packing Set 1U2546-0101 . 3/4" 316 S.S. Trim,-Micro-Flute Valve Plug 2J7335-3507 . : Valve Ring 1R1262-3507 Teflon Packing, Skirt-Top Guiding Spare Valve S.C. 07-75671 IMO: 45 IPMO: 126 . . Serial #.: 4435034 ' . ' .. - . D. Barksdale Pressure Switch #DIT-H18^ Range: 0-18 psig . Bronze Diaphragm: 1/4" IPS Conduit Conn: 1/2" NPS Setting Trips at 4.08# on drop t Stores Code; 44-73246 PCB-ARCH-EXT0373603 f PCB-ARCH-EXT0373604 INSTRUMENT FUNCTION OUTLINE X " ` - ~ -...................... .....r - - n ' - 1" TITLE #2 & #3 ABSORBERS FLOW CONTROLLER DEPARTMENT 246' -----------"------------------- *................ ................. LOOP NUMBER' 541-1 SHEET. 1TEN BY OF DATE REV. BY CLASSIFICATION FICA-541-1 DATEREV. NO . 3.0 OPERATION OF LOOP 3.1 NORMAL OPERATION . . ' 3.1.1: Start-Up Instructions , . The column should be running, on 1016 , and ready to cut forward from total reflux. ' . . . 3.1.2 Shut-Down Instructions ' . The column must, be on total relfux, or down. . 3.1.3 Normal Operating Instructions The controller set point will be about 95 (14 gpm) during the 1st part of a run. ''After the reflux ratio changes the set point will be about 65 (9 gpm) on the controller. The flow is acutally split to send an equal amount of product through the two absorbers and flow is balanced sending a equal amount of flow through the two rotometers. . 3.1.4 Route Checks Required 3.2 3.3 Check the level in the receiver frequently to hold it at 20%. Check :the rotometers at least 2 times a shift to keep the flow equalized ''through the absorbers. INTERLOCKS AND ALARMS '. ' . If the flow drops to about 3 gpm, the alarm will sound on the , annun ciator and the-window marked "low flow #2 & 3 absorber". ABNORMAL OPERATION . . . 3.3.1 Air Failure .... If the air fails, the valve will close and the alarm will sound. 3.3*2 Power Failure . If. the power fails, the alarm w i 1 l~'->n o.t^'S chin r?. i 3.3.3 Other None PCB-ARCH-EXT0373605