Document Dv0ExOyoME9xgg6o3gaKj88bQ
PORTABLE ELECTRIC TOOLS
Inspection Checklist
GENERAL
Low voltage equipment used in tanks and wet areas7
Tools well maintained7 Motors in good condition7 Approved tools used in explosive
atmospheres7 Tools left where they cannot fall7
CORDS
Insulation and plugs unbroken7 Cords protected against trucks and oil7 Cords not in aisles7
GROUNDING
Ground wire fastener in safe condition7 3-wire plug extension cord (if a 3-wire
tool)7 Ground wire used7 Defects or minor shocks reported7
GUARDING
Guards used on grinders and saws7 Movable guards operate freely7 Eye or face protection worn7
Fig 32-18 -- An inspection checklist card can be used for portable electnc tools Such a card en courages workers to inspect equipment before and after use More specific cards or tags simplify the prompt recording of defects and result in better
maintenance records
resultant degree of hazard The current is regulated by the resistance to the ground of the body of the operator and by the conditions under which he is working It is possible for a tool to operate with a defect or short in the wiring, and the use of a ground wire protects the operator under all conditions
Insulating platforms, rubber mats, and rub ber gloves provide an additional factor of safety when tools are used in wet locations, such as m tanks or boilers and on wet floors
Low voltage of 6,12,24, or 32 volts through portable transformers will reduce the shock hazard in wet locations Standing orders should be issued to supervisors and employ
ees to use low-voltage equipment on work in such locations Portable low-voltage trans formers may be provided
Electnc tools used in wet areas or in metal tanks expose the operator to conditions favor able to the flow of current through his body, particularly if he is wet with perspiration Most electnc shocks from tools have been caused by the failure of insulation between the current-carrying parts and the metal frames of the tools Only tools listed by Underwnters' Laboratones, Inc, should be used
Double insulated tools. Protection from electnc shock, while using portable power tools, has been descnbed as depending upon third wire protective grounding "Double insulated" tools, however, are available which provide more reliable shock protection with out third-wire grounding An amendment to the National Electrtcal Code permits unrestncted application of the "double insulation" idea Tools m this category are permanently marked by the words "double insulation" or "double insulated " Units designed to this category which have been tested and listed by Underwriters' Laboratones, Inc, will also em ploy the use of the UL symbol Many U S manufacturers are also using the symbol
to denote "double insulation " This symbol is also being widely used in most European countnes
Conventional electnc tools have a single layer of functional insulation and are metal encased For small-capacity tools, "double insulation" can be provided by encasing the entire tool in a nonconductive matenal which is also shatterproof The switch is also non conductive, so that no metal part comes in contact with the operator
Large capacity electnc tools require a more ngid design m order to provide for greater stress requirements where more power and high-torque geanng are involved Doubleinsulated tools with metal housings have an internal layer of protecting insulation com pletely isolating the electncal components
965