232
CHAPTER 15
1965 Guide And Data Book
Table 8 .... Alkalinity Interpretation for Natural Waters
? Aft* ,
Catowli
Bicarbonofe
<0 0 *M Alkk -2 P Aik "JM Aik (=2 P Aik
(-M Aik >|M Aik* = 2 (M Aik--P Aik)
' -M Aik = M Aik --2 P Aik
0
0
* Tmtad vital oe]j. Hyditndda smait.
r P Aik
AUnlisitr.
* M Aik TM Methyl Onego (Tote!) Alialinty.
Fr*o Draxido
0 0
content of the water. The hardness, particularly the calcium
is one of a group of factors which influence scale formation. Alkalinity is a measure of the capacity of a water to neu
tralize strong acids. In natural waters, the alkalinity will al most always consist largely of bicarbonate, although there
may also be some carbonate present. In treated waters, hydroxide, phosphate, and other constituents, if present, will
be included to some extent in the alkalinity measurement. The alkalinity is another contributing factor toward scale forma
tion. In water chemistry a rough qualitative interrelationship provides that factors which tend to increase scale formation also tend to decrease corrosion, and vice versa.* '
Alkalinity is measured using two different end-point in
dicators. The phenalphihalein alkalinity (or P alkalinity),
roughly speaking, measures the strong alkali present.'The
methyl orange alkalinity (or M alkalinity), also railed the
total alkalinity, measures all of the alkalinity present in the
water. Note carefully that the total alkalinity includes the
phenolphthalein alkalinity. For most natural waters, in
which the concentration of phosphates, borates, and other
noncarbonate alkaline materials is small,'the actual chemical
species present may be estimated from -the two alkalinity
measurements, as shown in Table 8.
pH is often confused with alkalinity or acidity. Such con-
fusion may "be avoided by keeping in mind that the pH-is
essentially an intensity factor (strength of acidity or alkalinity
present), whereas the ppm of alkalinity or acidity is a quan
tity measurement (amount of alkalinity or acidity present).
A rough parallel to this may be seen in a hydraulic system in
which pounds per square inch is an intensity factor and 'gal
lons is a quantity factor.
Generally, lower pH- waters tend to be more corrosive and
higher pH waters tend to be more scale forming, although
many other factors affect both properties.
1 "
' The total dissolved solids content of a water will also affect
both corrosion and scale formation. Higher dissolved solids
tend to increase scale formation. The effects upon corrosive
tendencies are ambivalent Because low solids' waters have
-less tendency to deposit scale, they-are-generally corrosive.
On tiie other hand, a high solids water which is nonscaling
will tend to produce-more intensive corrosion because of its high conductivity:
: Sulfates also contribute to scale formation in high calcium
--waters. Calcium sulfate scale, however,'forms only at much
higher concentrations than the more common calcium:car
bonate scale. High sulfates also contribute toward increased
corrosion because of their high' conductivity. .
Chlorides have no effect upon scale formation but do con
tribute toward corrosion because of their conductivity and
because the small size of the chloride ion permits the con
tinued flow of corrosion current when surface films are poroua.
- Chlorides are a useful measuring tool in evaporative sys
tems. Virtually all other constituents in the water increase or
decrease as a result either of the addition of common treat ment chemicals or of- chemical changes which take place in
the normal operation of the water- system. With few excep tions, chlorides are changed only by evaporation, so that the
ratio of chlorides in a water sample from an operating system to those of the makeup water provides a measure of the num
ber of times that the water system.
been concentrated in the
Sodium, potassium, and nitrate contribute to corrosion problems oidy through their conductivity.
Iron can form heat-insulating deposits by precipitation'of
iron hydroxide. Technically, this b not a scale, but a waterformed deposit.
Silica can form particularly hard to remove scales if per mitted to concentrate sufficiently. Fortunately, sflicate scales are far less common than others.
In addition to dissolved solids, waters, particularly un purified waters from surface sources or those which have been circulating in open equipment, frequently contain sus pended solids, both organic and inorganic. Organic matter in surface supplies may be present' as colloidal solutions. Nat ural coloring matter b usually in thb form.
