Document Dv5N8zZ2LOO79xZrRNKKb7GQ5
420
CHAPTER 30
1959 Guide
Panel Hearing
421
SCRATCH COAT
Air-Heated Ceilings, Walls, and Roars
Several methods have been devised to warm the interiot
room surfaces by circulating heated air through passages
ivhmrl tbp*a surfaces. In some cases, the heated air is re
circulated in a closed system. In others, all or a part of the
air is
through the room on its way back to the furnace
to provide supplementary heating and ventilation.' Figs. 5
and 6 indicate two common types of construction. Care
must be exercised to assure compliance with any building
codes that might apply. (See also section on Warm Air
Ceiling Panel Systems in Chapter 18.)
Electrically Heated Ceilings, Walls, or Floors
Several different forms of electric resistance units are
available for heating the interior room surfaces. These
include: (1) resistance cables that may be embedded in a
manner gimilftr to hot water piping in concrete or plaster;
PLASTER CEILING BELOW JOISTS
(2) prefabricated electric heating panels to be attached to room surfaces; and (3) electrically heated fabrics or other
Fig. 2 .... Coils in Plaster Above Lath
Fig. 4 .... Coils in Floor Slab on Grade
materials for application to, or incorporation into, finished room surfaces. Figs. 7 and 8 indicate two methods of in stallation. The constructions of electric panels for ceilings,
are installed below the lath. Generally, the surface tempera
walls, and floors are described in greater detail in Chapter
Fig. 9 .... Heat Output by Radiation
ture of plaster panels should not exceed 120 F, and this is the coils. It is recommended that insulation be used to reduce
17, Electric Heating.
usually met by limiting the water temperature in the pipes the perimeter and reverse losses. Fig. 4 shows the application
or tubes in contact with the plaster to a maximum tempera ture of 140 F. Insulation should be placed above the coils to reduce the reverse loss which is the difference between the heat supplied to the coil and the net useful output to the heated room.
In order to protect the plaster installation and to assure
of pipe coils in slabs resting on grade. Coils should be em
bedded completely and should not rest on an interface. Any supports used for positioning the heating coils should be non-
absorbent and inorganic. It is suggested that reinforcing steel, angle iron, pieces of pipe, or stone concrete mounds be used.
No wood, brick, concrete block, or similar materials should be used for support of coils. Generally, a waterproofing layer is desirable to protect insulation and piping.
HEAT OUTPUT FROM PANa SURFACES
A heated panel transfers heat to a room by convection and radiation. In the following paragraphs,- the two transfer mechanisms are first considered separately and then com bined to facilitate design calculations.
T, -- mean radiant temperature of all unheated surfaces, Fahrenheit, absolute.
F *= the configuration factor (dimensionless). F4 " the emissivity factor (dimensionless).
A combined configuration and emissivity factor - for a
proper air drying of the plaster, it is recommended that no
. b. Where the coils are embedded in structural load support
Radiation Transfer
simple, box-like room- in which there is a uniformly heated
heat be applied to the panels for two weeks after all plaster ing work has been completed. When the system is started for the first time, the water supplied to the panels should be at a temperature not more than 20 deg above the pre vailing room temperature at that time (but not in excess of
ing slabs above grade, construction codes may affect their position. Otherwise, the coil piping is installed in the same manner as described for slabs resting on grade.
c. A warm-up and start-up period for concrete-panels should be similar to that outlined tor plaster panels.
The radiation transfer can be evaluated by means of the Stefan and Boltzmann equation:
-()']
0)
calling, floor, or wall, all other, surfaces are at another tem perature, and all surfaces are perfectly diffusing is given by Hottel* as:
(2)
90 F). Water should be circulated at this temperature for about two dayB. Then the water temperature should be
where *(i
increased at a rate of approximately 5 deg increase per day to
H 140 F.
gr " heat transfer by radiation, Btu per (hour) (square where .
During the air-drying and preliminary warming-up periods, adequate ventilation should be provided to carry off moisture from the panels. No paint or paper should be applied to the panels until these periods have been completed. No paint or paper should be applied while the panels are being operated.
foot). T, -- temperature of panel heated surface, Fahrenheit,
absolute.
Ft = combined configuration and emissivity factor. Fi-t * = view factor ** 1.0. t\ and e* a emissivities of the surfaces. Ai and At = areas of the surfaces.
After paint and paper have been applied, a further shorter
warm-up period, similar to that for the first time starting, is
also recommended,.
Fig. 5 .... Warm Air Plaster Ceiling Construction
i Embedded Piping for Walls
1 Although not so universally used as ceiling panels, wall panels mav be constructed by any of (he methods outlined
| for ceilings.'
s Embedded Piping for Floors The construction for piping embedded in floors will depend
! upon whether (a) the floor is laid on grade, or (6) the floor is above grade.
Fig. 7 .... Ejectric Heating Cables in Plaster
In practice the emissivity of conventional, non-metallic, non-reflecting surfaces will be found to be about 0.9. When this emissivity is used in Equation 2, the combined factor will be found to be about 0.87 for most rooms. Substituting this value in Equation 1, the constant becomes about 0.15 and the equation can be rewritten:
t, + 460V YAUST + 460
\100 )
100
where
tp temperature of panel surface, Fahrenheit. AUST - area-weighted average temperature of unheated
7 a. Both ferrous and non-ferrous pipe and tube are used in
floor slabs which rest on grade. The coils are constructed as
either sinuous-continuous pipe coils, or arranged as header
coils with the pipes spaced from 6 to 18 in. on centers. The
coils are generally installed with IK to 4 in. of cover above
Fig. 6 .... Warm Air Floor Panel Construction
Fig. 6 .... Prefabricated Electric Panel
surfaces in room, Fahrenheit.
The actual radiation transfer in a room may be somewhat different from that given by Equation 3 because of nonuniform temperatures, irregular room surfaces, variations in