Biological Characteristics. Bacteria, algae, and fungi are present in many waters and their growth can cause operating problems. The usual bacteriological examination of water for sanitary purposes establishes the probable presence or ab sence of pathogens. In cooling systems, nonpathogenie or
ganisms are more important as causes of operating difficulties Living organisms are rarely a problem in heating systems because of the sterilising action of higher temperatures.
Bacteriological tests of the water are seldom satisfactory diagnostic tools for biological problems in industrial systems. Examination of deposits taken from the equipment b gen
erally more useful in the selection of proper preventive meas ures.
Heating and Cooling Water Systems
In order to evaluate the probable effects on a system of a water supply or, more important, the boiler water or cir culating water, the water treatment specialist needs, in addi tion to the actual or anticipated water analysis, much addi tional information. This includes data on the size, construc tion, operating' pattern, and other characteristics of the sys tem. Therefore, a review of the various types of water-con taining systems utilized for heating or cooling, together with some of tire changes occurring in these systems that influence water-caused difficulties, would be helpfuL
All heating and cooling systems, of course, involve a tem perature change and thb influences the rates at which watercaused problems can develop.
In steam heating systems, the concentration of dissolved solids in the boiler water will increase as boiler water b con verted to steam. In the ordinary space heating system thb change b limited because substantially all of the steam is, or should be, condensed and returned to the boiler. On the other hand, the nature of toe water changes taking place with in the boiler ore drastically altered if the''percentage of condensate returning to the boiler b reduced for any reason. The condensate itself has characteristics quite different from those of the boiler water, because -it b substantially free of any dissolved solids and creates different problems when there b an opportunity to dbsolve air or carbon dioxide.
In hot water hpAting and other closed circulating systems, there should, in theory, be no water-caused problems because there should be virtually no mskeup water and no opportu nity for significant changes in the composition of the water within the system. Experience has shown, however, that a
k
('Corrosion and Deposits
233
Hibstantial proportion of such systems do not behave in'ao ^rdance with tins theory1* and the need for water treatment to both ordinary hot water heating systems and high tem perature hot-water systems b now commonly accepted by
^frijThot water heating systems, closed cooling systems
(chilled water, chilled-hot water, brine, , or glycol) perform differently in practice than in theory. As a result, treatment of the circulating water or solution in these systems', b de-
^^Condensera and other heat exchangers in refrigeration and
air-conditioning systems may be cooled by water passing
through tiie equipment and going to waste. In such cases,
the water-caused, problems will be directly related .to the
^Komirid composition of the cooling water. As a result of in creasing water shortages, such once-thfough cooling b be
coming less common and b being replaced by open'circu
lating systems which use cooling towers, evaporative con
densers, or spray ponds. In these, the makeup water composi tion b drastically changed as a result of evaporation, aeration,
and other
and physical processes which depend upon
the contaminants present in the air to which the water b
exposed in the open circuit. Humidification and dehumidification equipment presents
several types of. water problems. During humidification,
water circulating in the equipment b subjected to essen
tially toe same exposure conditions and composition changes
as those which take place in open circulating systems. Dur
ing dehumidification, however, there b a combination of
dilution, which may result in a water as low in dissolved
solids as b steam condensate, plus exposure to aeration and
the scrubbing of contaminants from the air.
-
Materials 'of Construction. The seriousness of corrosion in
heating and cooling systems will depend, in part, upon the -
nature of toe materials of construction present, their degree
of proximity,: their relative areas and other physical factors,
as well as the chemical composition of the water.*
Ferrous metab comprise the largest tingle group of ma
terials used for toe construction of heating and cooling sys
tems. Steel is used for structural elements, boiler dnims.and
tubes, condenser shells, and many other components. Cast
iron b used for low pressure boilers, convectors, and con
denser heads, etc. Galvanized steel b a common component
of the smaller sizes of cooling towers, evaporative condensers,
humidifiers and dehumidifiers. Various alloy steels are also
used in these systems.
i
Copper tubes are widely used in air conditioning and-re
frigeration condensers and in heating system exchangers, but
tubes of modified brasses such as admiralty, stainless steel,
mild steel, aluminum, and cupronickel are-also employed.
Tube sheets may be made of steel, Muntz-metal, or other alloys,
Nonmetallic materials of construction are used as well,
large cooling towers are usually constructed of wood and
smaller cooling towers may include a considerable amount of
asbestos-cement tiding or fill. Various plastics are being used
more extensively in the construction of smaller cooling towers.
^Water-Caused Troubles
The operator of a heating or cooling system becomes aware of water-caused troubles with the appearance of one or more of three symptoms, each of which may *lsn be produced by causes other than the water. Several different conditions may act together in'the production of any'given symptom. ' "
The first of jtoese symptoms b a reduction in heat transfer rate. In tob case, the formation of an insulating deposit on a beat transfer surface generally significantly reduces the cool-
ing or heating capacity of the equipment. The second symp tom b reduced water flow, which results from a partial or complete blockage .of pipe lines, condenser tubes, or other openings. The third symptom b damage to, or destruction of, the equipment. Thb may result from corrosion of metab or deterioration of wood or plastics. It may also be caused by excessively rapid wear rates of moving parte, such as pumps,
shafts, or seals. Corrosion contributes to all three symptoms. Heat transfer
rates can be reduced and water flow blockages can be created by deposits of corrosion products. The damage or destruc tion of equipment b most often the result of metallic cor rosion and the somewhat -parallel phenomenon., of. wood
delignification. ' Scale formation also contributes to all three symptoms. Even a small buildup of scale on a heat exchange surface will reduce heating or cooling capacity. Further buildup wifi' re duce water flow.. Finally, scab buildup in boilers may con tinue until it reaches the point at which heat transfer b so low that toe metal overheats permitting rupture of tubes under
toe operating pressure. Scab particles can also accelerate.the
wear of moving parts. Biological growths, such as slime, can act as insulators to
reducecoolingcapacity. Algaegrowthsoften accumulate to the point at which they interfere with water flow in cooling towers. The poultice effect created by accumulations of organic mat ter can cause localized corrosive attack resulting in prema ture equipment failure. Wood destruction, too, can occur as a
result of fungus action. . Suspended solid matter, such as dirt scrubbed from the air or finely divided mill scab, can also contribute to all three symptoms. Deposits of such material can reduce heat trans fer or reduce water flow depending upon where they accumu late. Like local deposits of organic matter, such dirt deposits tend to localize corrosion and, of course, suspended solids
cause rapid wear of moving parts.
Water Treatment
.!
General Considerations. The complexity of water-caused
problems and their correction in heating and cooling systems
makes it important to obtain toe advice of a water treatment
specialist as early as possible in the design stage of any system
and to follow his advice regularly thereafter during'design;
construction, and operation. Often, factors considered to be
irrelevant by the byman' are actually quite important in
securing effective' protection against operating troubles.- The
improper use of water treatment chemicals can even result in
the development of problems more serious than'those which
would have occurred had no treatment at all been used.
More than one solution b frequently possibb for toe same
water treatment problem. The sebetionfrom among various
alternatives may be dictated by economic considerations or by considerations such as availabb space or labor. In ahy^,
event, it cannot be emphasized too strongly that toe choice'
of a water treatment program for any given system should
be made only after due consideration of the various factors mentioned in thb chapter. It b important to carry out the
selected treatment program diligently. No water treatment
program can be any more effective than the consistency and
control with which it b applied.
J
The use of chemicals for water treatment, as for other ap^
plications, involves certain safety considerations with which
building, operating, and maintenance personnel are-not or
dinarily familiar. It b important that the potential safety-
hazards associated with any particular water treatment ' chemical or program be well understood beforehand, thatsuit-
abb safety rubs be formulated, that appropriate safety
H
J]